Toshiba RAV-SM307MUT-E Service Manual page 48

Split type compact 4-way cassette type
Hide thumbs Also See for RAV-SM307MUT-E:
Table of Contents

Advertisement

[E04 trouble]
Does outdoor operate?
YES
Check indoor P.C. board.
Defect → Replace
NO
Is group address setup of
remote controller correct?
Are wiring in indoor unit and
1, 2, 3 inter-unit cables correct?
Are wirings of terminal blocks
(1, 2, 3) wired to CN67 normal?
Does the voltage between 2 and 3
of terminal blocks (1, 2, 3) vary?
Check outdoor P.C. board.
Defect → Replace
NO
YES
NO
YES
NO
YES
NO
YES
As shown in the following figure,
carry out measurement within 20 seconds
after the power was turned on.
Black
White
Terminal block
– 48 –
Check CODE No. [14].
Correct wiring and
inter-unit cables.
Correct wiring of connector
and terminal blocks.
Check indoor P.C. board.
(MCC-1643)
Defect → Replace
S5277G
3
2
1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents