Start-up
When the module is connected to the drive, the drive control program sets the applicable parameters.
See the appropriate drive manual.
Basic parameter settings
Index
Name
20.01
Ext1 commands
22.11
Speed ref1 source
28.11
Frequency ref1 source
50.01
FBA A enable
50.02
FBA A comm loss func
51.04
IP configuration
51.05...08
IP address
51.09
Subnet CIDR
51.14
Device obj ID lo
51.15
Device obj ID hi
To take the settings into use, validate and refresh the parameters with parameter 51.27 FBA par refresh.

Further information

See the latest version of FBIP-21 BACnet/IP adapter
module user's manual (3AXD50000028468 [English]) in
ABB library (www.abb.com/drives/documents)
FBIP-21 manual
3AXD50000158171 Rev A (EN) 2017-11-23
Value
Fieldbus A
FBA A ref 1
FBA A ref 1
Enable (or select the option slot in which the module is installed).
This activates the communication module. The HOST LED becomes green.
Fault
Set the IP address according your network configuration.
Set a unique device object instance value for BACnet devices.
For more information on fieldbus options and protocols
provided by ABB Drives, see the fieldbus
communications web page
.
(new.abb.com/drives/connectivity/fieldbus-connectivity).