Toshiba RAV-SM307MUT-E Service Manual page 51

Split type compact 4-way cassette type
Hide thumbs Also See for RAV-SM307MUT-E:
Table of Contents

Advertisement

[L20 trouble]
Are wiring connections
to communication lines
U3 and U4 normal?
YES
Is not the multiple same central
control system addresses connected?
NO
Check central controller
(including network adapter) and
indoor P.C. board (MCC-1643).
Defect → Replace
[L30 trouble]
Do outside devices normally work?
(Outside devices connected with Application
control kit input terminal TB2 : IN1)
YES
Check cause of operation.
[P30 trouble] (Central controller)
Is group operation carried out?
YES
Is there check code
on follower unit in main
and sub remote controllers?
YES
Check corresponding
indoor unit/outdoor unit.
NO
YES
NO
NO
NO
– 51 –
Correct wiring connection.
Correct central control system address.
Check outside devices.
Defect → Replace
Check indoor P.C. board (MCC-1643).
Defect → Replace