CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . 1
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Unit Identification. . . . . . . . . . . . . . . . . . . . . . . . . . 2
Installation Precautions . . . . . . . . . . . . . . . . . . . . . 3
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Unit/Ceiling Coordination . . . . . . . . . . . . . . . . . . . . 8
Unit-to-Unit Connections . . . . . . . . . . . . . . . . . . . . 8
Unit Suspension . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Unit Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Principles of Operation . . . . . . . . . . . . . . . . . . . . . 30
Preliminary System Check . . . . . . . . . . . . . . . . . . 30
Initial Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Gaining Access to Control Area . . . . . . . . . . . . . 30
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . 31
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Checking for Obstruction . . . . . . . . . . . . . . . . . . . 31
Checking for Leaks . . . . . . . . . . . . . . . . . . . . . . . . 31
To Check Duct Pressure . . . . . . . . . . . . . . . . . . . . 31
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53370001-01
Installation Instructions
Printed in U.S.A.
Form 37HS-10SI
Moduline

SAFETY CONSIDERATIONS

Air-handling equipment will provide safe and reliable service
when operated within design specifications. The equipment
should be operated and serviced only by authorized personnel
who have a thorough knowledge of system operation, safety
devices and emergency procedures.
When installing this unit, observe precautions in the literature,
tags and labels attached to the equipment, and any other safety
precautions that may apply.
See Fig. 1 for Proposition 65 warning label.
!
WARNING: Cancer - www.P65Warnings.ca.gov
Fig. 1 - Proposition 65 Warning Label

INTRODUCTION

Moduline
®
units are integral diffuser air terminals. They are
available with various control devices for constant volume
and variable volume heating and cooling applications.
All units consist of a plenum, valve assembly and diffuser. A
typical unit is shown in Fig. 2. The plenum is thermally and
acoustically insulated and contains a distribution baffle to
provide well-distributed flow to the valve assembly. Figure 3
shows a cross section of a typical 37HS unit.
The valve assembly includes the bellows, which is inflated in
proportion to the duct pressure to regulate airflow to the
space. The bellows is constructed of durable polyurethane.
The assembly is connected at either end to
tubing.
The diffuser assembly is available in a 2-slot, one-way or 2-
way blow configuration. A 3-slot director diffuser is available
for use in cooling/heating applications.
The standard diffuser assembly is not removable. Control ac-
cess is made through a ceiling opening (e.g., a removable
ceiling tile) or nearby light fixture. The 37HS Moduline ter-
minal is also available with a removable diffuser for installa-
tion in non-accessible ceilings.
Fig. 2 - Typical 37HS Moduline Air Terminal
Pg 1
37HS
®
Air Terminals
-in. OD control
1
4
PLENUM
VALVE
ASSEMBLY
CENTER
SIDE DIFFUSERS
DIFFUSER
8-18
Replaces: 37HS-1SI

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 37HS Moduline and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Carrier 37HS Moduline

  • Page 1: Table Of Contents

    • GENERAL CHECKOUT ceiling tile) or nearby light fixture. The 37HS Moduline ter- SERVICE ....... . 30 minal is also available with a removable diffuser for installa- tion in non-accessible ceilings.
  • Page 2: Installation

    CAUTION To avoid damage to bottom units, do not stack units more than 8 high. Make sure that arrows on cartons point up. Fig. 3 — Typical 37HS Moduline Unit Cross Section DIGIT 1 2 3 4 6 7 8 9 10 11 12 13 MODEL NO.
  • Page 3: General

    All 37HS Moduline units can be installed as single units or in General an air series. Layout guidelines for proper installations can be The Moduline 37HS units are designed for installation in ® found in the 37HS Application Data book.
  • Page 4 37HS2 Plenum Dimensions 37HS2 Standard Diffuser Lengths Available (in inches) A 46.92 47.00 47.38 48.00 58.92 59.00 59.38 60.00 PLENUM SIZE (sq) 1.25 1.25 1.25 1.25 7.25 7.25 7.25 7.25 39.25 41.25 41.25 41.25 41.25 41.25 10 10 NOTE: Dimensions are in inches. Fig.
  • Page 5 EXTRUDED ALUMINUM EXTRUDED ALUMINUM EXTRUDED ALUMINUM 2-WAY BLOW ONE-WAY BLOW 3-SLOT Dimensions are in inches. REMOVABLE DIFFUSER (STEEL) REMOVABLE DIFFUSER (ALUMINUM) 37HS1 (100 cfm) Diffuser Options 37HS2 (200 cfm) Diffuser Options CEILING T-BAR STYLE AND WIDTH DIFFUSER LENGTH (in.) CEILING T-BAR STYLE AND WIDTH DIFFUSER LENGTH (in.) 23.00 47.00...
  • Page 6 EXTRUDED ALUMINUM EXTRUDED ALUMINUM EXTRUDED ALUMINUM 2-WAY BLOW ONE-WAY BLOW 3-SLOT Available Lengths (in.) of Accessory Return-Air Diffusers 37HS1 37HS2 37HS4 23.00 47.00 47.00 47.00 47.38 47.38 59.00 59.00 Fig. 10 — Accessory Return-Air Diffusers 37HS1,2 37HS4 A (in.) 47.00 NOTES: 48.00 1.
  • Page 7 Table 1 — Installation Accessories for 37HS Units ADAPTER CAP, Qty 12 Adapter Package No. For 6-in. round adapter 37AH900102 For 8-in. round adapter 37AH900042 For 10-in. round adapter 37AH900212 DIFFUSER BAFFLE, Qty 50 Used On Length (in.) Package No. 37HS1, HS2 37AH900072 37HS4...
  • Page 8: Unit/Ceiling Coordination

