Section 6: Wire Resistance Table - Emerson Net Safety JB Series Reference Manual

Junction box
Table of Contents

Advertisement

Wire resistance table
June 2016

Section 6: Wire resistance table

Distance
Feet (Meters)
100 (30.5)
200 (61)
300 (91.4)
400 (121.9)
500 (152.4)
600 (182.9)
700 (213.4)
800 (243.8)
900 (274.3)
1000 (304.8)
1250 (381)
1500 (457.2)
1750 (533.4)
2000 (609.6)
2250 (685.8)
2500 (762)
3000 (914.4)
3500 (1066.8)
4000 (1219.2)
4500 (1371.6)
5000 (1524)
5500 (1676.4)
6000 (1828.8)
6500 (1981.2)
7000 (2133.6)
7500 (2286)
8000 (2438.4)
9000 (2743.2)
10000 (3048)
Resistance shown is one way. This figure must be doubled when determining closed loop resistance.
18
AWG #20
AWG #18
0.5mm
2
0.8mm
2
1.02
0.64
2.03
1.28
3.05
1.92
4.06
2.55
5.08
3.20
6.09
3.83
7.11
4.47
8.12
5.11
9.14
5.75
10.20
6.39
12.70
7.99
15.20
9.58
17.80
11.20
20.30
12.80
22.80
14.40
25.40
16.00
30.50
19.20
35.50
22.40
40.60
25.50
45.70
28.70
50.10
32.00
55.80
35.10
61.00
38.30
66.00
41.50
71.10
44.70
76.10
47.90
81.20
51.10
91.40
57.50
102.00
63.90
AWG #16
AWG #14
1.0mm
2
2.0mm
2
0.40
0.25
0.80
0.51
1.20
0.76
1.61
1.01
2.01
1.26
2.41
1.52
2.81
1.77
3.21
2.02
3.61
2.27
4.02
2.53
5.03
3.16
6.02
3.79
7.03
4.42
8.03
5.05
9.03
5.68
10.00
6.31
12.00
7.58
14.10
8.84
16.10
10.00
18.10
11.40
20.10
12.60
22.10
13.91
24.10
15.20
26.10
16.40
28.10
17.70
30.10
19.00
23.10
20.20
36.10
22.70
40.20
25.30
Reference Manual
MAN-0081, Rev 5
Wire resistance table

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents