Hermetic - HOSSEVEN HDU-5 Instruction Manual

Fireplace - natural gas - lpg stove
Table of Contents

Advertisement

Diameter of hole to be drilled on the wall is 27 cm. Hermetic stove must be mounted to the
wall, of which external side is open. Lower edge of the exhaust duct outlet mouth must be at
least 30 cm above from ground. Wall thickness must be maximum 42 cm, minimum 20 cm.
Make sure that minimum 1 cm, maximum 5 cm between air inlet holes and wall surface.
This distance can be adjusted with telescopic flue kit. At least 2,5 meters distance must be
available between exhaust gas pipes in the building façade If stove will be mounted under the
window, the distance between lower edge of window and upper edge of pipe must be at least
30 cm.
In the mounting of device to the sidewalk-fronted walls, the distance between exhaust pipe
outlet and ground must be 2m. For places such as semi-basement, on condition that to take
safety measures it can be 1 m.
Figure-2: Mounting towards pavement
Exhaust gas pipe outlet must be at least 40 cm above the roof surface.
Figure 3: Mounting to penthouse
6