Contact Information Visit our Web Site www.eatonelectrical.com view the on-line catalog, pricing, document support, distributor directory, news and events. For warranty support …………………………877-ETNCARE For a general directory of Eaton Electrical products …………………..(800) 525-2000 For on-site field service, commissioning & maintenance…………………(800) 498-2678...
Hazardous voltages in distribution switchboards and all other cover all configurations of this custom built product . Eaton has made electrical equipment pose a potential hazard to life and property .
. Prepare a sling and a spanner or spreader . (See Figure 3 and Figure 4 .) Eaton does not provide chain, cables, shackles, hooks, spanner, or spreader . eaton Corporation www.eaton.com...
Page 16
. Slowly lift equipment to the minimum height from the floor required to safely relocate it . Figure 4. Side View eaton Corporation www.eaton.com...
. Refer to the National Electrical Code for installations in damp locations for additional requirements . The entire area around the switchboard should be thoroughly cleaned of all debris . eaton Corporation www.eaton.com...
. Because electrical equipment is installed as part of a system, pre-engineering layouts are critical in seismic applications . When Eaton switchboards are marked as “seismic qualified, ” anchoring the switchboard is critical . Experienced engineers in seismic requirements should select methods and techniques of attachment and tested anchoring systems .
Page 19
Switchboard Front View mar the finish . Repair all scratches with touch-up paint, which is available from Eaton . Remove shipping skids and all packaging material . Remove any temporary shipping braces or spacers . Figure 11. Example of Rear (Only) Aligned Switchboard Remove lifting angles and associated hardware .
Page 20
. Once the switchboard structures are attached, visually inspect the board for foreign objects and visually inspect the structure for proper clearances of live parts . Figure 14. Switchboard Section Connection eaton Corporation www.eaton.com...
Torque all connections to torque requirements on labels affixed to the correct orientation or there are questions about the installation, each switchboard and as shown in Appendix A, Table 2 . contact Eaton before installing the splice plates . eaton Corporation www.eaton.com...
Page 22
DEAth. board lineup . Eaton’s selection of wire and cable follows UL 891 switchboard DO NOT work on electrical equipment while it is energized . Verify procedures, National Electrical Manufacturers Association (NEMAT), that power entering the equipment is de-energized at the source .
Page 23
. Refer to Appendix A, Table 2 for Cø torque values . 6.00 6.00 (152.4) (152.4) Figure 20. Cable Bracing Cable Lugs Cable Supports Cable Optional Cable Support Application Support Typical Cable Support Side View Detail Figure 21. Cable Bracing eaton Corporation www.eaton.com...
Page 24
Busway A switchboard may include one or more provisions for connection Recommended Busduct to Eaton brand busway . Busway can feed the switchboard, be fed Hardware for Bolting Flange from the load side of an overcurrent device within the switchboard,...
Page 25
For certain breakers with electronic trip units, a portable test kit is torque per instructions on the switchboard and on components . available from Eaton . An auxiliary power module is included in the test kit . This auxiliary power module powers the electronic trip unit 7.
Page 26
For certain breakers with electronic trip units, a portable test kit is power may be turned off by utilizing the control power switch or by available from Eaton, at additional cost . The kit includes complete removing the fuses . Components that use power supplies include...
. All parts should be aligned and secured when installed . Do not leave holes or gaps in the deadfront construction . Clean up any debris in and around the switchboard . eaton Corporation www.eaton.com...
4. Beginning with the main(s), turn ON each overcurrent device . The switchboard should be given a thorough maintenance check annually . Exercise extreme care to prevent the equipment from being connected to the power source while tests are being conducted. eaton Corporation www.eaton.com...
Page 29
The life of insulation material is dependent on keeping the material equipment, and other components . Damage to insulation and other dry and clean . surface materials can occur . Do not use compressed air in cleaning . eaton Corporation www.eaton.com...
Page 30
. Refer to the leaflet sure that it is clean and clear of debris, leaves, and obstructions . on each device . If leaflets are missing, contact Eaton for replacement . Records Circuit breakers It is essential to maintain the equipment in satisfactory condition .
Page 31
. Inspect for damage to components and any corrosion . If any dam- age or corrosion is present, contact Eaton . DO NOT RE-ENERGIZE SWITCHBOARD . After the switchboard has completely dried, remove all materials and tools from the equipment .
BE suRE to REcoNNEct thosE ciRcuits AftER mEGGER tEsts ARE complEtED. NotE: somE GRouND fAult ciRcuits mAy Not BE fusED; thEREfoRE, isolAtioN of thosE ciRcuits REQuiREs DiscoNNEctiNG WiRiNG fRom BusBARs. WARNiNG Do Not usE AltERNAtiNG cuRRENt (Ac) DiElEctRic/ mEGGER tEstiNG. DAmAGE to compoNENts Will occuR. eaton Corporation www.eaton.com...
Page 33
Phase-to-ground connections Neutral-ground connection A—Ground B—Ground C—Ground Notes: Date all overcurrent Devices open Phase-to-phase connections Phase-to-ground connections Neutral-ground connection A—Ground B—Ground C—Ground Date all overcurrent Devices Closed Phase-to-phase connections Phase-to-ground connections Neutral-ground connection A—Ground B—Ground C—Ground Notes: eaton Corporation www.eaton.com...
Page 34
Date Checklist notes and actions taken Cleaning Bus and cable connections Insulation inspection Overcurrent device inspection Meters Controllers Surge protective devices Other protective devices Secondary/control wiring Clean ventilation Refer to Maintenance section on page 16 . otee: eaton Corporation www.eaton.com...
Page 39
Technical Data 29-620 Page 1 October 1997 Type FDPW Mailed to: E, D, C/29-600A Fusible Panelboard Switches Application Type FDPW fusible panelboard switches are designed for commercial, industrial and service entrance applications to protect and 30 / 60 / 100A switch feeder and branch circuits.
Page 40
Time/Current Curves, Dimension Sheets, Application Data Technical Data 29-620 Page 2 Switch Selection Guide 30A / 60A / 100A 18" wide, 4X high 18" wide, 5X high 22" wide, 5X high Rating Fuse Catalog Number Unit 1 Unit 2 Rating Fuse Catalog Number Rating...
Page 41
Time/Current Curves, Dimension Sheets, Application Data Technical Data 29-620 Page 3 Switch Selection Guide 600A 22" wide, 11X high Rating Fuse Catalog Number 240 Volts Ac or 250 Volts Ac 18" wide, 16X high - Top Feed Main 18" wide, 16X high - Bottom Feed Main FDPW326R 600 (Main) FDPW326MR...
Page 42
Time/Current Curves, Dimension Sheets, Application Data Technical Data 29-620 Page 4 Switch Selection Guide 1200A 22" wide, 15X high 22" wide, 16X high - Top Feed Main 22" wide, 16X high - Bottom Feed Main Rating Fuse Catalog Number Rating Fuse Catalog Number Rating...
Page 45
PXM 2000 Series (PXM 2250/2260/2270) Multifunction Electricity Meter with Ethernet Communication User & Installation Manual IM02601001E Rev. 1.1 www.eaton.com...
Page 46
MENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental...
Page 47
3. Fill out the product registration information below and fax this page to 919-431-6240 Product:__________________________________________________________ Product Model or Version Number:_____________________________________ Product Serial or License Number:_____________________________________ Company:________________________________________________________ Your Name:_______________________________________________________ Address:_________________________________________________________ Address:_________________________________________________________ City:_________________________________ State:________ Zip:_______ Email:___________________________________________________________ Today’s Date:_____________________________________________________ Phone:___________________________________________________________ Eaton GO number (if known)_________________________________________...
COURSE OR DEALING OR USAGE OF TRADE ARE MADE REGARDING THE INFORMATION, RECOMMENDATIONS, AND DESCRIPTIONS CONTAINED HEREIN. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental, or consequential...
FAILuRE tO GROuNd tHE PXM 2250/2260/2270 MEtER MAY RESuLt IN INJuRY, dEAtH, OR EQuIPMENt dAMAGE. Properly ground the meter during installation. Covered by one or more of the following patents: uS Patent Numbers d526920, d525893, 6751563, 6735535, 6636030. www.eaton.com IM02601001E...
In addition to the PXM 2000 Series meter with integral display/transducer configuration, a transducer-only (without a display) configuration is available. The PXM 2000 Series Transducer provides RS485 communication via Modbus RTU, Modbus ASCII or DNP 3.0 protocols, as well as standard Ethernet communication. IM02601001E www.eaton.com...
This eliminates any possible point of failure at the meter. This is a preferred technique for insuring that relay class CT integrity is not compromised (the CT will not open in a fault condition). IM02601001E www.eaton.com...
Example: PXM 2260-M-A-6-5-1-1-5 (PXM 2260 Meter with 60 Hz System, 5 Amp Secondary, 90-265 VAC/100-370 VDC Power Supply, 2 Relay Outputs/2 Status Inputs I/O Card in Card Slot 1 and standard Power Xpert® Ethernet Gateway Card in Card Slot 2) IM02601001E www.eaton.com...
Voltage L-L Current per Phase Current Neutral WATT(A,B,C,Tot.) VAR (A,B,C,Tot.) VA (A,B,C,Tot.) PF (A,B,C,Tot.) +Watt-Hour (A,B,C,Tot.) -Watt-Hour (A,B,C,Tot.) Watt-Hour Net +VAR-Hour (A,B,C,Tot.) -VAR-Hour (A,B,C,Tot.) VAR-Hour Net (A,B,C,Tot.) VA-Hour (A,B,C,Tot.) Frequency %THD Voltage Angles Current Angles % of Load Bar IM02601001E www.eaton.com...
0.005VA Per Phase Max at 11 Amps Pickup Current: 0.1% of nominal Connections: O Lug or U Lug Electrical Connection (Diagram 4.1) Pass-through Wire, 0.177” / 4.5mm Maximum Diameter (Diagram 4.2) Quick Connect, 0.25” Male Tab (Diagram 4.3) Fault Withstand: 100A/10sec., 300A/3sec., 500A/1sec. IM02601001E www.eaton.com...
Page 58
3600 ⋅ P[Watt] - Not a scaled value pulse Kh – See Section 6-4 for values Watt IR LED Light Pulses Through face plate 90ms 90ms KYZ output Contact States Through Backplate (De-energized State) IM02601001E www.eaton.com...
3 With reference voltage applied (VA, VB, or VC). Otherwise, degrade accuracy to 0.2%. See hookup diagrams 8, 9, and 10 in Chapter 4. 4 At least one voltage input (minimum 20 Vac) must be connected for THD measurement on current channels. IM02601001E www.eaton.com...
NOtE: The drawings shown below and on the next page give you the meter dimensions in inches and millimeters (mm shown in brackets). Tolerance is +/- 0.1” [2.54 mm]. Figure 3.1: Meter Face Figure 3.2: Meter Dimensions Figure 3.3: Transducer Dimensions www.eaton.com IM02601001E...
Page 62
Mechanical Installation Fig. 3.4: Meter Back Figure 3.5: ANSI Mounting Panel Cutou Figure 3.6: DIN Mounting Cutout IM02601001E www.eaton.com...
3. Slide meter with Mounting Gasket into panel. 4. Secure from back of panel with lock washer and nut on each threaded rod. Use a small wrench to tighten. Do not overtighten. The maximum installation torque is 0.4 Newton-Meter. www.eaton.com IM02601001E...
Snap into place. 3. Secure meter to panel with lock washer and a #8 screw through each of the 2 mounting brackets. Tighten with a #2 Phillips screwdriver. Do not overtighten. The maximum installation torque is 0.4 Newton-Meter. IM02601001E www.eaton.com...
DIN Rails are commonly used as a mounting channel for most terminal blocks, control devices, circuit protection devices and PLCs. DIN Rails are made of cold rolled steel electrolitically plated and are also available in aluminum, PVC, stainless steel and copper. www.eaton.com IM02601001E...
Outputs, Inputs or Communications terminals. Eaton recommends the use of Shorting Blocks and Fuses for voltage leads and power supply to prevent hazard- ous voltage conditions or damage to CTs, if the meter needs to be removed from service. CT grounding is optional.
Page 68
Other current connections are shown in Figures 4.2 and 4.3. Voltage and RS485/KYZ Connection is shown in Figure 4.4. Current Gills (Nickel-Plated Brass Stud) Figure 4.1: CT Leads terminated to Meter, #8 Screw for Lug Connection Wiring Diagrams are shown later in this chapter. Communications Connections are detailed in Chapter 5. IM02601001E www.eaton.com...
Current Gills and place the CT wire directly through the CT opening. The opening will accomo- date up to 0.177” / 4.5mm maximum diameter CT wire. CT Wire passing through meter Current Gills removed Figure 4.2: Pass-Through Wire Electrical Connection www.eaton.com IM02601001E...
