4.6 ELECTRICAL SUPPLY

WARNING! THIS APPLIANCE MUST BE EARTHED IN ACCORDANCE WITH IEE REGULATIONS

Boiler electrical supplies must not be switched by a time clock.

Boilers are suitable for 230Volt, 50Hz supply.

External fuses should be rated for 10 amps

Wiring must be completed in heat resistant cable size 1.0mm² csa.

Each module should have individual means of isolation.

Electrical isolators must facilitate complete electrical isolation.

Electrical isolators must have contact separation of minimum 3mm in all poles.

Electrical isolators must be installed in readily accessible locations.

Electrical supplies to boiler modules should only serve the boiler.

Where volt free contacts are used, these too must be individually isolatable.

Time clock control should be via the boiler modules Remote On/Off circuit (5V DC).
Any circuit connected to the Remote On/Off MUST be volt free and compatible.
ADDITIONAL INFORMATION REGARDING ELECTRICAL SUPPLIES IS GIVEN IN BS
EN60335, Part 1.
NOTE: The appliance MUST be isolated from the electrical supply if electric arc welding
is carried out on connecting pipework.
FOR DETAILED WIRING INSTRUCTIONS SEE SECTIONS 5.3, 9.0 & APPENDIX B