14.2 Altering VFD Parameters For Use With CORAYVAC

Using the procedure described on Page 66, Section
14.1.1 through Section 14.1.5, alter the following
parameters:
Parameter
Parameter Name
Number
P01
Maximum Frequency (Hz)
P02
Minimum Frequency (Hz)
P03
Accel. Time (sec)
P04
Decel. Time (sec)
P07
Nominal Motor Voltage (V)
P08
Rated Motor Current (A)
P09
Rated Motor Frequency (Hz)
P12
Control Level
P14***
VFD Access Code
P36
Communication Configuration
*Depends on the VFD rated power
**VFD should be in modbus mode unless manual mode is desired temporarily
***Parameter Number P14 set to 101 unlocks parameters P15-P53
SECTION 14: V
ARIABLE
®

Modulating Heating Control

Factory Default
50.0
0.0
5
5
230*
4.8
Rated Motor Current (from Motor Data Plate)
Rated Motor Frequency (from Motor Data
50.0
0.0
0.0
-
-
-
F
D
P
REQUENCY
RIVE
ROGRAMMING
New Setting
60.0
40.0
10
10
(Motor Voltage)
Plate)
1 ‐ Manual Run Mode
3 ‐ Modbus (internal ramp times)**
101.0
VFD Slave Address (1) or (2)
Modbus RTU baud Rate (9600)
Time Out (0)
F
U
W
CORAY-
OR
SE
ITH
67 of 85