Protective Features

Overcurrent
Excessive Temperature
Over Voltage
Drive Rated Input = 200-240V AC
Drive Rated Input = 380-460V AC
Under Voltage
Drive Rated Input = 200-240V AC
Drive Rated Input = 380-460V AC
Control Ride Through
Ground Fault
Faultless Ride Through
Output Short Circuit

Programming

Programmer / Display Type
Local Controls
200% hardware limit (16 amps), 300% instantaneous fault (24 amps)
Embedded temperature sensor trips if heatsink temperature exceeds 95 degrees C
(203 degrees F)
DC Bus voltage is monitored for safe operation
Overvoltage trip occurs at 400V DC bus voltage (equivalent to 290V AC incoming line voltage).
Overvoltage trip occurs at 800V DC bus voltage (equivalent to 575V AC incoming line voltage).
DC Bus voltage is monitored for safe operation
Undervoltage trip occurs at 210V DC bus voltage (equivalent to 150V AC incoming line voltage).
Undervoltage trip occurs at 390V DC bus voltage (equivalent to 275V AC incoming line voltage).
Minimum ride through is 0.5 seconds - typical value 2 seconds
Protection in both Start and Run Mode
100 milliseconds
Any output phase to phase short
Program Keypad Module - 6 character LED display
Remote Keypad Module - 4 character LED display
CopyCat Keypad Module - 2 line, 16 character LCD display
SPEED, RUN, STOP, and DIRECTION controls