No.
Item
12
Louver control
(Continued)
Outline of specifications
<<Selection of Swing mode>>
• For the Swing mode, the following three types of modes
are selectable and settable by keeping Swing/Direction
SWING/FIX
button pushed for 4 seconds or more on the remote
controller.
1) Standard (4 pieces: same phase) swing
→ Data: [0001 (At shipment)]
When Swing operation is selected, four louvers align at
the horizontal discharge position and then start the
Swing operation at the same time.
2) Dual swing → Data: [0002]
When operation is selected, the louvers of louver No.
[01] and [03] move to the horizontal discharge position,
the louvers of louver No. [02] and [04] move to the
downward discharge position and then start the Swing
operation at the same time.
3) Cycle swing → Data: [0003]
When operation is selected, the louver No. [01] moves to
the horizontal discharge position, [03] to the downward
discharge position, [02] and [04] to the middle position
and then start the Swing operation at the same time.
• Three types of the swing modes can be also selected
and set by the setup data of Item code (DN) [F0].
• In case of selecting the Swing mode, "Dual swing" or
"Cycle swing", the following numerals is displayed at
the center of the remote controller screen for approx.
SWING/FIX
3 seconds when
[SWING]. (No display for the standard swing)
Alternate lighting
(0.5 sec.)
Dual swing
<<Louver lock (Louver fix)>>
• For the air direction setup for each discharge port, the louver
position can be locked during the normal operation.
• An arbitrary air direction of an arbitrary louver can be
registered and set by keeping
4 seconds or more on the remote controller.
• The louver lock can be set by registering the setup data to
Item code (DN) [F1] to [F4] according to the following table.
Item code
Objective louver No.
F1
01
F2
02
F3
03
F4
04
button was pushed to select
Alternate lighting
(0.5 sec.)
Cycle swing
UNIT
LOUVER
button pushed for
Setup data
0000: Release (At shipment)
0001: Horizontal discharge position
~
0005: Downward discharge position
– 32 –
Remarks
Carry out setting operation
during stop of the unit;
otherwise the unit stops
operation.
Carry out setting operation
during stop of the unit;
otherwise the unit stops
operation.