Page 70
Electrical Installation Quick Connect Crimp-on terminations For Quick Termination or for Portable Applications, a 0.25” Quick Connect Crimp-on Connectors can also be used. Quick Connect Crimp-on Terminations Figure 4.3: Quick Connect Electrical Connection IM02601001E www.eaton.com...
12/2.5 mm 2 wire for this connection. Voltage Fuses Eaton recommends the use of fuses on each of the sense voltages and on the control power, even though the wiring diagrams in this chapter do not show them. Use a 0.1 Amp fuse on each voltage input.
Page 72
5. Three-Phase, Three-Wire Delta with Direct Voltage 6. Three-Phase, Three-Wire Delta with 2 PTs 7. Three-Phase, Three-Wire Delta with 3 PTs 8. Current Only Measurement (Three Phase) 9. Current Only Measurement (Dual Phase) 10.Current Only Measurement (Single Phase) IM02601001E www.eaton.com...
Page 73
Electrical Installation 1. Service: WYE/delta, 4-Wire with No Pts, 3 Cts Select: “ 3 EL WYE ” (3 Element Wye) from the Meter’s Front Panel Display. (See Chapter 6. www.eaton.com IM02601001E...
Page 74
Electrical Installation 1a. Example of dual Phase Hookup Select: “ 3 EL WYE ” (3 Element Wye) from the Meter’s Front Panel Display. (See Chapter 6. IM02601001E www.eaton.com...
Page 75
Electrical Installation 1b. Example of Single Phase Hookup Select: “ 3 EL WYE ” (3 Element Wye) from the Meter’s Front Panel Display. (See Chapter 6. www.eaton.com IM02601001E...
Page 76
Power web page only the System values will be shown. Phase A, B, and C values will display as zero Select: “ 2.5 EL WYE ” (2.5 Element Wye) from the Meter’s Front Panel Display. (See Chapter 6. IM02601001E 4-10 www.eaton.com...
Page 77
Electrical Installation 3. Service: WYE/delta, 4-Wire with 3 Pts, 3 Cts Select: “ 3 EL WYE ” (3 Element Wye) from the Meter’s Front Panel Display. (See Chapter 6. www.eaton.com 4-11 IM02601001E...
Page 78
Power web page only the System values will be shown. Phase A, B, and C values will display as zero Select: “ 2.5 EL WYE ” (2.5 Element Wye) from the Meter’s Front Panel Display. (See Chapter 6. IM02601001E 4-12 www.eaton.com...
Page 79
Electrical Installation 5. Service: delta, 3-Wire with No Pts, 2 Cts Select: “ 2 Ct dEL ” (2 CT Delta) from the Meter’s Front Panel Display. (See Chapter 6. Not connected to meter www.eaton.com 4-13 IM02601001E...
Page 80
Electrical Installation 6. Service: delta, 3-Wire with 2 Pts, 2 Cts Select: “ 2 Ct dEL ” (2 CT Delta) from the Meter’s Front Panel Display. (See Chapter 6. Not connected to meter IM02601001E 4-14 www.eaton.com...
Page 81
7. Service: delta, 3-Wire with 2 Pts, 3 Cts Select: “ 2 Ct dEL ” (2 CT Delta) from the Meter’s Front Panel Display. (See Chapter 6. Not connected to meter NOtE: The third CT for hookup is optional and is for Current Measurement only. www.eaton.com 4-15 IM02601001E...
Page 82
Electrical Installation 8. Service: Current Only Measurement (three Phase) Select: “ 3 EL WYE ” (3 Element Wye) from the Meter’s Front Panel Display. (See Chapter 6. * For improved accuracy, this connection is recommended, but not required IM02601001E 4-16 www.eaton.com...
Page 83
Electrical Installation 9. Service: Current Only Measurement (dual Phase) Select: “ 3 EL WYE ” (3 Element Wye) from the Meter’s Front Panel Display. (See Chapter 6. * For improved accuracy, this connection is recommended, but not required www.eaton.com 4-17 IM02601001E...
Page 84
Electrical Installation 10. Service: Current Only Measurement (Single Phase) Select: “ 3 EL WYE ” (3 Element Wye) from the Meter’s Front Panel Display. (See Chapter 6. * For improved accuracy, this connection is recommended, but not required. IM02601001E 4-18 www.eaton.com...
Figure 5.1: Meter Back with RS485 Communication Installation RS485 allows you to connect one or multiple PXM 2000 Series meters to a PC or other device, at either a local or remote site. All RS485 connections are viable for up to 4000 feet (1219.20 meters). www.eaton.com IM02601001E...
Page 86
Termination Resistors may not be needed. When they are used, the value of the Termination Resistors is determined by the electrical parameters of the cable. Figure 5.3 shows a representation of an RS485 Daisy Chain connection. Figure 5.3: RS485 daisy Chain Connection www.eaton.com IM02601001E...
The PXM 2000 Series Transducer does not include a display or buttons on the front face of the meter. Programming and communication utilize the RS485 connection on the back face of the meter shown in section 5.1.2. Once a connection is established, Eaton Meter Configuration Software can be used to program the meter and communicate to slave devices.
Wh reading. The meter continues to provide scrolling readings until one of the buttons on the front panel is pressed, causing the meter to enter one of the other Modes. Figure 6.3: Wh Reading IM02601001E www.eaton.com...
CAutION! Reset demand YES resets all Max and Min values. Once you have performed a reset, the screen displays either “rSt dMd donE” or “rSt EnEr donE”and then resumes auto-scrolling parameters. www.eaton.com IM02601001E...
• If an incorrect Password has been entered, “PASS ---- FAIL” appears, and: • The previous screen is redisplayed, if you are in Reset Mode. • The previous Operating Mode screen is redisplayed, if you are in Configuration Mode. IM02601001E www.eaton.com...
9. If you have saved the settings, the Store ALL done screen appears and the meter resets. Press the Enter button to save the settings Press the Enter button to The settings have been saved Press the Right button for Stor All no screen Cancel the save www.eaton.com IM02601001E...
• To exit the screen without changing scrolling options, press the Menu button. • To return to the Main Menu screen, press the Menu button twice. • To return to the scrolling (or non-scrolling) parameters display, press the Menu button three times. IM02601001E www.eaton.com...
• The value for Amps is a product of the Ct-n value and the Ct-S value. • Ct-n and Ct-S are dictated by primary current; Ct-d is secondary current. Press Enter Use buttons to set Ct-n value The Ct-d cannot be changed Use buttons to select scaling www.eaton.com IM02601001E...
Pt-n value is 345, Pt-d value is 69, Pt-S value is 1000. NOtE: Pt-n and Pt-S are dictated by primary voltage; Pt-d is secondary voltage. Use buttons to set Pt-n value Use buttons to set Pt-d value Use buttons to select scaling IM02601001E www.eaton.com...
2. When you have finished making your selections, press the Menu button twice. 3. The StOR ALL YES screen appears. Press Enter to save the settings. Use buttons to enter Address Use buttons to select Baud Rate Use buttons to select Protocol www.eaton.com IM02601001E...
When the Load is over 120% of Full Load, all segments flash “On” (1.5 secs) and “Off” (0.5 secs). % of Load Segment table Segments Load >= % Full Load none no load 108% 1-10 120% All Blink >120% www.eaton.com 6-11 IM02601001E...
• Make sure the I/O card is inserted properly into the track to avoid damaging the card’s components. • For proper fit of cards, and to avoid damaging the unit, insert components in the following order: 1. Option Card 2. Detachable terminal block 1 www.eaton.com IM02601001E...
CAutION! FOR PROPER OPERAtION, RESEt ALL PARAMEtERS IN tHE uNIt AFtER HARdWARE MOdIFICAtION. The meter auto-detects any Option card installed in it. You configure the Option card through the Power Xpert® Ethernet Gateway card. The following sections describe the available Option cards. www.eaton.com IM02601001E...
(-40 to +80) °C Relative air humidity: Maximum 95%, non-condensing EMC - Immunity Interference: EN61000-4-2 Weight: 1.5oz Dimensions (inch) W x H x L: 0.72 x 2.68 x 3.26 External Connection: AWG 12-26/(0.129 - 3.31)mm 9 pin, 0.200” pluggable terminal block www.eaton.com IM02601001E...
Page 104
Using the I/O Option Cards Wiring Diagram Status Inputs For wet contacts For dry contacts Inputs (I1,I2) Inputs (I1,I2) Loop Common (C) Common (C) Relay Contacts Relay Outputs Fig. 7.3: Relay Contact (2) / Status Input (2) Card www.eaton.com IM02601001E...
Defaulted to Status Detect Pulse Outputs Defaulted to Energy Pulses Pulse Channel 1 1.8 +Watt-hrs per pulse Pulse Channel 2 1.8 -Watt-hrs per pulse Pulse Channel 3 1.8 +VAR-hrs per pulse Pulse Channel 4 1.8 -VAR-hrs per pulse www.eaton.com IM02601001E...
Page 106
Using the I/O Option Cards Wiring Diagram Status For wet contacts For dry contacts Inputs Inputs (I1,I2) Inputs (I1,I2) Loop Common (C) Common (C) Pulse Contacts - Form A Pulse Outputs Fig. 7.4: Pulse Output (4) / Status Input (4) Card www.eaton.com IM02601001E...
The PXM 2000 Series automatically recognizes the installed option card during Power Up. If you have not programmed a con- figuration for the card, the unit will default to the following: IP Address: 192.168.1.1 Subnet Mask: 255.255.255.0 default Gateway: 0.0.0.0 www.eaton.com 7-11 IM02601001E...
PXM 2000 Gateway Card With the installation of the Power Xpert® Meter 2000 Gateway Card, you gain the capability of communicating over the Ethernet medium using EATON’s Power Xpert architecture. Hardware Connection 1. The Gateway Card comes pre-installed in Slot #2 of the PXM Series meter. Refer to instructions at the beginning of this chapter for card installation.
Page 113
Performing Network Configuration As with the other Option cards, the PXM 2000 auto-detects the presence of the Gateway card. You configure the Gateway card through the Ethernet connection, using the Power Xpert webpage. See Chapter 10 for instructions. www.eaton.com IM02601001E...
Page 114
Using the I/O Option Cards www.eaton.com IM02601001E...
Environment (JRE), version 6 or newer. The web pages use a Java applet and you must have a local copy of Java for this to work. To access the meter’s web site, simply enter the meter’s IP address as the URL. You should see something similar to the following page. Loading Page IM02601001E www.eaton.com...
Line-Line or Line-Neutral. The radio buttons select the voltage information to view: Average, AB, BC, or CA. If more than one type of graph is available on the page, another drop-down menu in the IM02601001E www.eaton.com...
Page 117
3 - Eight days • 4 - Four-and-a-Half Weeks (Demand Profile and Demand Comparison) A table containing all of the plotted data points is beneath the plot. You can scroll through this to view individual data points. The Meter Page IM02601001E www.eaton.com...
You’ll need the administrative account name and password to modify the setup param- eters. Details about using the setup page are covered in the Setup on the Web Pages chapter. IM02601001E www.eaton.com...
Introduction to Web Server Pages Setup Page I/O Page The I/O page shows the current status of all of the inputs and outputs from any installed I/O cards. I/O Page IM02601001E www.eaton.com...
Generate a map of the Modbus registers for both the meter and installed I/O cards. • Access a web page from which you can download the various MIB files. • Access the Eaton firmware update page. • Access the Eaton Power Xpert Website. •...
The system average values are calculated for main voltage channels. The Power Xpert Meter maintains a log of all voltage rms measurements date and time ® stamps. This information is also available as a trend graph. The min, max, and averages IM02601001E www.eaton.com...
Page 122
Angle (deg). By default, the fundamental frequency is included. It can be excluded by selecting the Exclude Fundamental check box on the left side of the page. NOtE: the Waveform and Harmonics views are only available on the PXM 2270 model. IM02601001E www.eaton.com...
The most recent minimum and maximum values are detected for all the channels and are logged with date and time stamps. Current minimum and maximum values can be cleared by the user at any time. After the current values are cleared, the meter will start calculating new minimum and maximum values. IM02601001E www.eaton.com...
Page 124
Locating Frequency Information From the Meter page, click the Frequency radio button on the left side of the page. To view the trending and phasor graphs, click the drop-down box at the top of the page IM02601001E www.eaton.com...
Reactive Power (kvar) for System, Phase A, Phase B and Phase C The meter will log the trend for all of the above measurements, as well as detect and save Minimum and Maximum values with date and time stamps for all of the above parameters. IM02601001E www.eaton.com...
The formula for THD is provided below. The variables X and x may represent either voltage or current and may be expressed either as rms or peak values, as long as all are expressed in the same fashion. IM02601001E www.eaton.com...
Page 127
Trend View Harmonics View (PXM2270 only) The individual harmonics of the THD may be viewed for up to 40 har- monics of the fundamental frequency. Select this view from the upper-center drop down list. IM02601001E www.eaton.com...
Reactive Power (VAR) is the product of the voltage, the current, and the sine of the phase angle between them. • Apparent Power (VA) is the square root of the sum of the squares of the active and reactive powers. IM02601001E www.eaton.com...
