Siemens SICLOCK PCON Operating Instructions Manual page 18

Table of Contents

Advertisement

Outputs
Electrical outputs:
Short-circuit strength:
Connection:
Optical output:
Connector:
Display:
Alarm output
Alarm monitoring time
Display:
Dimensions, weight, and environment
Dimensions (WxDxH):
Weight:
Ambient temperature:
Relative humidity:
®
SICLOCK
PCON
Operating Instructions, 04/2012, A2B00056366E-01
RS422, RS232, TTY/20mA isolated
Voltage output 24 VDC/0.8A
(Supply voltage 12 to 30 VDC, maximum current 800mA),
Voltage output 120 VDC/0.1A isolated
(Supply voltage 24 to 120 VDC, maximum current 100mA)
Permanently short-circuit-proof and monitored for temperature
Terminal strip X2
Version 2XV9450-1AR63-1SA2 multimode FOC 820nm
BOFC (ST-compatible with IEC 874/10)
Yellow LED
Relay contact: 1 changeover contact
DC: 120V 1A/30W
AC: 120V 1A/30W
3 secs or 3 min
Red LED
100x70x135mm
460g
Operating mode: 0°C to +50°C
Storage: -25°C to +85°C
Operating mode: 10% to 95% (no condensation)
Storage: 10% to 95%
7-18