HONEYWELL IDENTIPOINT™ INTELLIGENT SMARTCARD SYSTEM
3. Click Test. The selected color blinks on the LED.
4. Click Exit. Exit from the LED test window.
To perform keypad test:
1. Click Keypad Test from the Diagnostics and Tools list.
The Keypad Test window is displayed.
2. Click Test to initiate the test.
3. Type any 'num' keys on the keypad. The same text is
displayed on the LCD of the reader.
4. Click Exit to close the page.
To perform IO test:
1. Click IO Test from the Diagnostics and Tools list, the
IO Test page is displayed.
2. For testing the output points select an output point from
the Output Point drop-down list.
a. Select a state from the State drop-down list.
b. Click Command, to set the command. The device
connected to the respective output point is set to the
appropriate selected state.
3. For testing the input points select an input point from the
Input Point dropdown list.
a. Click Read, to read the input channel status.
b. The state of the device that is connected to the input
point is displayed in the Current State text box.
To reboot the reader:
1. Click Reboot Reader from the Diagnostics and Tools
list. The Reboot Reader page is displayed.
2. Click Reboot, reboots the card reader.
To check the IP:
NOTE: The availability of an IP address is checked on
Ethernet and Wireless page.
1. Click Ping from the Diagnostics and Tools list on Ether-
net or Wireless page. The Ping page is displayed.
2. Type the IP to be searched in IP address to ping text
box.
3. Click Ping. The result is displayed on the Ping result
window.
To perform a factory reset on the reader:
1. Keeping the reader powered on normally, remove it from
the back-plate and find the factory reset switch at its
back (see Fig.3).
2. Press the factory reset switch for 10 seconds or more
until the reader LED/LCD is turned off.
3. When the LED/LCD is off, release the factory reset
switch.
4. Wait for the reader to restart.
5. If using an LCD model, the Honeywell banner will
appear on the display for a few seconds and then disap-
pear.
95-7767
6. Within 1 minute, the reader LED will start flashing green
indicating that the reader has been reset to the factory
firmware.
7. If using an LCD model with a DHCP server connected
via Ethernet, the following will appear on the display
within 1 minute:
Honeywell
IdentIPoint
Version: 1.0.18.0
aaa.bbb.ccc.ddd (where "aaa.bbb.ccc.ddd" is the IP
address assigned by DHCP)
8. If using an LCD model WITHOUT a DHCP server con-
nected via Ethernet, the following will appear on the
display within 3 minutes:
Honeywell
IdentIPoint
Version: 1.0.18.0
<blank> (no IP address assigned)
NOTE: In case factory reset fails (which might happen if
the factory reset switch is not released in time at
step 3), the reader will beep multiple times while
it is restarting. Afterwards it will not respond
when a card is presented.
To recover from factory reset failure:
1. Power off the reader and power it on again.
2. Wait for the reader to start in normal mode.
3. Repeat all the required factory reset steps above.

LIGHTNING PROTECTION

Standard Lightning Protectors
If the Bus wiring enters or exits the building, the protector (s)
listed in Table.13 must be used. Bus length must not exceed
3277 ft. (999 m). Refer to Honeywell Form No.95-7266
14502412 Lightning Protector Installation Instructions, and
applicable local codes and standards for lightning protector
installation.
Table 13. Lightning and Surge Protectors
Part Number
14502412-011
120VAC Input Line
14502412-012
Low Voltage Input Line
14502412-014
Transmission Bus (RS485, F&S and
Security Bus) Secondary Protection
14502412-020
Transmission Bus (RS-232 Bus)
Secondary Protection
14507678-004
Ethernet Port Surge Protector
46