Minimum and Maximum Operating Voltage
The heat pump must operate within specified voltages.
NOTICE
Operating equipment under higher or lower voltage conditions may result in damage to your compressor, motors or
l
other electrical components. This damage will not be covered by product warranty.
1. Measure site voltage. The site voltage MUST be measured under "FULL LOAD" conditions. Activate all
equipment using the same electrical panel as the heat pump.
2. If measured site voltage is outside listed ranges, immediately deactivate equipment until site conditions have been
corrected. If unsure of heat pump equipment rating, please see "Identifying Model Specifications" on page 26.
A Voltage
(208 to 230 Volts)
Single Phase 60 hertz
B Voltage
(208 to 230 Volts)
Three Phase 60 hertz
D Voltage
(380 to 420 Volts)
Three Phase 50 hertz
E Voltage
(380 Volts)
Three Phase 60 hertz
G Voltage
(460 Volts)
Three Phase 60 hertz
H Voltage
(200 to 240 Volts)
Single Phase 50 hertz
Failure to heed the following may result in damage to equipment.
Equipment Rating
Minimum
Maximum
Site Voltage
Site Voltage
200 Volts
253 Volts
200 Volts
253 Volts
361 Volts
441 Volts
361 Volts
399 Volts
437 Volts
483 Volts
180 Volts
264 Volts