Connecting; Rs232 And Rs422/485 Interface Of The Communication Module - Siemens SIMATIC ET 200SP Manual

Cm ptp communication module
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Connecting

3.1

RS232 and RS422/485 interface of the communication module

Pin assignment
Table 3- 1
RS232 connection
Terminal assignment of the
communication module
BaseUnit
Front view
CM PtP communication module (6ES7137-6AA00-0BA0)
Manual, 01/2013, A5E03790792-01
Pin
Designation
1
TXD Transmit Data
2
RXD Receive Data
3
RTS Request To Send
4
CTS Clear To Send
5
DTR Data Terminal Ready
6
DSR Data Set Ready
7
DCD Data Carrier Detect
8
RI Ring Indicator
GND Ground
9+10
Input/output
Meaning
Output
Transmit data
Input
Receive data
Output
Request to send
Input
Clear to send
Output
Data terminal ready
Input
Data set ready
Input
Received signal level
Input
Incoming call
-
GND functional ground
(isolated)