Installation; Uncrating; Location - BeaconMedaes Lifeline Camel Installation, Operation And Maintenance Manual

Lpv liquid ring medical vacuum system
Table of Contents

Advertisement

"Camel" Liquid Ring Medical Vacuum
Medical Systems

1. Installation

1.1 Uncrating

Upon delivery, the condition of the LifeLine "Camel" Medical Vacuum System should be carefully inspected. Any
indication of damage by the carrier should be noted on the delivery receipt, especially if the system will not be
immediately uncrated and installed. BeaconMedæs ships all systems F.O.B. factory; therefore, damage is the
responsibility of the carrier, and all claims must be made with them. LifeLine systems may remain in their shipping
containers until ready to be installed. If the unit is to be stored prior to installation, it must be protected from the
elements to prevent rust and deterioration. Rotate the vacuum pump motor shafts every two weeks. This can be
accomplished by removing the motor fan guard and rotating the motor fan. Although the vacuum pumps are
flushed with a water-soluble preservative prior to shipment, refer to your BeaconMedæs representative for storage
instructions.
Accessories are shipped in a separate container that is attached to the system shipping crate. TO AVOID LOSS OR
DAMAGE, MAKE CERTAIN THAT ACCESSORIES ARE IDENTIFIED AND KEPT IN A SAFE PLACE
UNTIL THEY ARE INSTALLED ON THE SYSTEM.
DO NOT REMOVE the protective covers from the inlet and discharge connection ports of the modules until they
are ready for connection to the hospital's pipeline distribution system.

1.2 Location

The LifeLine "Camel" Medical Vacuum System should be installed indoors in a clean, well-ventilated environment.
This location should be protected against flooding, freezing, excessive moisture and overhead dripping. Areas of
excessive dust, dirt, or other air-borne particulate should be avoided.
Certain considerations should be given to the placement of the system. The package may be installed in any location
that is flat, level and will support its weight. When selecting the location for the system, provisions should be made
to permit proper piping arrangement and dismantling. Allow space for service, such as cleaning, changing filters,
and component replacement. Clearance between the unit and adjacent walls should be no less than 24" to ensure
sufficient airflow for cooling. There should be a minimum of three feet of clearance in front of the control panel for
safe operation and maintenance. A vertical distance of 24" is required above the unit for ventilation and
maintenance. Refer to the general assembly drawings in Appendix C.1 for actual dimensions.
No special foundation is required. However, all units must be securely bolted using all mounting holes provided.
If a raised concrete pad is used, it must form a rigid support for the system. Pour a 4" to 6" concrete "housekeeping"
pad large enough for the system plus approximately 6" per side. The unit's base must not overhang the concrete
base. A method to drain away moisture is also necessary.
Adequate ventilation is required. The pumps are air-cooled. Therefore, it is very important that the ambient
temperature should be between 40˚F and 105˚F (If the maximum ambient exceeds 105˚F, contact factory for special
instructions). The system should be located as close as possible to the point of usage to prevent excessive loss of
operating vacuum due to pressure drop.
1-1

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for BeaconMedaes Lifeline Camel

Table of Contents