Removal of Compressor
Step
3
Release the clamp with
pliers to detach the
compressor lead wires.
4
Remove the putty.
Before working, make
sure that the refrigerant
gas is empty in the circuit.
Be sure to apply nitrogen
replacement when
heating up the brazed
part.
Remove the 2 nuts of
5
the compressor.
Heat up the brazed part
6
of the discharge side
and disconnect it.
20
Procedure
(R5304)
(R5305)
Warning
Be careful not to get yourself
burnt with the pipes and other
parts that are heated by the
gas brazing machine.
Warning
If the refrigerant gas leaks
during work, ventilate the
room. (If the refrigerant gas is
exposed to flames, toxic gas
may be generated.)
Warning
Since it may happen that the
refrigerant oil in the
compressor catches fire,
(R10257)
prepare wet cloth so as to
extinguish fire immediately.
Caution
From the viewpoint of global
environment protection, do
not discharge the refrigerant
gas in the atmosphere. Make
sure to collect all the
refrigerant gas.
(R5308)
Si00-875
Points
Removal Procedure

Hide quick links:

Advertisement

loading