Heat Anticipator Settings; Humidi-Mizer ® Control Connections - Carrier WeatherMaker 48FC04-07 Installation Instructions Manual

Single package rooftop gas heating/electric cooling unit with puron r-410a refrigerant
Table of Contents

Advertisement

Typical
Thermostat
Connections
C
G
W2
W1
O/B/Y2
(Note 1)
(Note 2)
Y1
R
Note 1: Typical multi-function marking. Follow manufacturer's configuration
Instructions to select Y2.
Note 2: Y2 to Y2 connection required on single-stage cooling units when
integrated economizer function is desired.
Field Wiring
Fig. 34 — Low-Voltage Thermostat Connections
Thermostat Wiring, Units Without Thru-Base Connection
Kit
Pass the thermostat control wires through the hole provid-
ed in the corner post; then feed the wires through the raceway
built into the corner post to the control box. Pull the wires
over to the terminal strip on the upper-left corner of the Unit
Control Board. See Fig. 35.
NOTE: If thru-the-bottom connections accessory is used, refer to
the accessory installation instructions for information on routing
power and control wiring.
RACEWAY
HOLE IN END PANEL (HIDDEN)
Fig. 35 — Field Control Wiring Raceway

HEAT ANTICIPATOR SETTINGS

Set heat anticipator settings at 0.14 amp for the first stage
and 0.14 amp for second-stage heating, when available.
Unit
Control
Board
C
HUM
T
H
G
E
R
W2
M
O
W1
S
T
Y2
A
T
Y1
R
HUMIDI-MIZER
CONTROL CONNECTIONS
®
Humidi-MiZer Space RH Controller
NOTE: The Humidi-MiZer system is a factory-installed option.
Humidi-MiZer system is not available for single phase (-3 volt-
age code) models.
The Humidi-MiZer dehumidification system requires a
field-supplied and field-installed space relative humidity con-
trol device. This device may be a separate humidistat control
(contact closes on rise in space RH above control setpoint) or
a combination thermostat-humidistat control device such as
Carrier's Edge
®
Pro Thermidistat™ device with isolated con-
tact set for dehumidification control. See Fig. 36 and Fig. 37.
The humidistat is normally used in applications where a tem-
perature control is already provided (units with SystemVu™
control).
Fig. 36 — Accessory Field-Installed Humidistat
Fig. 37 — Edge Pro Thermidistat
20
% RELATIVE HUMIDITY
®