Siemens SED2 Operating Instructions Manual page 17

Advanced operator panel (aop)
Hide thumbs Also See for SED2:
Table of Contents

Advertisement

Use
and
to scroll through the parameters and to highlight Command Source P0700.
4.
Press
to confirm the selection and the cursor advances to the parameter index.
Use
and
to scroll through the indexes for P0700 and to highlight P0700[1] (index 1).
Press
to confirm the selection and the cursor advances to the parameter value.
Use
and
to set P0700[1]=4 (USS on BOP/AOP local link).
Press
to confirm the setting and the cursor returns to the parameter.
Use
and
to scroll through the parameters and to highlight Selection of Frequency
5.
Setpoint P1000. Press
index.
Use
and
to scroll through the indexes for P1000 and to highlight P1000[1] (index 1).
Press
to confirm the selection and the cursor advances to the parameter value.
Use
and
to set P1000[1]=1 (motor potentiometer [MOP] setpoint).
Press
to confirm the setting and the cursor returns to the parameter.
Use
and
to scroll through the parameters and to highlight Commissioning parameter
6.
P0010. Press
to confirm the selection and the cursor advances to the parameter value.
Use
and
to set P0010[0]=0 (Ready) to exit the quick commissioning mode. Press
to confirm the setting and the cursor returns to the parameter.
Use
and
to scroll through the parameters and to highlight USS Telegram Off Time
7.
P2014. Press
to confirm the selection and the cursor advances to the parameter index.
Use
and
to scroll through the indexes for P2014 and to highlight P2014[1] (index 1,
Serial Interface BOP Link). Press
parameter value.
Use
and
to set P2014[1]=5000 (USS on BOP/AOP local link) to prevent unexpected
drive operation. In this mode, removal of the AOP from the SED2 VFD causes a timeout to
occur in 5 seconds. Press
Press
to return to r0000. Press
8.
Press
to switch the SED2 to hand mode.
9.
Press
to start the SED2.
10.
Use
to increase the output; Use
11.
Siemens Building Technologies, Inc.
to confirm the selection and the cursor advances to the parameter
to confirm the selection and the cursor advances to the
to confirm the setting and the cursor returns to the parameter.
to display the standard (operate) screen.
to decrease the output.
AOP Start-Up & Initialization
9