The analog-input multiplexer system

The MTL838C is an analog multiplexer receiver that is used with the MTL831C
hazardous area millivolt input multiplexer transmitter. The status of up to 32 analog
inputs may be communicated from the hazardous area to the safe area via a data
highway, comprised of a simple twisted pair - over distances up to 2000m.
Each data highway must be protected by an MTL5553/5053 digital isolator when
the inputs are located in a Zone 0,1 hazardous area. The MTL831C is typically used
with thermocouple and RTD inputs and is intrinsically safe. It can be mounted in a
Zone 0,1 hazardous area and will accept 16 inputs. For systems that do not require
Zone 0 or Zone 1 installation, the MTL5553/5053 can be eliminated.
Up to two MTL831C transmitters can be combined on a single MTL838C receiver
input - up to a total of 32 analog inputs - as shown in Figure 1.
The MTL838C acts as a Modbus slave . It may be connected into any standard
Modbus network, with up to 31 MTL838C slaves on each network. If each unit has
its full complement of 32 analog inputs, the status of a total of 992 analog inputs
may be passed to a Modbus master using a single RS485 network.
3 .2

Configuring the MTL838C

The MTL838C must first be configured using software on a PC and the USB
connection. This configures things such as the slave address and communication
parameters. After the initial configuration, the MTL838C is ready to communicate
with the Modbus host. At this point, the remaining configuration may be done in
one of two ways:
Using the PC software is required for initial configuration and recommended for
first time configuration of the measuring channels.
INM MTL83xC PC Modbus Rev 1
DRAFT - 06 January 2019

BACKGROUND TO THE MTL838C

Zone 0, 1 or 2
Hazardous Area
MTL831C
transmitter 1
mV
Up to 16 THC, RTD,
potentiometer
and mV inputs
Sensors can be in Zone 0
MTL831C
transmitter 2
mV
Up to 16 THC, RTD,
potentiometer
and mV inputs
Figure 1 - MTL838C/MTL831C System Diagram
• on-line via the Modbus link, direct from the host
• off-line using the PC software and USB connection
Safe Area
MTL5553/5053
isolator/PSU
DATA HIGHWAY (BUS)
19-30Vdc
Power
MTL838C
receiver
PLC
RS485
RS485
USB
2x SPST
relay
contacts
PC
(MTL 83xC Configurator Software)