Honeywell IdentIPoint Installation Instructions Manual page 26

Intelligent smartcard system
Hide thumbs Also See for IdentIPoint:
Table of Contents

Advertisement

HONEYWELL IDENTIPOINT™ INTELLIGENT SMARTCARD SYSTEM
DETAILED WIRING DIAGRAMS
Single Reader with REX and without IOM
To LAN
To Door Sensor
To REX Switch
To Door Lock
DC Power
DC – Power
12 to 24V
If PoE is not used.
To electrical
earth.
If unavailable,
connect to
Power-GND.
LEGEND
In the above configuration, one IdentIPoint reader operates in
stand-alone mode to control door access. It authenticates
users as well as releases the door lock using its relay contact.
Minimum Connections:
1. Connect the Ethernet/PoE cable to the RJ45 port of the
reader through the CAT5 pigtail. (Frame-GND connec-
tion to building GROUND Earth is recommended for
better electro-static discharge resilience.) See Fig.7.
2. If PoE switch is not used, connect a 12-24VDC power
supply to pins 1-2 (Power-IN - Power-GND) of port J9 of
the reader. See section Wire the Readers and IOM of
Wiring the Readers and IOM topic for details on power
supply connections.
95-7767
1KΩ
2KΩ
1KΩ
2KΩ
Power – Min. 18 AWG
Power Gnd – Min. 18 AWG
Ethernet – CAT5
Signal/Power – Min. 18 AWG
Signal
Signal – Min 18 AWG
Min. 18 AWG
Signal – Min. 18 AWG
Fig. 21. Connections for single reader with REX and without IOM
Ethernet
J9
PIN
PIN
9
1
SAI-1-GND
8
2
SAI-1
SAI-0-GND
7
3
6
4
SAI-0
R
l e
y a
N -
O
5
5
4
Relay-NC
6
3
7
Relay-C
2
2
8
8
Power-GND
Power GND
1
Power-IN
9
10
IdentIPoint Reader
3. Connect pin(s) 3/4/5 (Relay-C/Relay-NC/Relay-NO) of
port J9 to the door lock depending on the type of lock
(magnetic lock or door strike) used and the safety codes
to be followed. Also connect a power line to the lock.
See Wiring Other Devices topic for detailed wiring of
locks.
4. Connect pins 6-7 (SAI-0 - SAI-0-GND) and 8-9 (SAI-1 -
SAI-1-GND) to a Request-to-Exit (REX) switch and door
sensor with proper termination circuit as described in
section Supervisory Analog Input (SAI) termination cir-
cuit of Wiring Other Devices topic. An additional sensor
can be connected to SAI-2 of port J10.
26
J10
Power-OUT
Power-GND
RS485-A
RS485-B
RS485-GND
DO
DOGnd
SAI 2
SAI-2
SAI-2-GND
Frame-GND
S1