ALARM LED LOCATION
INSTALLED IN BASE
Figure 8
Positioning the Alarm LED
1. When installing FD-UL detectors in a FireFinder XLS panel,
2. When the audible base ABHW-4BZ works with FD-UL series
3. When the audible base ABHW-4BZ works with H-series
4. When use "External Powered" for alarm, the ABHW-4BZ still
5. For additional information on the modules used in an
WITH DETECTOR
use the following panel versions
PMI ver 10.02 or later
Zeus ver 10.02 or later
DLC ver 06.01 or later
detectors. Up to 6 tone patterns and 2 volume levels can be
selected by user with system configuration tool; there are
two power types for ABHW-4BZ during alarm, "Loop
Powered" and "External Powered" which can be configured
by system tool.
detector Only "External Powered" can be used. A fixed 85dB
tone is provided and only 2 tones can be selected (steady
and Temporal 3, refer to Figure 6): Steady: without a jumper
at terminals 3 and 4; Temporal 3: terminals 3 and 4 are
shorted with jumper.
takes some power from loop during both supervision and
alarm status to keep it alive and external power is only for
the alarm current.
individual system, refer to the Installation Instructions for that
particular module or contact your authorized Siemens
Industry, Inc. representative.