Page 129
15 minutes, it is not user programmable. For the Demand Profile, you can select a date from the drop down list and then click Show Profile to change the graph to reflect data from a different day. IM02601001E www.eaton.com...
Page 130
Today and Yesterday • This Week and Last Week • This Month and Last Month • 2 different Days • 2 different Weeks • 2 different Months Peak demand is shown in the graph as a dashed line. IM02601001E 9-10 www.eaton.com...
Page 131
Windows clipboard (Ctrl+C). Place the cursor where you wish to paste the information in the third-party application and press Ctrl+V. To select the entire table, press Ctrl+A IM02601001E www.eaton.com 9-11...
Percent THD Ic PF App Phase A PF App Phase B PF App Phase C PF Apparent Peak Demand Amps Avg Peak Demand Forward Watts Peak Demand Lagging Peak Demand Leading Peak Demand Net VARs VARs VARs IM02601001E 9-12 www.eaton.com...
Page 133
Click a specific event in the list to display the detailed information about that event at the bottom of the page. You can acknowledge or clear either the cur- rently selected event or all events. IM02601001E www.eaton.com 9-13...
Page 134
Functions on the Web Server Pages Events Page IM02601001E 9-14 www.eaton.com...
The information will be displayed in the midsec- tion of the page. Typical Setup Page Note: All configuration (edit) abilities discussed in the following sections require you to login with the admin account. IM02601001E www.eaton.com 10-1...
Page 136
B phase voltage. The Phase AB and BC voltage values shown on the Meter web page are estimates only, and on the Power web page only the System values will be shown. Phase A, B, and C values will display as zero.) Note: Wiring configurations are detailed in chapter 4, Electrical Installation. IM02601001E 10-2 www.eaton.com...
Page 137
• DHCP which resolves to a fixed IP address Eaton does not recommend using a DHCP setup that can randomly assign an IP address from a pool of possible addresses. Rather, if you use DHCP you should use a scheme wherein the router or layer 3 switch assigns a fixed IP based on the MAC address of the meter.
• The event information is sent as an RSS (Atom) feed. You can subscribe to the me- ter’s Atom feed by clicking the RSS icon at the top, right side of the page. In the RSS IM02601001E 10-4 www.eaton.com...
Page 139
RSS feeds page, from which you can view event details. Clicking an event on the RSS feeds page launches the meter’s Home web page. • The event information can be sent to one or more recipients as an email message. The Out of Limits Triggers Page IM02601001E www.eaton.com 10-5...
Page 140
These alarms include: • Restart is pending • Modbus RTU communications failure • Alarms based on the state of digital inputs. IM02601001E 10-6 www.eaton.com...
The user account is for access to the meter web pages only. Someone logged in as user cannot change any settings. The default password is user. • Use the admin account to change settings or delete data. The default password is admin. Passwords Page IM02601001E www.eaton.com 10-7...
Page 142
For example, if you select 15 minutes as the demand interval and 5 minutes as the subinterval, the demand will calculate every 5 minutes using the 3 subinterval values (15 = 5X3). IM02601001E 10-8 www.eaton.com...
Page 143
Communications Settings - Com 2 Setup You can set the protocol, Modbus address, baud rate, response delay, parity, and stop and data bits for the RS-485 serial connection. The protocol is selectable between Mod- bus RTU, Modbus ASCII, or DNP. IM02601001E www.eaton.com 10-9...
Page 144
Recipient drop-down list and then configuring the recipient’s address information by clicking the Edit button. The following example is typical of the status emails sent by the meter: Power Xpert Meter Status Report Device=Power Xpert Meter 2000 Gateway Card IM02601001E 10-10 www.eaton.com...
Page 145
Note that the requirements for the two protocols are different. For SNMP 1 you are only required to provide a read-only and read-write community string. However, SNMP 3 requires separate usernames and passphrases (passwords) for both read and write privi- leges. Consult your SNMP software documentation for more information. IM02601001E www.eaton.com 10-11...
• Channel selects the electrical parameter through the Set Limit Channel dialog box. The various electrical measurements from the meter are grouped under the categories of Demand, Reading, and Total Harmonic Distortion (THD). IM02601001E 10-12 www.eaton.com...
Page 147
Without the compression factor, the accumulator might roll over either too much or too rapidly and lose history. Digital Input Setup Edit Page IM02601001E www.eaton.com 10-13...
Page 148
KYZ; in this case either 1.8 or a ratio of that number. The Set Limit Channel dialog box associates a meter measure, like kW Demand or Phase B current, with each of the outputs, and gets a pulse train whose rate reflects the present value of that measure. IM02601001E 10-14 www.eaton.com...
Page 149
KYZ module that is outputting a pulse every 1.8 kWh, you would set the Accumulator Kt to be the value of the KYZ; in this case either 1.8 or a ratio of that number. Pulse Output Setup Edit IM02601001E www.eaton.com 10-15...
Page 150
Each output can be assigned to one of any of the electrical parameters in the Demand, Reading, or THD groups. You can set the Minimum and Maximum values as well as enable Bidirectional Current (0-1 mA card only). Analog Output Setup Edit Page IM02601001E 10-16 www.eaton.com...
Page 151
Click Setup. Expand Meter Setup & Commissioning. Click Save/Restore Settings. Click the Browse button beside the Configuration file to restore field. Select the configuration .xml file. Click Save/Restore Configuration Page IM02601001E www.eaton.com 10-17...
Time Protocol) as the Time Sync Source, at least one IP Address must be entered (as many as three NTP server IP addresses may be entered). A list of public NTP servers is available at: http://support.ntp.org/bin/view/Servers/WebHome. Note: The time Zone and Date format settings only affect logs and e-mails. IM02601001E 10-18 www.eaton.com...
Page 153
Firmware Configuration Page: Select the Reboot when complete checkbox. Click the new firmware image link, which will direct the meter to the eaton.com website where firmware files are stored. Select the firmware type from the list.
Note: You can tell who has made configuration changes to the meter from the log as it not only logs changes but the IP address of the computer from which the changes were made. System Log Page IM02601001E 10-20 www.eaton.com...
Page 155
Setup on the Web Server Pages diagnostics - System Hardware The System Hardware page provides a single, convenient page you can use to check information about the meter and the cards installed in it. System Hardware Page IM02601001E www.eaton.com 10-21...
Page 156
Setup on the Web Server Pages IM02601001E 10-22 www.eaton.com...
Open the browser, type the IP address of the meter in the address bar, and select For example: https://192.168.1.1/ca.html. The security alert dialog box ap- pears. The security alert dialog box Click the View Certificate button. The certificate dialog box appears. IM02601001E www.eaton.com 11-1...
Page 158
Root Certificate Authority Installation Certificate Dialog Box Select the Certification Path tab. On the tab, select the line with PowerXpert fol- lowed by a series of hexadecimal digits. Click the View Certificate button. The Certificate dialog box appears. IM02601001E 11-2 www.eaton.com...
Page 159
Root Certificate Authority Installation Click the Install Certificate button. The Certificate Import Wizard appears. Certificate Import Wizard Click the Next button. The store dialog box appears. IM02601001E www.eaton.com 11-3...
Page 160
Root Certificate Authority Installation Certificate Import Wizard - store dialog Select Place all certificates in the following store and then click Browse. Select trusted Root Certificate Authorities and then click OK. Click Next. IM02601001E 11-4 www.eaton.com...
Page 161
The certificate wizard displays a completed dialog. Click Finish. The Security Warn- ing dialog box will appear. Security Warning dialog box Click Yes to install the CA. A message box opens to verify that the import was successful. Import Successful message box Click IM02601001E www.eaton.com 11-5...
Security certificate problem page If the security certificate problem page appears, you’ll next see the following security warning dialog box. Click Yes. Warning: Security dialog box The install CA certificate page appears. Click the Root CA Certificate link. IM02601001E 11-6 www.eaton.com...
Page 163
Install CA certificate page Click the Open button. Figure 2. File download dialog box In the Certificate dialog box, click the Install Certificate button. NOtE: The certificate cannot be verified yet because it is issued by a nontrusted CA. IM02601001E www.eaton.com 11-7...
Page 164
Root Certificate Authority Installation Figure 3. Certification Path Window Follow the remaining steps for installing a certificate using Internet Explorer 6, starting with step 2. IM02601001E 11-8 www.eaton.com...
Reserved Reserved Reserved Reserved Normal behavior Reset the card to factory defaults on boot up. After a successful boot, the switch should be turned back off before rebooting the card. Reserved Reserved Reserved Reserved www.eaton.com IM02601001E...
Page 243
Instruction Manual IM01005019E - Rev. 3 Effective April 2010 Eaton SPD Series Surge Protective Device For Integrated Units...
Page 244
7.0 Warranty .................... 12 Eaton is a registered trademark of Eaton Corporation or its subsidiaries and affiliates. National Electric Code and NEC are registered trade- marks of the National Fire Protection Association. Power Chain Management is a registered trademark of Eaton Corporation, UL is a federally registered trademark of Underwriters Laboratories, Inc.
Page 245
® (SPD). This manual is organized into seven sections, as follows: 1.4 Catalog Numbering System Each Eaton SPD Series unit has a name plate that identifies 1.0 Introduction the parameters used for manufacture. These parameters are 2.0 Installation expressed in letters and numbers, to reflect the Series, kA 3.0 Operating Features...
Page 246
Check the facility grounding system. All grounding, bonding, • Every Eaton SPD Series unit is tested at the factory for dielec- and earthing must meet the NEC and any other national, state tric breakdown. No further SPD testing is required for installa- and local electrical codes.
Page 247
Eaton SPD Series Instruction Manual IM01005019E - Rev.3 Surge Protective Device for Integrated Units Effective April 2010 6. Select the correct wiring diagram for the SPD you are install- ing. You must refer to this diagram while wiring the SPD.
Page 248
Eaton SPD Series Instruction Manual IM01005019E - Rev. 3 Surge Protective Device for Integrated Units Effective April 2010 Figure 6. Wiring - Single Phase Units (230 L) Figure 8. Wiring - 3-Phase Delta Units Figure 7. Wiring - Split Phase Units Figure 9.
Page 249
Eaton SPD Series Instruction Manual IM01005019E - Rev.3 Surge Protective Device for Integrated Units Effective April 2010 9. The SPD (Standard and Standard with Surge Counter mod- els) also has an available connection for remote monitoring of the Form C relay contacts. See Figure13. This is a green connector located on the side of the SPD.
Page 250
Eaton SPD Series Instruction Manual IM01005019E - Rev. 3 Surge Protective Device for Integrated Units Effective April 2010 6. Connect the System Ground wire (green) to the SPD’s 2. Connect the RDP cable to the SPD. Use tie wraps Surge Ground connection using a ring terminal suitable (already on the SPD) to secure the cable to the for use with a #10 fastener and #10-32 x 3/8"...
The Eaton SPD Series Standard Feature Package display is 3.1 General shown in Figure 19. The Eaton SPD Series comes in three feature packages: Basic, Standard, and Standard with Surge Counter. The operating spe- cifics of each feature package are described below.
Page 252
3.2.4 SPD Display Rotation The SPD display can be rotated on the SPD enclosure, up to 360 The Eaton Series SPD displays may be monitored on a remote degrees. This allows you to position the display for the best vis- display panel (RDP).
Page 253
Eaton SPD Series Instruction Manual IM01005019E - Rev.3 Surge Protective Device for Integrated Units Effective April 2010 Table 3. Troubleshooting Chart condition probable cause solution Green LEDs ON (1 per phase) and one Green LED ON for Normal operation N/A.
Eaton SPD Series Instruction Manual IM01005019E - Rev. 3 Surge Protective Device for Integrated Units Effective April 2010 5.0 Specifications Table 4. Specifications description specification Surge current capacity per phase 50, 80, 100, 120, 160, 200, 250, 300, 400 kA ratings available...
Page 255
Eaton SPD Series Instruction Manual IM01005019E - Rev.3 Surge Protective Device for Integrated Units Effective April 2010 6.0 Ordering Guidelines Table 5. Eaton SPD Series SPD 250 480D 2 J kA Rating voltage code Options options 50kA Per Phase 80kA Per Phase...
Page 256
Surge Protective Device for Integrated Units Effective April 2010 7.0 Warranty Eaton warrants these products for a period of 10 years from the date of delivery to the purchaser to be free from defects in both workmanship and materials. Eaton assumes no risk or liability...
Page 257
Eaton SPD Series Instruction Manual IM01005019E - Rev.3 Surge Protective Device for Integrated Units Effective April 2010 Notes Eaton Corporation www.eaton.com...
Page 258
OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including neg- ligence), strict liability or otherwise for any special, indirect, incidental or consequential damage...
