For 8” Wc – 10.5” Wc Initial Supply Pressure; Sample Gas Line; Maximum Undiluted Propane (Lp) Delivery Capacity - Noritz NR501-OD Service Manual

Hide thumbs Also See for NR501-OD:
Table of Contents

Advertisement

Table 2. For 8" WC – 10.5" WC initial supply pressure
Maximum Natural Gas Delivery Capacity (3.0" Pressure Drop)
Pipe
10'
20'
Size
(3m)
(6m)
1/2"
454
3/4"
949
1"
1,787
1,228
1 1/4"
3,669
2,522
1 1/2"
5,497
3,778
2"
10,588
7,277
2 1/2"
16,875
11,598
3"
29,832
20,503
4"
43678
30,020
Values in Table are in Cubic Feet of Gas per Hour (0.60 Specific Gravity, 3.0" Pressure Drop, 8.0" WC or greater supply pressure, inlet
pressure less than 2psi). Contact your gas supplier for BTU/Cubic Foot ratings. For simplification of your calculations, 1 Cubic Foot of
Gas is approximately equivalent to 1000 BTU.

Sample Gas Line

Noritz Condensing Tankless Gas Water Heater
(120,000 Btuh)
Outlet E
10' (3m)
Section 4
Section 3 Section 2
5' (1.5m)
5' (1.5m)
Outlet D
10' (3m)
Gas Fireplace
(25,000 Btuh)
Natural Gas
Meter
Table 3. Maximum Undiluted Propane (LP) Delivery Capacity in Thousands of
BtuH (0.5" WC Pressure Drop)
Pipe
10'
20'
Size
(3m)
(6m)
1/2"
275
189
3/4"
567
393
1"
1,071
732
1 1/4"
2,205
1,496
1 1/2"
3,307
2,299
2"
6,221
4,331
For reference only. Please consult gas pipe manufacturer for actual pipe capacities.
Final Check
When the installation is complete, verify that inlet gas pressure for the entire gas system does not
drop below 5" WC for NG or 8" WC for LP at all appliances. This can be tested by turning on all
gas burning appliances including the water heater, then check the inlet pressure at each appliance
to verify all appliances are receiving a minimum of 5" WC for NG or 8" WC for LP. If all appliances
are not receiving the minimum inlet pressure the gas piping system may need to be changed.
30'
40'
(9m)
(12m)
312
250
214
652
524
448
986
844
2,025
1,733
3,034
2,597
5,844
5,001
9,314
7,971
16,465
14,092
24,107
20,632
Barbecue
(50,000 Btuh)
Outlet A
Clothes Dryer
(35,000 Btuh)
Outlet C
5' (1.5m)
Section 1
5' (1.5m)
10' (3m)
5' (1.5m)
Outlet B
Gas Range Stove
(65,000 Btuh)
30'
40'
50'
(9m)
(12m) (15m) (18m) (21m) (24m) (27m) (30m) (38m) (45m) (60m)
152
129
114
315
267
237
590
504
448
1,212
1039
913
1,858
1,559
1,417
3,465
2,992
2,646
Length (including fittings)
50'
60'
70'
(15m)
(18m)
(21m)
190
172
158
397
360
331
748
678
624
1,536
1,392
1,280
2,302
2,085
1,919
4,433
4,016
3,695
7,065
6,401
5,889
12,489
11,316
10,411
18,286
16,569
15,243
Instructions
1. Size each outlet branch starting from the furthest
using the Btuh required and the length from the meter.
2. Size each section of the main line using the length to
the furthest outlet and the Btuh required by everything
after that section.
Sample Calculation (Using 3.0" WC Pressure Drop Table)
10' (3m)
Outlet A: 45' (13.5m) (Use 50' (15m)), 50,000 Btuh requires 1/2"
Outlet B: 40' (12m), 65,000 Btuh requires 1/2"
Section 1: 45' (13.5m) (Use 50' (15m)), 115,000 Btuh requires 1/2"
Outlet C: 30' (9m), 35,000 Btuh requires 1/2"
5' (1.5m)
Section 2: 45' (13.5m) (Use 50' (15m)), 150,000 Btuh requires 1/2"
Outlet D: 25' (7.5m) (Use 30' (9m)), 25,000 Btuh requires 1/2"
Section 3: 45' (13.5m) (Use 50' (15m)), 175,000 Btuh requires 1/2"
Outlet E: 25' (7.5m) (Use 30' (9m)), 120,000 Btuh requires 1/2"
Section 4: 45' (13.5m) (Use 50' (15m)), 295,000 Btuh requires 3/4"
Length (including fittings)
60'
70'
80'
103
96
89
217
196
185
409
378
346
834
771
724
1,275
1,181
1,086
2,394
2,205
2,047
CAUTION
66
80'
90'
100'
(24m)
(27m)
(30m)
147
138
308
289
580
544
1,191
1,118
1,785
1,675
3,437
3,225
5,479
1,540
9,865
9,087
14,181
13,305
12,568
90'
100'
125'
83
78
69
173
162
146
322
307
275
677
630
567
1,023
976
866
1,921
1,811
1,606
125'
(38m)
131
116
273
242
514
456
1,056
936
1,582
1,402
3,046
2,700
4,856
4,303
8,584
7,608
11,139
150'
200'
63
55
132
112
252
213
511
440
787
675
1,496
1,260