CHAPTER 3 - INSTALLATION GUIDE

R
efer to the appropriate wiring diagram during installation of
the 815UHP system. The wiring diagrams are in chapter 4.
Follow these instructions for a tractor trailer installation:
1. Pick a spot for the 815UHP to be mounted. It can be inside
or outside of the cab, but it should be mounted on the truck,
rather than the trailer. Do not mount the controller where it
can be kicked and it should be easy to see and out of direct
road spray. It is recommended that the controller be mounted
close to the PTO control.
2. Mount the display enclosure using the mounting flange holes,
being certain to shim the enclosure away from the mounting
surface with the spacers provided to allow water drainage.
Broken display enclosures caused by water freezing
behind the enclosure are NOT covered by warranty.
IMPORTANT:
should be soldered.
3. Mount a standard 7 pin socket to the front of the trailer and a
7 pin plug and cable from the tractor.
4. A single wire needs to be connected between the green wire
of the 808P2, the grey wire of the 810PS2 and the yellow wire
of the 815UHP through the 7 pin socket. From inside the
displays, seal the wire entry into the S
RTV silicon rubber. Make sure that the RTV fully surrounds the
wire where it goes though the fitting.
5. Connect the 808P2 or 810PS2 and the 815UHP to the same
chassis ground using each displays black wires. Verify the truck
and trailer are grounded together through the 7 pin plug.
6. Connect the orange controller wire to the truck's electrical horn
switch (or button). Make sure that grounding this connection
will cause the horn to sound. This connection is normally to
the horn relay coil, not to the horn itself. Complete the wiring
in accordance with the applicable wiring diagram supplied by
Garnet.
7. Program the alarm points in the gauge. Program alarm #1
as SHUT DOWN at the point beyond which loading is not
permitted. Program alarm #2 as SHUT DOWN at the point
where the horn alarm should activate. Program alarm #3 as
SHUT DOWN at the point where the tank is considered empty,
normally a few inches off the bottom. Do not program the