understanding the % of Load Bar

The 10-segment LED bar graph at the bottom left of the meter's front panel provides a graphic representation of
Amps. The segments light according to the load, as shown in the % Load Segment Table below.
When the Load is over 120% of Full Load, all segments flash "On" (1.5 secs) and "Off" (0.5 secs).
www.eaton.com
% of Load Segment table
Segments
none
1
1-2
1-3
1-4
1-5
1-6
1-7
1-8
1-9
1-10
All Blink
IM02601001E
Using the PXM 2000 Series
Load >= % Full Load
no load
1%
15%
30%
45%
60%
72%
84%
96%
108%
120%
>120%
6-11