Page 261
ENGINEERING DATA SHEET - SEISMIC 1A32007.XLS GUIDELINES FOR SWITCHBOARDS User Date THE INFORMATION ON THIS DOCUMENT WAS CREATED BY EATON CORPORATION. IT WAS DISCLOSED IN CONFIDENCE AND IS ONLY TO BE USED FOR THE PURPOSE Wardie 12/11/2012 IN WHICH IT WAS SUPPLIED.
Page 263
Date PDF Generated:12/11/2012 Page: 1 of 1 Certified Production Test Report Switchboards CERTIFICATION Production tests performed in accordance with UL 891, Section 44 and Eaton ISO 9000 certified Work Instructions for Low Voltage Switchboard Inspection and Testing, as follows: TEST PASSED Dielectric: (Power Bus @ 2.5Kv, 1 Second)
Page 265
Date PDF Generated:10/24/2012 Page: 1 of 1 The information on this document is suitable for use in establishing final installation and construction details.
Page 267
Incoming Utility Structures (Incoming Utility Section) Horizontal isolating barrier Groundlugs: 2 Auxiliary Bus The information on this PREPARED BY DATE Eaton Corporation document is created by Eaton EricSNims 04/29/13 Sumter, SC Corporation. It is disclosed APPROVED BY DATE JOB NAME...
Page 269
Height-MM 2285 2285 Weight-Lbs.(Est.) Weight-Kg.(Est.) The information on this PREPARED BY DATE Eaton Corporation document is created by Eaton EricSNims 04/29/13 Sumter, SC Corporation. It is disclosed APPROVED BY DATE JOB NAME Banner Health Centers in confidence and it is only...
Page 271
Main Switch - Ind Mtd-800A/600V Ind. Mtd. Main 3P FDPW Fus. Sw. L-Fuse Terminals, Mechanical, (3) 3/0-750 kcmil, Bottom The information on this PREPARED BY DATE Eaton Corporation document is created by Eaton EricSNims 04/29/13 Sumter, SC Corporation. It is disclosed APPROVED BY...
Page 273
Date PDF Generated:10/24/2012 Page: 1 of 1 The information on this document is suitable for use in establishing final installation and construction details.
Page 275
Date PDF Generated:10/19/2012 Page: 1 of 1...
Page 277
ENGINEERING DATA SHEET 1A32007 EXCEL SEISMIC GUIDELINES FOR USERS OF SHEET 1 OF 1 PRLC / PRLI LOW VOLTAGE SWITCHBOARDS 2/12/07 1. A generic type NEMA 1 and NEMA 3R PRLC/PRLI low voltage switchboard assembly was attached to a triaxial seismic simulator to duplicate the effects of an earthquake. 2.
Page 279
Certified Production Test Report S00IKW9901.DOC Assembly S00F293A01.DOC User Date THE INFORMATION ON THIS DOCUMENT WAS CREATED BY EATON CORPORATION. IT WAS DISCLOSED IN CONFIDENCE AND IS ONLY TO BE USED FOR THE PURPOSE Gretchen 4/23/2013 IN WHICH IT WAS SUPPLIED. Schneider...
Page 281
Certified Production Test Report Switchboards CERTIFICATION Production tests performed in accordance with UL 891, Section 44 and Eaton Electric ISO 9000 certified Work Instructions for Low Voltage Switchboard Inspection and Testing, as follows: TEST PASSED Dielectric: (Power Bus @ 2.5Kv, 1 Second)
Page 283
Description/Modifications Bottom incoming main lugs on 50x chassis (Incoming Main Device/MLO Section) Groundlugs: 11 The information on this PREPARED BY DATE Eaton Corporation document is created by Eaton JerryRPetruk 04/23/13 Sumter, SC Corporation. It is disclosed APPROVED BY DATE JOB NAME...
Page 285
90.00 Height-MM 2286 Weight-Lbs.(Est.) Weight-Kg.(Est.) The information on this PREPARED BY DATE Eaton Corporation document is created by Eaton JerryRPetruk 04/23/13 Sumter, SC Corporation. It is disclosed APPROVED BY DATE JOB NAME Banner Health Centers in confidence and it is only...
Page 287
Lockoff devices: Padlockable Hasp Blank Cover -3 X RBL CTs-RBL CTs Main Lugs-Main Lugs The information on this PREPARED BY DATE Eaton Corporation document is created by Eaton JerryRPetruk 04/23/13 Sumter, SC Corporation. It is disclosed APPROVED BY DATE JOB NAME...
Page 298
NOTICE AND DISCLAIMER The information in this publication was considered technically sound by the consensus of persons engaged in the development and approval of the document at the time it was developed. Consensus does not necessarily mean that there is unanimous agreement among every person participating in the development of this document.
Page 299
PB 1.1-2007 Page i CONTENTS Page Foreword ...........................iv Section 1 SCOPE ............................1 Section 2 REFERENCES .......................... 2 Section 3 GENERAL ..........................3 Successful Operation of Panelboards ..................3 Qualified Personnel ........................3 Definition of Qualified Personnel ....................3 3.3.1 Requirements ........................
Page 300
PB 1.1-2007 Page ii 6.10 Debris ............................12 6.11 Steps In Section 7 ........................12 Section 7 STEPS TO BE TAKEN BEFORE ENERGIZING..............13 Accessible Electrical Connections................... 13 Blocks and Packing Materials ....................13 Switches, Circuit Breakers, and Other Operating Mechanisms ..........13 Short Circuits and Ground Faults ....................
Page 302
LVDE Section. Product Group approval of the standard does not necessarily imply that all Product Group members voted for its approval or participated in its development. At the time it was approved, the Product Group was composed of the following members: Eaton Electrical Inc.—Pittsburgh, PA GE—Plainville, CT Hubbell, Inc.—Orange, CT Milbank Manufacturing Company—Kansas City, MO...
Page 303
PB 1.1-2007 Page 1 Section 1 SCOPE This publication covers single panelboards or groups of panel units suitable for assembly in the form of single panelboards, including buses, and with or without switches or automatic overload protective devices (fuses or circuit breakers), or both. These units are used in the distribution of electricity at 600 volts and less with: 1600—ampere mains or less 1200—ampere branch circuits or less...
Page 304
PB 1.1-2007 Page 2 Section 2 REFERENCES National Fire Protection Association (NFPA) Batterymarch Park Quincy, MA 02269 NFPA 70 2005 National Electrical Code NFPA 70E 2004 Safety Related Work Practices National Electrical Manufacturers Association (NEMA) 1300 North 17th Street, Suite 1752 Rosslyn, Virginia 22209 AB 4- 2003 Guidelines for Inspection and Preventative Maintenance of Molded Case Circuit...
Page 305
PB 1.1-2007 Page 3 Section 3 GENERAL WARNING—HAZARDOUS VOLTAGES IN ELECTRICAL EQUIPMENT CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. UNLESS OTHERWISE SPECIFIED, INSPECTION AND MAINTENANCE SHOULD ONLY BE PERFORMED ON PANELBOARDS AND EQUIPMENT TO WHICH POWER HAS BEEN TURNED OFF, DISCONNECTED AND ELECTRICALLY ISOLATED SO THAT NO ACCIDENTAL CONTACT CAN BE MADE WITH ENERGIZED PARTS.
Page 306
PB 1.1-2007 Page 4 Section 4 INSTALLATION OF PANELBOARD CABINETS (BOXES) INSTALLATION INSTRUCTIONS Installation of the cabinet in a neat and workmanlike manner. Follow the manufacturer's installation instructions. LOCATION IN BUILDING Locate the cabinet so that it is readily accessible and not exposed to physical damage. FLAMMABLE MATERIAL Locate the cabinet well away from flammable material.
Page 307
PB 1.1-2007 Page 5 4.10 FLUSH MOUNTING IN WALL In walls of concrete, tile, or other noncombustible material, install the cabinet so that its front edge will not set back more than 1/4 inch from the finished surface. In walls of wood or other combustible material, cabinets should be flush with or project beyond the finished surface.
Page 308
PB 1.1-2007 Page 6 Section 5 INSTALLATION OF CONDUIT AND CONDUCTORS CONDUITS INSTALLATION Conduits should be installed so as to prevent moisture or water from entering and accumulating within the enclosure. Provision should be made to protect conductors from abrasion in accordance with Article 312 of the National Electrical Code.
Page 313
PB 1.1-2007 Page 11 Section 6 INSTALLATION OF PANELBOARD PROPER STORAGE Store the panelboard in a clean, dry place located so that mechanical damage from work personnel in the area is not likely to happen. UNPACKING Care should be exercised in unpacking the panelboard to prevent damage and loss of instruction materials and loose parts.
Page 314
PB 1.1-2007 Page 12 LINE AND BRANCH CONDUCTORS Connect Line and Branch Conductors 6.7.1 Conductors Use care in stripping insulation from conductors so as not to nick or ring the conductor. For aluminum, clean all oxide from the stripped portion and apply an antioxide compound. 6.7.1.1 Wiring Gutters Distribute and arrange conductors neatly in the wiring gutters.
Page 315
PB 1.1-2007 Page 13 Section 7 STEPS TO BE TAKEN BEFORE ENERGIZING ACCESSIBLE ELECTRICAL CONNECTIONS Tighten all accessible electrical connections to the manufacturer's torque specifications. If such information is not provided with the equipment, consult the manufacturer. BLOCKS AND PACKING MATERIALS Make certain that all blocks and packing materials used for shipment have been removed from all component devices and the panelboard.
Page 317
PB 1.1-2007 Page 15 Section 8 INSTALLATION OF CABINET FRONT CABINET FRONT OR TRIM PACKAGE The cabinet front or trim package is designed to prevent damage to the front during shipment and handling. UNPACKING Care should be used when unpacking and handling the cabinet front. COVERS AND DOORS Install covers, close doors, and make certain that no conductors are pinched and that all enclosure parts are properly aligned and tightened.
Page 318
PB 1.1-2007 Page 16 Section 9 ENERGIZING EQUIPMENT WARNING—HAZARDOUS VOLTAGES IN ELECTRICAL EQUIPMENT CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ENERGIZING A PANELBOARD FOR THE FIRST TIME AFTER INITIAL INSTALLATION OR MAINTENANCE IS POTENTIALLY DANGEROUS. QUALIFIED PERSONNEL Only qualified personnel should energize equipment for the first time. If short circuit conditions caused by damage or poor installation practices have not been detected in the procedures specified in Section 7, serious personal injury and damage can occur when the power is turned on.
Page 319
PB 1.1-2007 Page 17 Section 10 MAINTENANCE 10.1 MAINTENANCE PROGRAM A maintenance program for panelboards should be conducted on a regularly scheduled basis in accordance with the following: 10.2 PANELBOARD WHICH HAS BEEN CARRYING ITS REGULAR LOAD FOR AT LEAST 3 HOURS A panelboard which has been carrying its regular load for at least 3 hours just prior to inspection should be field tested by feeling the deadfront surfaces of circuit breakers, switches, interior trims, doors, and...
Page 320
PB 1.1-2007 Page 18 CAUTION—Do not remove plating from aluminum parts in joints or terminations. Damage to plating can result in overheating. Replace damaged aluminum parts. 10.4.3 Fuse Clip Contact Pressure and Contact Means Examine fuse clip contact pressure and contact means. If there is any sign of overheating or looseness, follow the manufacturer’s maintenance instructions or replace the fuse clips.
Page 321
PB 1.1-2007 Page 19 10.6.4.3 Clean, Light Grease If no instructions are given on the devices, sliding copper contacts, operating mechanisms, and interlocks may be lubricated with clean, light grease. 10.6.4.4 Excess Lubrication Wipe off excess lubrication to avoid contamination. CAUTION—Hydrocarbon spray propellants and hydrocarbon based sprays or compounds will cause degradation of certain plastics.
Page 322
PB 1.1-2007 Page 20 10.10 SEVERE ELECTRICAL SHORT CIRCUIT If a severe electrical short circuit has occurred, the excessive currents may have resulted in structural component and/or bus and conductor damage due to mechanical distortion, thermal damage, metal deposits, or smoke. Examine all devices and bus supports for cracks or breakage. The manufacturer should be consulted before cleanup and correction is attempted.
Page 323
PB 1.1-2007 Page 21 Section 11 PERMISSIBLE LOADING OF PANELBOARDS 11.1 NATIONAL ELECTRICAL CODE In compliance with the National Electrical Code, the normal continuous loads (3 hours or more) of panelboard circuits should be not more than 80 percent of the rating of the overcurrent protective device, unless the marking of the device indicates that it is suitable for continuous duty at 100 percent of its rating.
Page 327
Current Cutler-Hammer Panelboards Renewal Parts Supersedes RP.38F.01.T.E pages 1 – 48 dated February 2000 Description Page Current Cutler-Hammer Panelboards PRL1a and PRL2a ..........5 Trim Locks .
Page 328
Renewal Parts Current Cutler-Hammer Panelboards Page 2 Effective: February 2009 Table 1. Product History Time Line Table of Contents Page Product 1985 1990 1995 Present Procedure for Identifying Panelboard Type ... . . 3 Cutler-Hammer PRL1a, 2a Oct.
