Maintenance - Fisher EZR Series Instruction Manual

Pressure reducing regulator

Advertisement

Type EZR
Shutdown for Both Single-Regulator and
Monitoring Installations
!
If pilot supply pressure is shut down
first, the downstream system may be
subjected to full inlet pressure.
  1.   I f the pilot setting must be disturbed, be sure to 
keep some tension on the spring. This will prevent 
trapping inlet pressure during blow down.
  2.   C lose the valves shown in Figure 3 or 4, in the 
following order:
        a. Inlet block valve
        b. Outlet block valve
        c. Control line valve(s), if used
3. Open the vent valves to depressurize the system.

Maintenance

Regulator parts are subject to normal wear and
must be inspected periodically and replaced as
necessary. Due to the care Emerson takes in meeting 
all manufacturing requirements (heat treating,
dimensional tolerances, etc.), use only replacement
parts manufactured or furnished by Emerson. Also,
when lubrication is required, use a good quality
lubricant and sparingly coat the recommended part.
The frequency of inspection and parts replacement
depends upon the severity of service conditions,
applicable codes and government regulations and
company inspection procedures. Table 12 lists various
regulator problems and possible solutions for them.
Type EZR Main Valve Trim Parts
Instructions are given for complete disassembly and 
assembly. The main valve body may remain in the
pipeline during maintenance procedures. Key numbers
are referenced in Figures 14 through 18.
avoid personal injury or damage to
property from sudden release of pressure
or uncontrolled gas or other process
fluid. Before starting to disassemble,
carefully release all pressures according
to the Shutdown procedure. Use gauges
to monitor inlet and outlet pressures
while releasing these pressures.
16
WaRnIng
CaUTIOn
ELaSTOMER/FaBRIC
MaTERIaL CODE
LOCaTE InK CODE
BETWEEn RaDII
MaTERIaL
InK CODE
ManUFaCTURER
Figure 8. Diaphragm Markings
Table 11. Diaphragm Imprint Codes
STYLE
MaTERIaL
Imprint Ink Mark Imprint Ink Mark
2
17E68
4
17E88
2
130
5
17E97
Converting a Fisher™ E-Body to Type EZR
Remove all trim parts from the main valve and clean
the body interior. Then follow procedure in Assembly
section to convert a Fisher E-body to a Type EZR.
When installing a Type EZR trim package
make sure flow is up through the center
of the cage and down through the cage
slots. In some cases, correct flow path
is achieved by removing the body from
the line and turning it around. If this is
done, change the flow arrow to indicate
the correct direction. Damage may result
YEaR OF ManUFaCTURE
THICKnESS
CODE
RaDIaL LOCaTIOn
TO LOCaTE
IMPRInT CODE
1
DOME IDEnTIFICaTIOn
THICKnESS InK
CODE (USE OnE
LOCaTIOn OnLY)
CODE
DIaPHRagM MaTERIaL
17E68 - Nitrile (NBR)
(low temperature)
17E88 - Fluorocarbon (FKM)
(high aromatic hydrocarbon
content resistance)
17E97 - Nitrile (NBR)
(high pressure and/or
erosion resistance)
CaUTIOn