Installation Instructions
Valve should be installed and adjusted by a licensed contractor in accordance with
local codes and ordinances. Further, this valve should be installed in a location where it
is accessible for cleaning, service or adjustment.
1. Close both the hot and cold water shutoff valves upstream nearest to the intended
installation.
2. Bleed the remaining water from the system.
3. Connect the water supply to valve as shown in Figure 1 or 2, depending on the
application. Supply piping must be flushed clean before making connections to the
valve.
IMPORTANT!: To prolong the life of the Model 1170-M2, L1170-M2, LF1170-M2 or
LFL1170-M2 valve, it is recommended that it be trapped as shown: i.e. the hot water
inlet to the 1170-M2 or LF1170-M2 valve should be 8" – 12" (200 – 305mm) below
the hot water supply feed.
4. Valve can be installed in any position. Note: the inlet hot supply is to be connected
to the "H" side of the valve, the cold supply side to the "C" side and the mixed water
outlet to the "M" side.
5. Make sure union nuts are placed over tailpieces prior to
soldering or threading to pipe.
6. For valves with Quick-Connect tailpieces refer to "Quick-
Connect Installation" instructions below.
Note: To prevent damage to valve from excessive heat during
soldering, remove unions and gaskets from valve body prior to
soldering.
7. After soldering, flush piping and install valve using filter washer
on hot and cold water inlet and fiber washer on the mixed
water outlet.
8. Start-up: Open cold water supply, then hot water supply.
Inspect for leaks.
9. Adjust temperature to desired setting (see Temperature
Adjustment Section).
Figure 1
Domestic Hot Water Application
Watts
Vacuum Relief
Valve
Watts T&P
Relief Valve
Domestic Hot Water Application
*Note: To prolong the life of the valve, it is recommended the
valve be trapped as shown
† Devices tested to ASSE 1070 or ASSE 1069 such as Watts
USG, LFUSG, L111, MMV or LFMMV should be used at
fixture to prevent possible injury.
*8" – 12"
1170-M2, L1170-M2
LF1170-M2 or LFL1170-M2
Cold
Quick-Connect Installation
To Connect
1
1
/
in. (38.1mm)
2
/
in.Pipe (12.7mm)
1
2
1
3
/
in. (44.45mm)
4
/
in.Pipe (19.05mm)
3
4
1
/
in. (47.63mm)
7
8
1 in.Pipe (25.4mm)
1. Mark pipe as shown.
This is pipe insertion depth.
PEX tubing only
Pipe Stiffener
Tail Piece
3. If using PEX tubing, insert pipe
stiffener (provided) into end of pipe.
To Disconnect
1. Remove collet clip.
IS-1170-M2_L1170-M2
LF1170-UT-M2
1170-QC-M2
2. Clean pipe end.
Collet clip
Mark
4. Push tubing into tailpiece up to mark.
5. Insert collet clip.
Collet depressed
2. Depress collet.
3. Pull tubing from tailpiece.

Advertisement

loading

Summary of Contents for Watts 1170 Series

  • Page 1 2. Depress collet. valve be trapped as shown 3. Pull tubing from tailpiece. † Devices tested to ASSE 1070 or ASSE 1069 such as Watts USG, LFUSG, L111, MMV or LFMMV should be used at fixture to prevent possible injury.
  • Page 2 Severe bodily injury (i.e. scalding or chilling) and/or death may result depending upon system water pressure changes. ASSE Standard 1016, ASSE 1070 listed devices such as Watts Model L111, LFL111 Series USG, LFUSG, MMV or LFMMV should be used at fixtures Colder to prevent possible injury.
  • Page 3 Watts 1170-M2, LF1170-M2, L1170-M2, LFL1170-M2 Troubleshooting Guide Problem & Cause Answer A. Unable to reach required set point or set point difficult to set A.1 Supply temperatures not within specified limits A.1 Check differential temperature between hot and cold supplies and outlet 10°F (5.6°C) minimum required...
  • Page 4 Limited Warranty: Watts Regulator Co. (the “Company”) warrants each product to be free from defects in material and workmanship under normal usage for a period of one year from the date of original shipment. In the event of such defects within the warranty period, the Company will, at its option, replace or recondition the product without charge.