5.5.3

Electromagnetic compatibility

Pulse-shaped interference
The following table shows the electromagnetic compatibility of modules with regard to pulse-
shaped interference. This requires the device to meet the specifications and directives for
electrical installation.
Pulse-shaped inter-
ference
Electrostatic
discharge
in accordance with
IEC 61000-4-2
Bursts
(high-speed transient
interference)
in accordance with
IEC 61000-4-4
Powerful single pulse (surge) according to IEC 61000-4-5, external protective circuit is required (see
function manual "SIMATIC S7-1500, ET 200MP, ET 200SP, ET 200AL Designing interference-free
controllers", section 7 "Lightning protection and overvoltage protection") on the Internet
(https://support.industry.siemens.com/cs/ww/en/view/59193566).
Asymmetrical
coupling
Symmetrical
coupling
The following lightning protection element was used during the testing of the Industrial Flat Panel:
1
Dehn BVT AVD 24" (Order No. 918 422)
Sinusoidal interference
The following table shows the EMC behavior of the modules with respect to sinusoidal
interference. This requires the HMI device to meet the specifications and directives for
electrical installation.
Sinusoidal interfer-
ence
HF radiation
(electromagnetic
fields) according to
IEC 61000-4-3
HF power applied to
lines and line shields
according
IEC 61000-4-6
Siemens Drives & PLCs
IFP2200 INOX MT ETH
Compact Operating Instructions, 03/2018, A5E42185570-AA
Test voltage
Air discharge: 8 kV
Contact discharge: 6 kV (front)
Contact discharge: 4 kV (rear)
2 kV power supply cable
2 kV signal cable, > 30 m
1 kV signal cable, < 30 m
2 kV power supply cable
DC voltage with protective elements
2 kV signal/data cable, > 30 m,
with protective elements as required
1 kV power supply cable
DC voltage with protective elements
1 kV signal cable, > 30 m,
with protective elements as required
Test values
80% amplitude modulation at 1 kHz
with 10 V/m in the range of 80 MHz to 1 GHz
with 3 V/m in the range 1.4 GHz to 2 GHz
with 1 V/m in the range 2 GHz to 2.7 GHz
Test voltage 10 V, with 80% amplitude modulation of 1 kHz
in the 150 kHz to 80 MHz range
Technical specifications
5.5 Ambient conditions
1
1
1
1
Degree of
severity
3
2
3
3
3
Degree of
severity
3
3
39