Page 329
Current Cutler-Hammer Renewal Parts Panelboards Page 3 Effective: February 2009 Procedure for Identifying Procedure for Identifying Panelboard Type Renewal Parts The current line of Pow-R-line C 1. Identify the type of panelboard, panelboards was introduced in 1993. i.e. PRL1a, PRL2a, PRL3a, PRL4, PRL5P by reading the nameplate.
Page 330
Current Cutler-Hammer Renewal Parts Panelboards Page 4 Effective: February 2009 Cutler-Hammer Satellite Plants Seattle Hartford Chicago New Jersey Cleveland Baltimore San Francisco St. Louis Denver Raleigh Phoenix Atlanta Angeles Dallas Orlando Houston Figure 2. Satellite Plants Atlanta Denver Phoenix 7990-A 2nd Flag Drive 14101 East 33rd Place, Suite F 7160 South Harl Avenue Austell, GA 30001...
Page 331
Current Cutler-Hammer Renewal Parts Panelboards Page 5 Effective: February 2009 PRL1a, 2a Connector Kits PRL1a, 2a Parts Section Page Connector Kits, Table 2. Vertical Breaker Assemblies Vertical Breakers ..5 Device Device 3-Phase 1-Phase...
Page 332
Current Cutler-Hammer Renewal Parts Panelboards Page 6 Effective: February 2009 PRL1a, 2a Connector Kits Table 3. 100 Ampere Lug Assemblies Panel Lug Wire Size Quantity 3-Phase 1-Phase Type Options Range Per Phase Tin-Plated Silver-Plated Tin-Plated Silver-Plated Aluminum Connector Copper Connector Aluminum Connector Copper Connector Catalog Number...
Page 333
Current Cutler-Hammer Renewal Parts Panelboards Page 7 Effective: February 2009 PRL1a, 2a Connector Kits Table 4. 225 Ampere Lug Assemblies Panel Lug Wire Size Quantity 3-Phase 1-Phase Type Options Range Per Phase Tin-Plated Silver-Plated Tin-Plated Silver-Plated Aluminum Connector Copper Connector Aluminum Connector Copper Connector Catalog Number...
Page 334
Current Cutler-Hammer Renewal Parts Panelboards Page 8 Effective: February 2009 PRL1a, 2a Connector Kits Table 5. 400 Ampere Lug Assemblies Panel Lug Wire Size Quantity 3-Phase 1-Phase Type Options Range Per Phase Tin-Plated Silver-Plated Tin-Plated Silver-Plated Aluminum Connector Copper Connector Aluminum Connector Copper Connector Catalog Number...
Page 335
Current Cutler-Hammer Renewal Parts Panelboards Page 9 Effective: February 2009 PRL1a Horizontally Mounted Connector Kit Assemblies Table 6. Bolt-on QUICKLAG Breaker Assemblies Breaker Drawing Branch 3-Phase 1-Phase Frame Number Circuit Tin-Plated Silver-Plated Tin-Plated Silver-Plated Quantity Aluminum Connector Copper Connector Aluminum Connector Copper Connector Item Number BA, BAB,...
Page 336
Current Cutler-Hammer Renewal Parts Panelboards Page 10 Effective: February 2009 PRL1a Horizontally Mounted Connector Kit Assemblies Table 7. Plug-in QUICKLAG Breaker Assemblies Breaker Drawing Branch 3-Phase 1-Phase Frame Number Circuit Tin-Plated Silver-Plated Tin-Plated Silver-Plated Quantity Aluminum Connector Copper Connector Aluminum Connector Copper Connector Item Number HQP, QPHW,...
Page 338
Current Cutler-Hammer Renewal Parts Panelboards Page 12 Effective: February 2009 PRL1a, 2a Neutral Assemblies Table 9. 100 Ampere Neutral Assemblies Panel Main Neutral Drawing Panel Lug Wire Size Quantity Tin-Plated Silver-Plated Bus Ampere Rating Type Number Options Range Aluminum Connector Copper Connector Rating Item Number...
Page 339
Current Cutler-Hammer Renewal Parts Panelboards Page 13 Effective: February 2009 PRL1a, 2a Neutral Assemblies Table 10. 225 Ampere Neutral Assemblies Panel Main Neutral Drawing Panel Lug Wire Size Quantity Tin-Plated Silver-Plated Bus Ampere Rating Type Number Options Range Aluminum Connector Copper Connector Rating Item Number...
Page 340
Current Cutler-Hammer Renewal Parts Panelboards Page 14 Effective: February 2009 PRL1a, 2a Neutral Assemblies Table 11. 400 Ampere Neutral Assemblies Panel Main Neutral Drawing Panel Lug Wire Size Quantity Tin-Plated Silver-Plated Bus Ampere Rating Type Number Options Range Aluminum Connector Copper Connector Rating Item Number...
Page 341
Current Cutler-Hammer Renewal Parts Panelboards Page 15 Effective: February 2009 PRL1a, 2a Neutral Assemblies Table 12. 100 Ampere Neutral Assemblies for 21.00 – 27.00-Inch (533.4 – 685.8 mm) High Enclosures Only Panel Main Neutral Drawing Panel Lug Wire Size Quantity Tin-Plated Silver-Plated Bus Ampere...
Page 342
Renewal Parts Current Cutler-Hammer Panelboards Page 16 Effective: February 2009 PRL1a, 2a Ground Assemblies PRL1a, 2a Service Entrance Kits Table 13. Standard Ground Table 15. PRL1a, 2a Service Entrance Kits Drawing Enclosure Height Item Drawing Panel Tin-Plated Bare Silver-Plated Tin-Plated Number in Inches (mm) Material...
Page 343
Current Cutler-Hammer Renewal Parts Panelboards Page 17 Effective: February 2009 PRL1a, 2a Deadfront Covers Note: Does not apply to PRL4 sub-chassis. Table 16. Assembly Drawing Standard Enclosure Height in Inches (mm) Number 24.00 36.00 42.00 48.00 60.00 72.00 90.00 (609.6) (914.4) (1066.8) (1219.2)
Page 344
Renewal Parts Current Cutler-Hammer Panelboards Page 18 Effective: February 2009 PRL1a, 2a Deadfront Covers Note: Does not apply to PRL4 sub-chassis. Table 19. Filler Covers Table 18. Horizontally Mounted Devices Device/Frame Drawing Item Mounting Device/ Drawing Branch Circuit Item Quantity Number Number Arrangement...
Page 345
Current Cutler-Hammer Renewal Parts Panelboards Page 19 Effective: February 2009 Panelboard Trim Locks Panelboard trims use different trim locks, see pictures below for styles and part numbers. Contact your nearest Satellite for availability on the styles listed below. See Page 4 for Satellite listings. Table 20.
Page 346
Renewal Parts Current Cutler-Hammer Panelboards Page 20 Effective: February 2009 Panelboard Fastrim Clamps and Screw-on Hardware Kits For panelboard trim clamps, contact your nearest Satellite for availability on the styles listed below. See Page 4 for Satellite listings. Table 21. Panelboard Fastrim Clamps and Screw-on Hardware Kits Description Style Number...
Page 347
Current Cutler-Hammer Renewal Parts Panelboards Page 21 Effective: February 2009 PRL3a Horizontally Mounted Connector Kit Assemblies PRL3a Parts Section Page Connector Kits, Table 22. Connector Kit Assemblies Branch Breakers ..21 Devices Circuits 3-Phase...
Page 348
Current Cutler-Hammer Renewal Parts Panelboards Page 22 Effective: February 2009 PRL3a F-Frame Horizontally Mounted Connector Kit Assemblies Table 23. Connector Kit Assemblies Devices Circuits 3-Phase 1-Phase Notes or Pole Catalog Number Phase Catalog Number Phase EHD, FD, FDB, 3-Pole Breaker KPRL3AFD3 A/B/C —...
Page 349
Current Cutler-Hammer Renewal Parts Panelboards Page 23 Effective: February 2009 PRL3a Ground Assemblies PRL3a Deadfront Covers Table 24. PRL3a Ground Assemblies Table 26. Assembly Material Standard Isolated Style Chassis Height/Item Number Number Catalog Number Aluminum/Copper 5158C05G02 2C11296G02 6559C59 Copper Only 5158C05G04 2C11296G04 Assembly groups include the frame only (two rails and two end...
Page 350
Renewal Parts Current Cutler-Hammer Panelboards Page 24 Effective: February 2009 PRL3a Vertical Devices Deadfront Covers Table 27. Vertical Mounting Position Device/Frame Trip Unit Style “X” Item Number Type Number Space Without With Required Lock-offs Lock-offs EHD, FD, FDB, HFD, 4176B68 FDC, ED, EDH, EDC (Top) EHD, FD, FDB, HFD, FDC, ED, EDH, EDC (Bottom)
Page 351
Current Cutler-Hammer Renewal Parts Panelboards Page 25 Effective: February 2009 PRL3a Horizontal Devices Deadfront Covers PRL3a Deadfront Cover Blank Fillers Table 28. Horizontal Mounting Position Table 29. PRL3a Deadfront Cover Blank Fillers Device/Frame Device Style Total Circuit “X” Space Item Poles Number Quantity...
Page 352
Renewal Parts Current Cutler-Hammer Panelboards Page 26 Effective: February 2009 PRL4 Vented Cover Assemblies PRL4B/F Parts Section Page Vented Cover Assemblies and Side Gutter Covers ..26 Nameplate PRL4 Blank Covers ..27 PRL4 Breaker Connector Kits .
Page 353
Current Cutler-Hammer Renewal Parts Panelboards Page 27 Effective: February 2009 PRL4 Blank Covers Used to cover blank space on chassis. All PRL4 cover heights Neutral are measured in “X” units. 1X equals 1.38 inches (35.1 mm). Table 31. PRL4 Blank Covers Cover Style Number Size...
Page 356
Renewal Parts Current Cutler-Hammer Panelboards Page 30 Effective: February 2009 PRL4 Breaker and Fusible How to Order a Breaker Retrofit Kit Switch Retrofit Kits by Catalog Number Use “KPRL4” prefix and add catalog Breaker Retrofit Kits number of breaker as shown below. Use suffix “T”...
Page 357
Current Cutler-Hammer Renewal Parts Panelboards Page 31 Effective: February 2009 PRL4 Energy Sentinel IQ Central Energy Display The space-saving design characteris- tics of the IQ Energy Sentinel mean they can be quickly and easily retrofit- ted onto Series C circuit breakers in existing equipment…with no addi- tional space required.
Page 358
Renewal Parts Current Cutler-Hammer Panelboards Page 32 Effective: February 2009 PRL1a, 2a, 3a Special Trims and Enclosures Ventilated Trim Fastrim Door-In-Door Required on PRL1a, 2a, 3a, 600 ampere Used when concealed trim mounting Piano hinge on the right side of the and above panels only.
Page 359
Current Cutler-Hammer Renewal Parts Panelboards Page 33 Effective: February 2009 PRL4 Special Trims Table 40. Special Trims and Enclosures and Enclosures Standard Box Mounting Channel Door-In-Door Trim Catalog Number Catalog Number Style Number Surface Flush Door-In-Door Trim BX2457 8708C82G02 LDD2457STW LDD2457FTW BX2473 8708C82G03...
Page 360
Renewal Parts Current Cutler-Hammer Panelboards Page 34 Effective: February 2009 Ordering Procedure PRL5P Parts Section Page Step 2 Refer to the 5P panelboard layout on Page 35 to verify the PRL5P Chassis Layout ..35 amount of “X”...
Page 361
Current Cutler-Hammer Renewal Parts Panelboards Page 35 Effective: February 2009 PRL5P Chassis Layout Double-Bus Interior Mounted in Single-Bus Interior in 48-inch (1219.2 mm) Wide Enclosure 30-inch (762.0 mm) Wide Enclosure (1219.2) (762.0) (254.0) (254.0) Neutral — No “X” Space Required Neutral —...
Page 362
Renewal Parts Current Cutler-Hammer Panelboards Page 36 Effective: February 2009 PRL5P Breaker Assemblies Catalog Numbers Table 42. Catalog Numbering System — 5P Single or Twin Breakers with Adapters 5P FD 3 0060 M S B Panelboard Connection Breaker Mounting B = Branch C = Combination Ampere T = Twin...
Page 363
Current Cutler-Hammer Renewal Parts Panelboards Page 37 Effective: February 2009 Branch Devices Single-pole breakers in single adapter units. Include two Dual breaker adapters — Any two breakers listed in Table 46 or three single-pole 15 – 60 ampere assembled on one unit. may be mounted on the same 2X or 3X dual breaker adapter.
Page 364
Renewal Parts Current Cutler-Hammer Panelboards Page 38 Effective: February 2009 PRL5P Main or Through-Feed Lugs Table 47. PRL5P Main or Through-Feed Lugs Description Ampere Wire Size “X” Space Catalog Rating Range Required Number Single Bus Chassis Mounting Ampere Lug Unit (1) 1/0 –...
