Issues And Resolutions - Aquacal Heatwave Superquiet TropiCal Installation Manual

Table of Contents

Advertisement

3.2 Issues and Resolutions

WARNING
Repairs must not be attempted by untrained or unqualified individuals.
l
The heat pump contains refrigerant under pressure. Repairs to the refrigerant circuit must not be attempted by
l
untrained or unqualified individuals. Service must be performed only by qualified HVAC technicians. Recover
refrigerant before opening the system.
NOTICE
Service by unauthorized personnel will void the factory warranty.
l
Please perform the following troubleshooting.
For further assistance, please see "Contacting AquaCal AutoPilot, Inc." on page 1.
Display Panel Not Responding
1. If the heat pump is controlled be an external controller, confirm the external controller settings.
2. If the issue is still occurring, disconnect external controller from the heat pump. Then check operation at heat
pump.
If display panel responds, the problem lies with the external controller or its installation. Contact the
l
manufacturer of the external control device.
Heat Pump Not Running
1. Confirm equipment is receiving power. Is the heat pump display illuminated?
If not, confirm the main breaker (located at the power supply panel) and the disconnect switch (located near
l
the heat pump) are both turned on.
If the display still does not illuminate, it is recommended that the heat pump installer or electrician confirms
l
heat pump is receiving power.
2. Confirm correct mode is selected.
3. Confirm thermostat is set correctly.
When heating the water is desired, the thermostat should be set above the current water temperature.
l
When cooling the water is desired, the thermostat should be set below the current water temperature.
l
4. If an error code is displayed, diagnose and correct the cause of the code. See "Fault Codes" on page 31.
5. If the heat pump is using an external controller, the heat pump may not be set correctly to accept the controller's
signal.
See "Connecting an External Controller" on page 18.
l
Heat Pump's Tripping Breaker
1. Have an electrician confirm breakers are in good condition and properly sized for the heat pump.
2. Multiple heat pumps installed at the same site may benefit from special automatic sequencing controllers to avoid
excessive power drops at start-up.
3. If a fault occurs immediately when the compressor starts, a qualified technician should evaluate the system.
Failure to heed the following may result in injury or death.
Failure to heed the following may result in damage to equipment.
Page - 34

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents