Download Print this page

Siemens ABHW-4BZ Installation Instructions Manual page 8

Intelligent audible base

Advertisement

FROM THE DEVICE LINE OF
THE COMPATIBLE LISTED
IN THE SPECIFICATION
Note:
1.
The NAC circuit shown in the diagram is the active state at terminal 1 and 2 of ABHW-4BZ.
2.
ABHW-4BZ terminals 5-6 are polarity insensitive. Line 1 and Line 2 can be either line of
device loop.
3.
The wiring at NAC of PAD-3/PAD-4/PAD-5 shown in the diagram for ABHW-4BZ is Style Z
(Class A)(No EOL needed). If Style Y (Class B) wiring used at NAC output, EOL (24K, 0.5W
resistor) must be used.
4.
For the max load current and max cable resistance, refer to the specifications of PAD-
3/PAD-4/PAD-5, P/N: 315-099082/315-050217/A6V101030358.
Figure 3
Installation/Wiring Diagram for ABHW-4BZ Audible Base Powered by NAC of
PAD-3/PAD-4/PAD-5 system
FROM THE DEVICE LINE OF
THE COMPATIBLE LISTED
IN THE SPECIFICATION
Note:
1.
The NAC circuit shown in the diagram is the active state at terminal 1 and 2 of ABHW-4BZ.
2.
ABHW-4BZ terminals 5-6 are polarity insensitive. Line 1 and Line 2 can be either line of
device loop.
3.
The wiring at NAC of FC2005/FC901 shown in the diagram for ABHW-4BZ is Style Z (Class
A) (no EOL needed). If Style Y (Class B) wiring used at NAC output, EOL (24K, 0.5W
resistor) must be used.
4.
For the max load current and max cable resistance, refer to the specifications of FC2005/FC901.
Figure 4.1
Installation/Wiring Diagram for ABHW-4BZ Audible Base Powered by NAC of
FC2005/FC901
LINE 1
LINE 2
8
7
6
5
ABHW-4BZ
1
2
3
4
NAC1 NAC1 NAC2 NAC2 NAC3 NAC3 NAC4 NAC4
NAC outputs of PAD-3/
PAD-4/PAD-5
LINE 1
LINE 2
5
8
7
6
ABHW-4BZ
1
2
3
4
N_AN N_AP N_BN N_BP
NAC outputs of
F 2005 / FC901
C
8
1b
6
5
1a
8
7
6
5
ABHW-4BZ
1
2
3
4
6
5
5
8
7
6
ABHW-4BZ
1
2
3
4
LINE 2
TO NEXT
ADDRESSABLE
DEVICE
LINE 1
LINE 2
TO NEXT
1b
ADDRESSABLE
DEVICE
1a
LINE 1

Advertisement

loading