IAdditional information on SEG 3, 4, 5, 6, 8, 9
When SEG 3 is set to 1 and the HR-specific auto changeover function is run, the indoor unit operates as shown in the
following figure:
Temperature
Ts
Set temperature
for Auto mode
The mode change between the Cool and Heat modes is made only when the thermo off state is maintained for the
period of time set with SEG9.
DVM TK Wind-Free 1way IM EN_DB68-07553A-00.indb 35
Reference temperature for change from
heating to cooling
b
Reference temperature for
cooling
d
Reference
temperature for
cooling
C
c
B
A
D
a
Reference temperature for heating
A: Set with SEG4 (˚C)
B: Set with SEG5 (˚C)
C: Set with SEG6 (˚C)
D: Set with SEG8 (˚C)
35