    Table 1 — Installation Accessories for 37HS Units (cont) END TRIM, Qty 50 Used on 37HS1, HS2 Color Package No. 2-Slot T-Bar* White 37CM900132 White 37CM900252 2-Slot Tegular† Black 37CM900352 Black and White 37CM900452 3-Slot T-Bar* White 37CM900142 White 37CM900302 3-Slot Tegular†...
  • Page 9: Unit Installation

    Fig. 13 — 37HS Unit Wire-Hung in a T-Bar Ceiling Unit Installation Fig. 14 — Installing T-Bar Mounting Bracket T-BAR CEILING T- BAR SUPPORT WIRE WEDGE NOTE: Moduline ® systems are normally designed with multiple (MAIN T- BAR MEMBER) unit and control arrangements within a single system. Proper system operation is dependent on careful adherence to the specified job layout.
  • Page 10 unit that has already been installed, and then into the next unit as the unit is being positioned in the ceiling structure. After alignment channel is installed, filler trim piece can be snapped into place. Fig. 18 — Inserting Alignment Channel into Unit Fig.
  • Page 11: Tegular Ceiling

    The 37HS Moduline terminal may be used in the center of a ers when used in recessed T-bar ceilings. The end trim piece 2 ft x 4 ft ceiling tile, or to replace a recessed T-bar member.
  • Page 12: Non-Accessible Ceilings

    NON-ACCESSIBLE CEILINGS discretion of the individual plasterer. One typical method, shown in Fig. 21, shows 2 Model Moduline ® 37HS air termi- Non-accessible ceilings include plaster and concealed spline nals installed. Wire hangers with eyebolts for leveling and ceilings. These applications require the 37HS unit equipped supporting the terminals are shown at the plenum ends.
  • Page 13 The installed Moduline ® air terminal pro- vides an excellent, secure installation. The 37HS Moduline matching dummy and return-air diffus- ers may also be independently suspended when applied in a plaster ceiling. Concealed Spline Ceiling In a concealed spline ceiling, the tiles butt together to provide the roomside appearance of a smooth, nondirectional surface.
  • Page 14 ® Fig. 23 — 37HS Moduline Units Installed in a Plaster Ceiling Fig. 24 — Typical Concealed Spline Ceiling Using 37HS Air Terminals (Details)
  • Page 15 Fig. 25 — Typical Concealed Spline Ceiling Using 37HS Air Terminals...
  • Page 16: Controls

    CLIP Table 2 shows the many control combinations available for VOLUME CONTROLLER 37HS Moduline air terminals and the control packages re- Fig. 26 — Variable Air Volume Controls quired for each set of functions. Figure 28 shows the installa- Installed on Unit tion of 3 control arrangements.
  • Page 17 SINGLE MASTER UNIT INSTALLATION MASTER UNIT WITH ONE SLAVE MASTER UNIT WITH 3 SLAVES Fig. 28 — Control Arrangements - Master Units with Slaves...
  • Page 18: Operating Sequences

    OPERATING SEQUENCES the bleed nozzle, increasing the bellows output pressure, thus closing the unit. System powered control for the Moduline terminal is shown ® A minimum airflow can be set on the volume controller to schematically in Fig. 29. prevent the unit from closing completely. The minimum air- System Powered Cooling flow adjustment restricts the volume controller seat from A high-pressure signal and a low-pressure signal, measured...
  • Page 19 Table 2 — 37HS Control Combinations CONTROL FUNCTION MODEL PACKAGES CONNECTION ARRANGEMENT REQUIRE 37HS1 37HS900003 37HS2 37HS900003 37HS4 37HS900003 SYSTEM POWERED CONSTANT VOLUME COOLING 37HS1 37HS900001 37HS2 37HS900002 37HS4 37HS900004 SYSTEM POWERED VARIABLE VOLUME COOLING DIFFUSER THERMOSTAT 37HS900003 37HS1 37CM901012 37HS900003 37HS2 37CM901012...
  • Page 20 Table 2 — 37HS Control Combinations (cont) CONTROL FUNCTION MODEL PACKAGES CONNECTION ARRANGEMENT REQUIRE 37HS900003 37HS1 37CM900152 37CM901012 37HS900003 37HS2 37CM900152 37CM901012 SYSTEM POWERED 37HS900003 VARIABLE VOLUME 37HS4 37CM900152 COOLING 37CM901012 SYSTEM POWERED WARM-UP WALL THERMOSTAT* 37HS900003 37HS1 37CM900192 37CM901992 37HS900003 37HS2 37CM900192...
  • Page 21 Table 2 — 37HS Control Combinations (cont) CONTROL FUNCTION MODEL PACKAGES CONNECTION ARRANGEMENT REQUIRE 37HS900003 37HS1 37CM900792† 37CM901992 37HS900003 37HS2 37CM900792† 37CM901992 37HS900003 37HS4 37CM900792† SYSTEM POWERED 37CM901992 VARIABLE VOLUME HEATING AND COOLING ELECTRIC CHANGEOVER WALL THERMOSTAT 37HS900001 37HS1 37CM900922 37HS900002 37HS2 37CM900922...
  • Page 22 Table 2 — 37HS Control Combinations (cont) CONTROL FUNCTION MODEL PACKAGES CONNECTION ARRANGEMENT REQUIRE 37HS900003 37CM900972 (NO) with 37HS900007 37HS1 (DA) 37CM900982 (NC) with 37HS900008 (RA) SYSTEM POWERED 37HS900003 VARIABLE VOLUME 37CM900972 (NO) COOLING with 37HS900007 PNEUMATIC 37HS2 (DA) PILOT VALVE FOR 37CM900982 (NC) HEATING/COOLING with 37HS900008...
  • Page 23: Control Installation