Page 365
Current Cutler-Hammer Renewal Parts Panelboards Page 39 Effective: February 2009 PRL5P Neutrals and Grounds Table 48. Neutral Assemblies with Lugs Incoming Number of Cables Catalog Neutral Assembly and Wire Size Number (4) 250 – 500 kcmil 800 Amperes Aluminum/Copper 5PN800A (4) 250 –...
Page 366
Renewal Parts Current Cutler-Hammer Panelboards Page 40 Effective: February 2009 PRL5P Box, Trim and Deadfront Filler Plates Table 51. PRL5P Box, Trim and Deadfront Filler Plates Chassis Catalog Number “X” Factor Back Box Trim Trim Door Kit Single Bus Chassis — 30.00-Inch (762.0 mm) Wide Box 5PB2430G 5PT2430S 5PD24S...
Page 367
Current Cutler-Hammer Renewal Parts Panelboards Page 41 Effective: February 2009 PRL1a, 2a-LX Table 53. Type 1 Box and Trims Box Height Catalog Number in Inches (mm) Surface Trim Surface Trim Standard Door-In-Door Incoming Location Top Fed 69.00 (1752.6) YSC969 LTC969S LTCD969S Trim 78.00 (1981.2)
Page 368
Current Cutler-Hammer Renewal Parts Panelboards Page 42 Effective: February 2009 Pow-R-Command Additional Services For replacement parts, see PRL3a Since virtually all panelboards are Section, Page 21. Parts available are supplied to meet specific customer the following: requirements, other parts not listed in this publication might occasionally be ■...
Page 369
Current Cutler-Hammer Renewal Parts Panelboards Page 43 Effective: February 2009 This page intentionally left blank. RP01400001E For more information visit: www.eatonelectrical.com...
Page 373
Main Device Mods: PLK1 Padlockable Hasp Lockoff Notes: The information on this PREPARED BY DATE Eaton Corporation document is created by Eaton EricSNims 04/29/13 Corporation. It is disclosed APPROVED BY DATE JOB NAME Banner Health Centers in confidence and it is only...
Page 375
Main Device Mods: PLK1 Padlockable Hasp Lockoff Notes: The information on this PREPARED BY DATE Eaton Corporation document is created by Eaton EricSNims 04/29/13 Corporation. It is disclosed APPROVED BY DATE JOB NAME Banner Health Centers in confidence and it is only...
Page 377
PLK1 Padlockable Hasp Lockoff PROV Notes: The information on this PREPARED BY DATE Eaton Corporation document is created by Eaton EricSNims 04/29/13 Corporation. It is disclosed APPROVED BY DATE JOB NAME Banner Health Centers in confidence and it is only...
Page 379
Frame Amps KAIC PROV Notes: The information on this PREPARED BY DATE Eaton Corporation document is created by Eaton EricSNims 04/29/13 Corporation. It is disclosed APPROVED BY DATE JOB NAME Banner Health Centers in confidence and it is only 04/29/13...
Page 381
Frame Amps KAIC PROV Notes: The information on this PREPARED BY DATE Eaton Corporation document is created by Eaton EricSNims 04/29/13 Corporation. It is disclosed APPROVED BY DATE JOB NAME Banner Health Centers in confidence and it is only 04/29/13...
Page 383
Frame Amps KAIC PROV Notes: The information on this PREPARED BY DATE Eaton Corporation document is created by Eaton EricSNims 04/29/13 Corporation. It is disclosed APPROVED BY DATE JOB NAME Banner Health Centers in confidence and it is only 04/29/13...
Page 385
Trip Frame Amps KAIC Notes: The information on this PREPARED BY DATE Eaton Corporation document is created by Eaton EricSNims 04/29/13 Corporation. It is disclosed APPROVED BY DATE JOB NAME Banner Health Centers in confidence and it is only 04/29/13...
Page 393
I.L. PG24836G-591H Page 1 Página 1 Instructions for Installation, Instrucciones para la Operation, and Maintenance instalación, operación y of Dry-Type Distribution mantenimiento de los Transformers Transformadores de Distribución Tipo Seco CONTENTS CONTENIDO Description Descripción Section 1: Introduction ..............2 Sección 1: Introducción ..............2 Section 2: Receiving ................
Page 394
I.L. PG24836G-591H Page 2 Página 2 WARNING ADVERTENCIA ALWAYS TURN OFF THE POWER SUPPLYING THIS EQUIPMENT SIEMPRE DESENERGICE ESTE EQUIPO ANTES DE TRABAJAR BEFORE WORKING INSIDE. FAILURE TO DO SO COULD RESULT IN EN ÉL. EL NO HACERLO PUEDE CAUSAR LESIONES SERIOUS PERSONAL INJURY, DEATH, OR PROPERTY DAMAGE.
Page 395
I.L. PG24836G-591H Page 3 Página 3 Orificos (2) para izado por Para aplicaciones en Weather Shields are Lifting Holes (2) in the inside dentro o por fuera con tapones intemperie (NEMA 3R), or with Removable Hole Plugs. Required to Cover removibles.
Page 396
I.L. PG24836G-591H Page 4 Página 4 4. STORAGE PRIOR TO ENERGIZATION 4. ALMACENAJE PREVIO A CONEXION Store dry-type transformers in their original shipping cartons indoors Mantenga los transformadores en su empaque original, en interiores in a clean, dry, temperature stable environment. secos, limpios y a temperatura estable.
Page 397
I.L. PG24836G-591H Page 5 Página 5 All general purpose dry-type distribution transformers are designed to Todos los transformadores de distribución tipo seco son diseñados meet NEMA ST-20 established sound levels. However, to minimize the para cumplir con los niveles de sonido establecidos por NEMA, norma potential for sound transmission to surrounding structures and sound ST-20.
Page 398
I.L. PG24836G-591H Page 6 Página 6 Do not make any connections other than those shown on the No intente realizar conexiones no mostradas en la placa de datos. No nameplate or diagram. Do not change connections or taps while the intente modificaciones o cambio de derivaciones (taps) con el unit is energized.
Page 399
I.L. PG24836G-591H Page 7 Página 7 Practically no maintenance is required on a dry-type transformer but El transformador tipo seco prácticamente no necesita mantenimiento; inspect it periodically as indicated below: aún así, acostumbre revisarlo de la manera siguiente: De-energize transformer. Desenergice el transformador.
Page 400
I.L. PG24836G-591H Page 8 Página 8 or fitness for a particular purpose, other than those specifically set out adecuación a un propósito particular, mas que aquellas estipuladas by any existing contract between the parties. Any such contract states en un contrato existente entre las partes. Tal contrato establece toda the entire obligation of seller, the contents of this document shall not la obligación del vendedor.
Page 415
2 Pole 3 Pole 3 Pole Load Load Fig. 5-2 Fig. 5-4 Figure 6. Load Isolated from Power Source. Grounded or Figure 8. Load Isolated from Power Source. Grounded or Ungrounded Systems. If System Voltage Exceeds 300 Vdc, then Ungrounded Systems. If System Voltage Exceeds 125 Vdc, then Load Isolated from Power Source. Ungrounded Systems Only. Ungrounded Systems Only. Grounded or Ungrounded Systems. If System Voltage Exceeds 300 Vdc. Then Ungrounded Systems Only. Eaton CorporatIon www.eaton.com...
Page 416
HFD, FDC, HFDDC Circuit Breakers and Molded Case Switches Effective January 2011 The.instructions.for.installation,.testing,.maintenance,.or.repair. herein.are.provided.for.the.use.of.the.product.in.general.commercial. applications.and.may.not.be.appropriate.for.use.in.nuclear.applica- tions ..Additional.instructions.may.be.available.upon.specific.request. to.replace,.amend,.or.supplement.these.instructions.to.qualify.them. for.use.with.the.product.in.safety-related.applications.in.a.nuclear. facility . The.information,.recommendations,.descriptions,.and.safety.nota- tions.in.this.document.are.based.on.Eaton’s.experience.and.judg- ment.with.respect.to.Retrofitting.of.Power.Breakers ..This.instruction- al.literature.is.published.solely.for.information.purposes.and.should. not.be.considered.all-inclusive ..If.further.information.is.required,.you. should.consult.an.authorized.Eaton.sales.representative . The.sale.of.the.product.shown.in.this.literature.is.subject.to.the. terms.and.conditions.outlined.in.appropriate.Eaton.selling.policies. or.other.contractual.agreement.between.the.parties ..This.literature. is.not.intended.to.and.does.not.enlarge.or.add.to.any.such.contract .. The.sole.source.governing.the.rights.and.remedies.of.any.purchaser. of.this.equipment.is.the.contract.between.the.purchaser.and.Eaton . NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE, ARE MADE REGARDING THE INFORMATION, RECOMMENDATIONS, AND DESCRIPTIONS CONTAINED HEREIN..In.no.event.will.Eaton.be.responsible.to.the. purchaser.or.user.in.contract,.in.tort.(including.negligence),.strict.
Page 426
NOTICE AND DISCLAIMER The information in this publication was considered technically sound by the consensus of persons engaged in the development and approval of the document at the time it was developed. Consensus does not necessarily mean that there is unanimous agreement among every person participating in the development of this document.
Page 427
KS 3-2010 Page i CONTENTS Foreword ..............................ii Introduction..............................iii SECTION 1 GENERAL..........................1 Scope.............................. 1 Referenced Standards........................1 SECTION 2 SAFETY PROCEDURES ......................3 Warning ............................3 Safety Procedure ..........................3 Reinstallation Safety Procedure ..................... 3 SECTION 3 GUIDELINES ..........................5 To Avoid Damaged or Otherwise Inoperable Switches Being Inadvertently Returned to Service 5 Guidance Regarding Inspection and Preventive Maintenance Procedures ........
Page 428
At the time it was approved, the Switches Voting Classification had the following members: ABB Control, Inc.—Wichita Falls, TX Boltswitch, Inc.—Crystal Lake, IL Cooper Bussmann—St. Louis, MO Eaton Corporation—Pittsburgh, PA GE Industrial Solutions—Plainville, CT Hubbell Inc.—Bridgeport, CT Mersen USA—Newburyport, MA Siemens Industry, Inc.—Alpharetta, GA Schneider Electric—Palatine, IL...
Page 429
KS 3-2010 Page iii Introduction NEMA KS 3 deals with guidelines for inspection and preventive maintenance of switches used in commercial and industrial applications. These guidelines are to be used to identify switches requiring maintenance or replacement. Good practice includes periodic switch maintenance during plant shutdown or during a regular maintenance period as specified, for example, in NFPA 70B.
Page 430
KS 3-2010 Page iv Section 7 deals with the operation of accessory devices. Failure of an accessory would lead to replacement of that accessory, or switch replacement if accessories are not removable. In summary, following an automatic overcurrent interruption at or near its interrupting rating, the condition of any protective device should be checked prior to circuit re-energization.
Page 431
KS 3-2010 Page 1 Section 1 GENERAL Scope NEMA Standards Publication KS 3 sets forth, for use by qualified personnel , a number of basic procedures that may be used for the inspection and preventive maintenance of switches used in industrial and commercial applications rated up to and including 600 V 50/60 Hz ac or ac/dc.
Page 432
KS 3-2010 Page 2 National Electrical Manufacturers Association 1300 North 17th Street Suite 1752 Rosslyn, Virginia 22209 Evaluating Water-Damaged Electrical Equipment NEMA KS 1 Enclosed and Miscellaneous Distribution Equipment Switches (600 Volts Maximum) NEMA KS 2 Distribution Equipment Switch Application and Maintenance Guide, A User’s Reference NEMA 250 Enclosures for Electrical Equipment (1000 Volts Maximum) Underwriters Laboratories, Inc.
Page 433
KS 3-2010 Page 3 Section 2 SAFETY PROCEDURES The inspection and preventive maintenance of switches in service require the user to take all necessary precautions to avoid being injured. Warning 2.1.1 Switch Testing WARNING—Hazardous voltages in electrical equipment can cause death or severe personal injury.
Page 435
KS 3-2010 Page 5 Section 3 GUIDELINES To Avoid Damaged or Otherwise Inoperable Switches Being Inadvertently Returned to Service To avoid damaged or otherwise inoperable switches being inadvertently returned to service, it is suggested that such switches be destroyed. Guidance Regarding Inspection and Preventive Maintenance Procedures Industrial users have requested guidance regarding inspection and preventive maintenance procedures that could be carried out on a regularly scheduled basis.
Page 436
KS 3-2010 Page 6 Section 4 INSPECTION PROCEDURES General The following inspection practices are recommended. Exposed Surfaces Temperature Check 4.2.1 Purpose To determine if there is excessive temperature on the external cover of a switch. CAUTION—Severe burns can result from high temperatures. Do not hold hand or fingers in contact with surfaces if excessive heat is felt.
Page 437
KS 3-2010 Page 7 a. If there is no evidence of looseness, e.g., overheating, do not disturb or tighten the connections. b. If there is evidence of overheating (as noted in 4.2) or arcing, an investigation of the cause should be made and corrective steps taken. (See Section 5.) Figure 1 Pitting Figure 2...
