Chapter 3. Function And Operation Of Pro- Tective Procedures Protection Device Functions And Operations - Sharp AY-XP9LSR Service Manual

Hide thumbs Also See for AY-XP9LSR:
Table of Contents

Advertisement

AYXP9LSR
CHAPTER 3.
AYXP9LSR
FUNCTION AND OPERATION OF PROTECTIVE PROCEDURES
[1] PROTECTION DEVICE FUNCTIONS AND OPERATIONS
* These models no have Expansion valve, Suction temp. thermo. and 2-way valve temp. thermo.
Function
1
Indoor unit fan lock
Operation stops if there is no
input of rotation pulse signal from
indoor unit fan motor for 1 minute.
Indoor unit fan rota-
Operation stops if rotation pulse
tion speed error
signal from indoor unit fan indi-
cates abnormally low speed
(about 300 rpm or slower).
2
Indoor unit freeze
Compressor stops if temperature
prevention
remains below 0°C for 4 minutes.
3
2-way valve freeze
Compressor stops if temperature
prevention
of outdoor unit 2-way valve
remains below 0°C for 10 continu-
ous minutes during cooling or
dehumidifying operation.
4
Indoor unit heat
Operating frequency lowers if
exchanger over-
indoor unit heat exchanger tem-
heat shutdown
perature exceeds overheat tem-
perature during heating
operation.
Compressor stops if indoor unit
heat exchanger temperature
exceeds overheat temperature for
60 seconds at minimum fre-
quency.
Overheat temperature setting
value indoor unit heat exchanger
thermistor temperature: about 45
to 54°C
5
Outdoor unit heat
Operation frequency lowers if out-
exchanger over-
door unit heat exchanger temper-
heat shutdown
ature exceeds about 55°C during
cooling operation.
Compressor stops if outdoor unit
heat exchanger temperature
exceeds about 55°C for 120 sec-
onds at minimum frequency.
6
Compressor dis-
Operating frequency lowers if
charge overheat
temperature of compressor
shutdown
chamber thermistor (TH1) falls
below about 110°C.
Compressor stops if temperature
of compressor chamber ther-
mistor (TH1) remains at about
110°C (for 120 seconds in cooling
operation, or 60 seconds in heat-
ing operation) at minimum fre-
quency.
7
Dehumidifying oper-
Compressor stops if outside air
ation temporary
temperature thermistor is lower
stop
than about 16°C during dehumidi-
fying operation.
8
DC overcurrent
Compressor stops if electric cur-
error
rent of about 25 A or higher flows
in IPM.
Operation
Description
Detection period
When indoor unit fan
is in operation
When indoor unit fan
is in operation
When in cooling or
dehumidifying opera-
tion
When in cooling or
dehumidifying opera-
tion
When in heating
operation
When in cooling or
dehumidifying opera-
tion
When compressor is
in operation
When in dehumidify-
ing operation
When compressor is
in operation
Service Manual
Reset condition
Operation OFF or ON *2
Operation OFF or ON *2
Automatic reset when
heat exchanger tem-
perature rises above
freeze prevention
temperature (2°C or
higher)
Automatic reset when
temperature of 2-way
valve rises above
10°C.
Automatic reset after
safety period (180
sec).
Automatic reset after
safety period (180
sec).
Automatic reset after
safety period (180
sec).
Automatic reset when
outside air tempera-
ture rises above
16°C.
Operation OFF or ON Yes *1
3 – 1
Self-diagnosis
result display
Indoor
Indoor
Outdoor
unit
unit
unit
error
display
Yes
None
Yes
None
None
None
None
Yes
Yes
None
Yes
Yes
None
Yes
Yes
None
Yes
Yes
None
Yes
Yes
Yes
Yes