    CONTROL INSTALLATION Controls may be installed in the unit before or after the unit is hung or placed in the ceiling grid. However, if warm-up switches or changeover valves are used, the controls should be installed before the unit is placed in the ceiling structure. Refer to Table 3 for control packages and accessory identification.
  • Page 24 LOW-PRESSURE PORT FILTER BELLOWS CONNECTION HIGH-PRESSURE PORT VOLUME CONTROLLER THERMOSTAT PORT CAPPED HIGH-PRESSURE PORT Fig. 33 — Control Filter Installed Fig. 36 — Constant Volume Control Installed on Unit THERMOSTAT PORT SHIM INDICATOR ADJUSTMENT LABEL Fig. 37 — 37HS Control Connections Variable Air Volume Applications Remove the plugs from the high-pressure and low-pres- sure ports located at the control block of the unit.
  • Page 25 controller connected by a flexible offset tube. Verify that the offset is in the correct direction. See Fig. 38. Remove cap from thermostat port of volume controller. See Fig. 34. Pull shim down until released from thermostat port and then pull shim out from volume AIR FILTER controller body.
  • Page 26 Table 3 — Control Identification CONTROL PACKAGE, VARIABLE VOLUME, QTY 1 Used On Package No. FILTER/MANIFOLD DIFFUSER WITH FILTER 37HS1 37HS900001 THERMOSTAT/ EXTENSIONS ASPIRATOR 37HS2 37HS900002 37HS4 37HS900004 FILTER/MANIFOLD DIFFUSER THERMOSTAT/ ASPIRATOR VOLUME CONTROLLER DIFFUSER BAFFLE VOLUME CONTROLLER DIFFUSER BAFFLE SPRING CLIP ADAPTER TUBE 37HS1 VAV Control Package...
  • Page 27 Table 3 — Control Identification (cont) SYSTEM POWERED CHANGEOVER CONTROL, QTY1 Package No. 37CM900192 SYSTEM POWERED WALL-MOUNTED THERMOSTATS Thermostat Type Part No. Package No. DA (Cooling) HL08TE006 37CM901012 RA (Heating) HL08TE005 37CM901002 RA/DA (Heating/Cooling) HL08TE004 37CM900992 ELECTRIC WARM-UP/CHANGEOVER VALVE Voltage Package No.
  • Page 28: Airflow Adjustment

    AIRFLOW ADJUSTMENT Table 5 — Maximum cfm Through the Inlet Collar of Each 37HS volume controller is equipped with a maximum a Single Unit or of Units in Air Series cfm lever for setting the required unit airflow in the field. The lever is located at the bottom of the controller.
  • Page 29: Functional Checkout

    OPEN MINIMUM CFM STAR WHEEL MAXIMUM CFM LEVER VOLUME CONTROLLER Fig. 41 — Minimum and Maximum Airflow Adjustments, 37HS Controller To set maximum cfm with zero minimum cfm: Move thermostat lever to extreme right (red - warm) position. Then check that bellows of control (master) Set diffuser or wall thermostat for maximum cooling.
  • Page 30: Start-Up

    (Master) Unit - Units with System-Powered Controls building is occupied but after conditioned spaces are reason- and Standard Diffusers ably clean. The high induction ratio of 37HS Moduline ® dif- fusers can produce ceiling smudges within a few days if con-...
  • Page 31: Troubleshooting

    If control is lost by adding a new slave, check for loose, TROUBLESHOOTING cracked or disconnected tubing. Isolate that slave and General cap all bellows ports. Attach a Magnehelic gage to one If system design parameters have been met, such as ductwork port and blow into it.
  • Page 32 69°F and the cfm is not at design requirements, although lever is at the extreme blue area. © Carrier Corporation 2018 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.