Page 438
KS 3-2010 Page 8 Evidence of excessive high current switch closing operation includes: • Bright metal or metallic deposits on insulating surfaces or the enclosure interior • An excessive number of small, bright metal balls resting on the enclosure bottom end wall •...
Page 439
KS 3-2010 Page 9 Section 5 PREVENTIVE MAINTENANCE General Under normal conditions, properly applied switches require maintenance only for verification of environmental conditions and that the correct enclosure type for those conditions is being used. However, when inspections determine an abnormal condition and indicate the possibility of damage, it may be necessary to perform certain maintenance steps.
Page 440
KS 3-2010 Page 10 If the damage is extensive, or cannot be corrected by dressing the surfaces, the damaged parts should be replaced if they are intended by the manufacturer to be replaceable. If the damaged parts are not intended to be replaceable, the complete switch and/or bus connections should be replaced.
Page 441
KS 3-2010 Page 11 Section 6 TEST PROCEDURES General The KS 3 Standards Publication is not intended, nor is it adequate, to verify proper electrical performance of a switch that has been disassembled, modified, rebuilt, refurbished, or handled in any manner not intended or authorized by the original switch manufacturer.
Page 442
KS 3-2010 Page 12 Insulation Resistance Test CAUTION—If applied incorrectly, the voltages utilized in the insulation resistance tests may damage electronic or other accessory components. Refer to the manufacturer's instructions for guidelines. NOTE—Where the switch can be safely isolated as installed, the test may be performed with the switch in its equipment. See Figure 3 for typical test set-up.
Page 443
KS 3-2010 Page 13 6.3.4 Test 6.3.4.1 All exposed metal parts except line, load, and accessory terminals should be electrically connected together. 6.3.4.2 Using an insulation resistance tester, apply a voltage of at least 500 volts to determine the resistance. Voltage is to be applied as follows. WARNING—High Voltage—Do not touch switch or leads.
Page 445
KS 3-2010 Page 15 Figure 6 Non-Fused Switch Individual Pole Resistance Test Set-Up 6.4.1 Purpose To assess the electrical integrity of internal connections and contacts in a switch. This can be done by conducting a millivolt drop test across the line and load terminals of each pole with the switch contacts closed.
Page 446
KS 3-2010 Page 16 6.4.4 Test NOTE—If the switch is equipped with an under-voltage trip release, energize the trip release to allow proper operation of the switch. 6.4.4.1 The test is performed as follows. 6.4.4.1.1 Apply test current across a pole equal to the switch rating (or 500 Amperes minimum for switch rated in excess of 500 Amperes).
Page 447
KS 3-2010 Page 17 Section 7 ACCESSORY DEVICE TEST PROCEDURES General If testing instructions for the specific accessory being tested are available from the manufacturer, those instructions should be followed to verify the operation of the accessory. If the manufacturer's instructions are not available, the tests described below may be used to verify the basic operation of the accessory.
Page 448
KS 3-2010 Page 18 7.2.3.2 Connect a test power supply to the terminals (or leads) of the shunt trip release device. WARNING—High Voltage. Do not touch switch or test leads while voltage is applied. 7.2.3.3 Operate the switch to the ON position. 7.2.3.4 Set the power supply voltage to 75% of the rated voltage of the shunt trip and energize.
Page 449
KS 3-2010 Page 19 7.3.1 Purpose To verify that the electrical operator (Figure 8) will operate the switch to the ON and OFF positions. 7.3.2 Equipment This test requires a power supply capable of maintaining the rated voltage. 7.3.3 Procedure WARNING—Follow all safety procedures described in Section 2.
Page 450
KS 3-2010 Page 20 Auxiliary Switch Tests Figure 9 Sample Auxiliary Switch 7.4.1 Purpose To verify that the contacts of the auxiliary switch(es) (see Figure 9) change status when the main switch contacts are opened and closed. 7.4.2 Equipment This test requires an ohmmeter or low voltage continuity tester. 7.4.3 Procedure WARNING—Follow all safety procedures described in Section 2.
Page 451
KS 3-2010 Page 21 7.4.3.6 When the test is completed, reconnect the control circuit wires to the terminals (or leads) of the auxiliary switch(es). If an under-voltage trip release device was connected, refer to 7.2.3.5 for instructions. 7.4.4 Results Each auxiliary contact should change position (move from open to closed or vice versa) as the main switch is operated from the OFF to ON or ON to OFF positions.
Page 455
DT363NWK to DT663URK ........12 RP00801001E For more information visit: www.cutler-hammer.eaton.com...
Page 456
Switch Interior Assembly 70-8063-3 Fuse Base 70-8063-7 70-8063-8 70-7833-5 70-7833-2 DH225NPK Switch Interior Assembly 70-8063-3 Fuse Base 70-8063-7 70-8063-8 70-7833-5 70-7833-2 DH225NRK Switch Interior Assembly 70-8063-3 Fuse Base 70-8063-7 70-8063-8 70-7833-5 70-7833-2 Two used. Three used. For more information visit: www.cutler-hammer.eaton.com RP00801001E...
Page 457
DH321FWKX Switching Base 70-7758-14 Fuse Base 70-7758-26 70-7758-34 70-8304 70-7813-3 DH321FWK2JK Switching Base 70-7831 Fuse Base 70-7831-3 70-7758-34 70-7813 70-7813-3 DH321NCK Switching Base 70-7758-14 Fuse Base 70-7758-26 70-7758-34 — — Two used. Three used. RP00801001E For more information visit: www.cutler-hammer.eaton.com...
Page 458
Switch Interior Assembly 70-8063-4 Fuse Base 70-8063-7 70-8063-8 70-7833-5 70-7833-2 DH325FGK Switch Interior Assembly 70-8063-4 Fuse Base 70-8063-7 70-8063-8 70-7833-5 70-7833-2 DH325FPK Switch Interior Assembly 70-8063-4 Fuse Base 70-8063-7 70-8063-8 70-7833-5 70-7833-2 Three used. For more information visit: www.cutler-hammer.eaton.com RP00801001E...
Page 459
70-7831-3 70-7758-34 70-7813 70-7813-3 DH361NCK Switching Base 70-7758-12 Fuse Base 70-7758-27 70-7758-34 — — DH361NDK Switching Base 70-7758-12 Fuse Base 70-7758-27 70-7758-34 70-7813 70-7813-2 DH361NDK-10 Switching Base 70-7758-12 Fuse Base 70-7758-27 — 70-7813 70-7813-2 RP00801001E For more information visit: www.cutler-hammer.eaton.com...
Page 460
70-7997-7 70-7758-34 70-7813 70-7813-3 DH362NWKW Switching Base 70-7997-2 Fuse Base 70-7997-7 70-7758-34 70-7813 70-7813-3 DH362NWKW2 Switching Base 70-7997-2 Fuse Base 70-7997-7 70-7758-34 70-7813 70-7813-3 DH362NWKX Switching Base 70-7997-2 Fuse Base 70-7997-7 70-7758-34 70-8304 70-7813-3 For more information visit: www.cutler-hammer.eaton.com RP00801001E...
Page 461
Switching Base 70-7758-5 — — 70-7758-35 70-7813 70-7813-2 DH363UDK3 Switching Base 70-7758-5 — — 70-7758-35 70-7813 70-7813-2 DH363UGK Switching Base 70-7758-5 — — 70-7758-35 70-7813 70-7813-2 DH363UGK2 Switching Base 70-7758-5 — — 70-7758-35 70-7813 70-7813-2 RP00801001E For more information visit: www.cutler-hammer.eaton.com...
Page 462
Switch Interior Assembly 70-8063-6 Fuse Base 70-8063-7 70-8063-8 70-7833-5 70-7833-2 DH365NPK Switch Interior Assembly 70-8063-6 Fuse Base 70-8063-7 70-8063-8 70-7833-5 70-7833-2 DH365NPKLW Switch Interior Assembly 70-8063-6 Fuse Base 70-8063-7 70-8063-8 70-7833-5 70-7833-2 Three used. For more information visit: www.cutler-hammer.eaton.com RP00801001E...
Page 463
Switching Base 70-7759-9 Fuse Base 70-7759-4 70-7759-12 70-7833-4 70-7833-2 Consult Factory Consult Factory 70-7833-4 70-7833-2 DH424FGK Switching Base Consult Factory Fuse Base DH425FGK Switch Interior Assembly 70-8270 Fuse Base 70-8063-7 70-8270-4 70-7833-5 70-7833-2 Four used. RP00801001E For more information visit: www.cutler-hammer.eaton.com...
Page 464
— DT224URK Switching Base 70-8059 — — — — — DT224URK-EXC Switching Base 70-8059 — — — — — DT224URK-N Switching Base 70-8059 — — — — — Two used. Four used. Six used. For more information visit: www.cutler-hammer.eaton.com RP00801001E...
Page 465
DT363FGK Switching Base 70-7758-3 Fuse Base 70-7758-21 70-7758-35 — — DT363FRK Switching Base 70-7758-3 Fuse Base 70-7758-21 70-7758-35 — — DT363FWK Switching Base 70-7758-3 Fuse Base 70-7758-21 70-7758-35 — — Two used. Upper. Lower. RP00801001E For more information visit: www.cutler-hammer.eaton.com...
Page 469
Nameplate Field Installed Kits Safety Switch Catalog No. DH261FGK The information on this PREPARED BY DATE Eaton Corporation document is created by Eaton JerryRPetruk 04/26/13 Corporation. It is disclosed APPROVED BY DATE JOB NAME Banner AC Discos in confidence and it is only...
Page 473
Nameplate Field Installed Kits Safety Switch Catalog No. DH261FGK The information on this PREPARED BY DATE Eaton Corporation document is created by Eaton JerryRPetruk 04/26/13 Corporation. It is disclosed APPROVED BY DATE JOB NAME Banner AC Discos in confidence and it is only...
Page 477
Nameplate Field Installed Kits Safety Switch Catalog No. DH261FGK The information on this PREPARED BY DATE Eaton Corporation document is created by Eaton JerryRPetruk 04/26/13 Corporation. It is disclosed APPROVED BY DATE JOB NAME Banner AC Discos in confidence and it is only...
Page 481
Nameplate Field Installed Kits Safety Switch Catalog No. DH261FGK The information on this PREPARED BY DATE Eaton Corporation document is created by Eaton JerryRPetruk 04/26/13 Corporation. It is disclosed APPROVED BY DATE JOB NAME Banner AC Discos in confidence and it is only...
Page 485
"R" Fuse Adapter Kit : DS46FK (Field Installed) Safety Switch Catalog No. DH364FRK The information on this PREPARED BY DATE Eaton Corporation document is created by Eaton EricSNims 04/29/13 Corporation. It is disclosed APPROVED BY DATE JOB NAME Banner Health Centers...
Page 489
"R" Fuse Adapter Kit : DS46FK (Field Installed) Safety Switch Catalog No. DH324NGK The information on this PREPARED BY DATE Eaton Corporation document is created by Eaton EricSNims 04/29/13 Corporation. It is disclosed APPROVED BY DATE JOB NAME Banner Health Centers...
Page 493
"R" Fuse Adapter Kit : DS26FK (Field Installed) Safety Switch Catalog No. DH362FRK The information on this PREPARED BY DATE Eaton Corporation document is created by Eaton EricSNims 04/29/13 Corporation. It is disclosed APPROVED BY DATE JOB NAME Banner Health Centers...
Page 497
"R" Fuse Adapter Kit : DS12FK (Field Installed) Safety Switch Catalog No. DH321NRK The information on this PREPARED BY DATE Eaton Corporation document is created by Eaton EricSNims 04/29/13 Corporation. It is disclosed APPROVED BY DATE JOB NAME Banner Health Centers...
Page 501
"R" Fuse Adapter Kit : DS26FK (Field Installed) Safety Switch Catalog No. DH362FRK The information on this PREPARED BY DATE Eaton Corporation document is created by Eaton JerryRPetruk 04/29/13 Corporation. It is disclosed APPROVED BY DATE JOB NAME Banner Health Centers...
Page 505
"R" Fuse Adapter Kit : DS12FK (Field Installed) Safety Switch Catalog No. DH221NGK The information on this PREPARED BY DATE Eaton Corporation document is created by Eaton JerryRPetruk 04/29/13 Corporation. It is disclosed APPROVED BY DATE JOB NAME Banner Health Centers...
Page 509
Nameplate Field Installed Kits Safety Switch Catalog No. DH361UGK The information on this PREPARED BY DATE Eaton Corporation document is created by Eaton JerryRPetruk 04/29/13 Corporation. It is disclosed APPROVED BY DATE JOB NAME Banner Health Centers in confidence and it is only...
