  • Page 1 Operating instructions Temperature transmitter with display TDxxxx...
  • Page 2: Table Of Contents

    Contents 1 Preliminary note ���������������������������������������������������������������������������������������������������3 1�1 Explanation of symbols ����������������������������������������������������������������������������������3 2 Safety instructions �����������������������������������������������������������������������������������������������3 3 Functions and features ����������������������������������������������������������������������������������������3 4 Function ���������������������������������������������������������������������������������������������������������������4 4�1 Analogue function ������������������������������������������������������������������������������������������4 5 Installation������������������������������������������������������������������������������������������������������������5 6 Electrical connection ��������������������������������������������������������������������������������������������5 7 Operating and display elements ��������������������������������������������������������������������������6 8 Parameter setting ������������������������������������������������������������������������������������������������6 9 Operation �������������������������������������������������������������������������������������������������������������7 10 Technical data ����������������������������������������������������������������������������������������������������8 10�1 Temperature resistance �������������������������������������������������������������������������������8...
  • Page 3: Preliminary Note

    1 Preliminary note 1.1 Explanation of symbols ► Instruction > Reaction, result […] Designation of keys, buttons or indications → Cross-reference Important note Non-compliance can result in malfunction or interference� 2 Safety instructions • Please read this document prior to set-up of the unit� Ensure that the product is suitable for your application without any restrictions�...
  • Page 4: Function

    4 Function • The unit converts the measured signal into a temperature-proportional analo- gue signal: 4���20 mA if [OU2] = [I] or 20���4 mA if [OU2] = [Ineg]� • The analogue signal can be scaled. On delivery → 11 Factory setting. • The unit supports IO-Link� 4.1 Analogue function Current output 4���20 mA Maximum setting Measuring range scaled In the set measuring range the output signal is between 4 and 20 mA�...
  • Page 5: Installation

    5 Installation ► Connect the unit to the process using a fixing element (Triclamp, adapter)� For G½" sealing cone (type TD25xx): tightening torque 30���50 Nm� 6 Electrical connection The unit must be connected by a qualified electrician� The national and international regulations for the installation of electrical equipment must be adhered to�...
  • Page 6: Operating And Display Elements

    7 Operating and display elements 1: Current temperature in °C 2: Current temperature in °F 3: 7-segment LED display (4 digits) 8 Parameter setting Using an IO-Link capable parameter setting tool, the following options are availa- ble: - Reading current process values� - Reading, changing and saving current parameter settings and transmitting them to other units of the same type�...
  • Page 7: Operation

    Zero-point calibration� Setting range: ± 10 K in steps of 0�1 K� The internal measured value "0" is shifted by this value� Behaviour of the output in case of an internal fault� - [ON] = the analogue signal goes to the upper end stop value (21�1 mA)�...
  • Page 8: 10 Technical Data

    10 Technical data 10.1 Temperature resistance [min] [°C] Maximum operation time depending on the medium temperature Further technical data and scale drawing at www. ifm.com → Data sheet search → Enter the article number. 11 Factory setting Factory setting User setting → Technical data at www.ifm.com → Technical data at www.ifm.com → Technical data at www.ifm.com More information at www�ifm�com...