[6] MALFUNCTION (PARTS) CHECK METHOD

1. Procedure for determining defective outdoor unit IPM/compressor
The following flow chart shows a procedure for locating the cause of a malfunction when the compressor does not start up and a DC overcurrent indi-
cation error occurs.
Connect power cord
to AC outlet.
Using remote control,
operate air conditioner
so
that
compressor
starts.
After about
20 seconds
Is
there
230
VAC
NO
between (1) and (N)
on outdoor unit PCB?
YES
NO
Is LED1 on outdoor
unit flashing?
YES
Compressor starts up.
Immediately
after startup
YES
Does LED1 indicate
DC overcurrent error?
NO
YES
Does LED1 indicate
rotation error?
NO
Normal
Check inter-unit wiring.
Check indoor unit PWB.
No
(unlit)
Does LED1 remain lit?
YES
Serial signal error.
Check wiring.
Check inter-unit wiring.
.
Check indoor and
outdoor unit PWBs.
Replace outdoor unit
Replace outdoor unit PWB.
PWB.
Check compressor.
2/3-way valve closed.
Refrigerant shortage.
OK
Replace outdoor unit
NO
Replace compressor.
3 – 8
AYXP9LSR
End.