Page 519
Technical Information Publication 8231 Page 1 ECN01, ECN02, ECN05, ECN06, ECN07 AN16, AN56, CN15 & CN55 NEMA Sizes 00-9, 600V Max. February 2, 1998 Non-Reversing & Reversing Contactors & Starters Supersedes TIP AN16, AN56, CN15, CN55 NEMA Type Enclosures 1, 3R, 4X & 12 Pages 1-20, Dated 1/1/94 Details On UL &...
Page 520
Technical Information Publication 8231 Page 2 NEMA, Contactors & Starters, (Freedom) DESIGN CHARACTERISTICS (Continued) OPTIONAL FEATURES • • ± Terminals — Size 00 through 1 screw type with Auxiliary Contacts — Open type starters will accept captive, backed-out self-lifting pressure plates. Fin- up to 8 NO or NC auxiliary contacts (4 for Size 8) —...
Page 521
Technical Information Publication 8231 Page 3 NEMA, Contactors & Starters, (Freedom) The “Freedom Series” starters feature a compact space saving Tamper proof overload relay adjustment locking covers snap design using state-of-the-art technology and the latest in high over the top of overload relays to prevent accidental turning of strength, impact and temperature resistant insulating materials.
Page 522
Technical Information Publication 8231 Page 4 NEMA, Contactors & Starters, (Freedom) Side Auxiliary Contacts — All starters are supplied as stand- Diagram Heater Pack Selection Table ard with one normally open (1 NO) auxiliary contact for use as Motor FLA Rating Heater a holding circuit contact.
Page 523
Technical Information Publication 8231 Page 5 NEMA, Contactors & Starters, (Freedom) – ON DELAY/OFF DELAY - Timer delay occurs on DC Magnet Coils — Dc Magnet Coils are available either fac- both energization and deenergization of timer. tory installed or as field conversion kits. –...
Page 524
Technical Information Publication 8231 Page 6 NEMA, Contactors & Starters, (Freedom) Mechanical Interlock and Reversing Kits — These kits are Short Circuit Protection — Fuses and Inverse-Time Circuit available for field assembly of reversing starters using Breakers may be selected per Article 430, Part D of the components.
Page 525
Technical Information Publication 8231 Page 7 NEMA, Contactors & Starters, (Freedom) Electrical Data REFERENCE DATA NEMA Maximum Horsepower NEMA AN16 Starters — High Fault Current Circuit Ampere Size Ratings — UL508 Rating, Motor Voltage φ φ Frame Continuous 60 Hz Cir Bkr Short Width...
Page 527
Technical Information Publication 8231 Page 9 NEMA, Contactors & Starters, (Freedom) AC COIL DATA P.U. Volts P.U. Sealed D.O. Volts Mech. Max. P.U. D.O. NEMA Operation Time Time Sizes Rate Cold Watts Watts Cold Ops/Hour 74.0% 10,800 74.0% 10,800 74.0% 7,200 72.0% 49.8...
Page 528
Technical Information Publication 8231 Page 10 NEMA, Contactors & Starters, (Freedom) RENEWAL PARTS Magnet Coils Coil Volts and Hertz Size 00 Size 0 Size 1-2 Size 3 Size 4-5 120/60 or 110/50 9-2823-1 9-2824-1 9-2703-1 9-2756-1 9-1891-1 240/60 or 220/50 9-2823-2 9-2824-2 9-2703-2...
Page 529
Technical Information Publication 8231 Page 11 NEMA, Contactors & Starters, (Freedom) RENEWAL PARTS Magnet Coils (Continued) Size 8 Coil Volts and Hertz Common Control Separate Control Main Coils Feeder Group Main Coils Feeder Group 120/50-60 9-2654 9-2664 208/50-60 9-2654-6 9-2664-6 240/50-60 9-2654-2 9-2664-2...
Page 530
Technical Information Publication 8231 Page 12 NEMA, Contactors & Starters, (Freedom) APPROXIMATE DIMENSIONS AND SHIPPING WEIGHTS Do not use for construction. NON-REVERSING OPEN TYPE SIZE 00 & 0 SIZE 1 & 2 SIZE 3 & 4 MOUNTING SCREWS — #1/2 - 13 SIZE 9 SIZE 5 SIZES 6 THROUGH 8...
Page 531
Technical Information Publication 8231 Page 13 NEMA, Contactors & Starters, (Freedom) APPROXIMATE DIMENSIONS AND SHIPPING WEIGHTS (Continued) Do not use for construction. REVERSING OPEN TYPE SIZE 4-5 SIZE 00-2 SIZE 3 MTG. FOR (8) 1/2-13 SCREWS MOUNTING SCREWS #1/2 - 13 SIZE 9 SIZE 6 OPEN TYPE —...
Page 532
Technical Information Publication 8231 Page 14 NEMA, Contactors & Starters, (Freedom) APPROXIMATE DIMENSIONS AND SHIPPING WEIGHTS (Continued) Do not use for construction. NON-REVERSING & REVERSING CONTACTORS — ENCLOSED TYPE NEMA 1 Dimensions in Inches [mm] Ship Mounting NEMA Size (poles) Wide High Deep...
Page 533
Technical Information Publication 8231 Page 15 NEMA, Contactors & Starters, (Freedom) APPROXIMATE DIMENSIONS AND SHIPPING WEIGHTS (Continued) Do not use for construction. NON-REVERSING & REVERSING CONTACTORS — ENCLOSED TYPE NEMA 3R, 4/4X & 12 Dimensions in Inches [mm] Ship Mounting NEMA Size (poles) Wide High...
Page 534
Technical Information Publication 8231 Page 16 NEMA, Contactors & Starters, (Freedom) APPROXIMATE DIMENSIONS AND SHIPPING WEIGHTS (Continued) Do not use for construction. NON-REVERSING & REVERSING STARTERS — ENCLOSED TYPE NEMA 1 Dimensions in Inches [mm] Ship Mounting NEMA Size (poles) Wide High Deep...
Page 535
Technical Information Publication 8231 Page 17 NEMA, Contactors & Starters, (Freedom) APPROXIMATE DIMENSIONS AND SHIPPING WEIGHTS (Continued) Do not use for construction. NON-REVERSING & REVERSING STARTERS — ENCLOSED TYPE NEMA 3R, 4/4X & 12 Dimensions in Inches [mm] Ship Mounting NEMA Size (poles) Wide High...
Page 553
1. The nameplate ratings of the con- plant location where it is to be troller must agree with the power ® Eaton’s Cutler-Hammer installed. supply and the rating of the load Enclosed Control Units (motor).
Technical Data Storage, Handling, Installation and Page 2 Effective: January 2005 Maintenance of Controllers General guidelines 4. For the connections between a DC 12. Close the circuit to the power sup- ammeter shunt and a remotely ply. If a motor controller has sepa- The whole purpose of maintaining mounted ammeter, choose a wire rate switches for the power circuit...
Page 555
Storage, Handling, Technical Data Installation and Page 3 Effective: January 2005 Maintenance of Controllers Cleaning Mechanical checks temporary wiring should be removed, or permanently secured and diagrams Soot, smoke, or stained areas (other Tighten all electrical connections. Look marked accordingly. than inside arc chutes), or other for signs of overheated joints, charred unusual deposits, should be investi-...
Page 556
Technical Data Storage, Handling, Installation and Page 4 Effective: January 2005 Maintenance of Controllers Figure 2. New Figure 3. Start of Service Life Figure 4. End of Service Life Table 1. Contact Evaluation Time of Service Contact Appearance The new contact has a uniform silver color. (See Figure 2 .) Start of Service The contact surface will have a blue coloring.
Page 557
Storage, Handling, Technical Data Installation and Page 5 Effective: January 2005 Maintenance of Controllers Troubleshooting Table 3. Contactor Troubleshooting Chart Defect Cause Remedy Contactor Overheating Load current too high Reduce load. Use larger contactor. Loose connections Clean discolored or dirty connections and retighten. Replace poorly crimped lugs.
Page 558
Technical Data Storage, Handling, Installation and Page 6 Effective: January 2005 Maintenance of Controllers Table 3. Contactor Troubleshooting Chart, Continued Defect Cause Remedy Contacts, continued Short Contact Life or Filing or dressing DO NOT FILE SILVER CONTACTS. Rough spots or discoloration will not harm Overheating contacts or impair their efficiency.
Page 559
Storage, Handling, Technical Data Installation and Page 7 Effective: January 2005 Maintenance of Controllers Table 3. Contactor Troubleshooting Chart, Continued Defect Cause Remedy Manual Starters Failure to Operate Worn or broken mechanical parts Replace unit. Mechanically Welded contacts due to misapplication or Replace contacts and use correct application.
Page 563
Horizontal or vertical ● number following a short-circuit fault. mounting on upright panel Designed to meet or ● for application freedom exceed UL, CSA ® , IEC, VDE, BS and other international standards and listings V10-T2-2 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com...
Page 564
Renewal Parts ......Tab 16 Technical Data and Specifications ... . Tab 17 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com V10-T2-3...
Page 565
When control power transformer modification codes (C1–C11) are used or when starter class 240/480/600 wired for 480V includes CPT (that is ECN07, 18) see the table at right for system voltage code. By description — V10-T2-4 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com...
Page 566
Add code letter from the table below to catalog number for voltage—kits only. Example: C400GK0B. Rating Code Letter Rating Code Letter Rating Code Letter 120V 60 Hz 277V 60 Hz 480V 60 Hz 208V 60 Hz 380V 50 Hz 600V 60 Hz 240V 60 Hz Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com V10-T2-5...
Page 567
Code Letter Rating Code Letter Rating Code Letter 120V 60 Hz 277V 60 Hz 480V 60 Hz 208V 60 Hz 380V 50 Hz 600V 60 Hz 240V 60 Hz Order quantity (2) of C400T10. V10-T2-6 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com...
Page 568
R63/F R64/F 60–300 R63/G R64/G 120–600 R63/H R64/H Notes Features: • Self-powered • Phase loss protection • Current adjustment knob • ±1% repeat accuracy • 1NO and 1NC isolated contacts Not UL Listed. Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com V10-T2-7...
Page 569
Type 12 enclosure is without safety door interlock. When safety door interlock is required, add modification E11. Fuse clips are for Class R fuses. For H and J fuses, see modifications in Tab 15. Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com V10-T2-33...
Page 570
Type 12 enclosure is without safety door interlock. When safety door interlock is required, add modification E11. Type 4 (painted steel) sizes 6–9. Supply hp, voltage, FLA and whether motor is design E or not when ordering the motor. For 1250 and 1600 hp ratings at 460V, consult Eaton. V10-T2-34 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com...
Page 571
All Type 12 enclosures are standardized with external reset. For internal reset, order modification code R5. Type 12 enclosure is without safety door interlock. When safety door interlock is required, add modification E11. Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com V10-T2-35...
Page 572
Type 12 enclosure is without safety door interlock. When safety door interlock is required, add modification E11. Type 4 (painted steel) sizes 6–9. Supply hp, voltage, FLA and whether motor is design E or not when ordering the starter. For 1250 and 1600 hp ratings at 460V, consult Eaton. V10-T2-36 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com...
Connect Separate Control Lines to Stop Use with 3/14 the Number 1 Terminal on the Remote Auto Reset 2/13 Pilot Device and to the Number 96 Stop OL Relays Terminal on the Overload Relay 260878 D4 “A” V10-T2-48 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com...
Page 574
Remove Wire “C” When it is Supplied. Connect Separate Control Lines to the Number 1 Forward Terminal on Remote Pilot Device, and to the Number 95 Terminal on the Overload Relay 260882 D4 Reverse Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com V10-T2-49...
Page 575
Right Hand Contactor Figure B Figure D Black Three-Position Selector Switch Pilot Light (REVERSE) Black/White Black Black Forward Connect to Reverse Coil Terminals Black “A1” and “A2” Blue Black/White 260810 D1 Reverse 260812 D1 V10-T2-50 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com...
Page 576
Common control. For separate 120V control, insert letter D in 7th position of listed catalog number. Example: AN56VND0CB. NEMA Sizes 00 and 0 only. NEMA Sizes 00 and 0 only. Sizes 1–8 are 24/60 only. Control Products Catalog CA08102001E—August 2010 www.eaton.com...
Page 577
Minimum per NEC. Maximum wire size: Sizes 00 and 0 to 8 AWG and Sizes 1–2 to 2 AWG. Two compartment box lug. Maximum horsepower where operation is interrupted more than 5 times per minute, or more than 10 times in a 10 minute period. NEMA Standard ICS2-1993 table 2-4-3. Control Products Catalog CA08102001E—August 2010 www.eaton.com...
Page 581
The information on this PREPARED BY DATE Eaton Corporation document is created by Eaton EricSNims 04/29/13 Corporation. It is disclosed APPROVED BY DATE JOB NAME Banner Health Centers in confidence and it is only to be used for the purpose in...
Page 583
The information on this PREPARED BY DATE Eaton Corporation document is created by Eaton EricSNims 04/29/13 Corporation. It is disclosed APPROVED BY DATE JOB NAME Banner Health Centers in confidence and it is only to be used for the purpose in...