Ab Parts - Allen-Bradley GuardPLC 1753 Safety Reference Manual

Controller systems
Hide thumbs Also See for GuardPLC 1753:
Table of Contents

Advertisement

Figure 3.2 Emergency Off Switches
DO
1
Emergency
OFF 1
DI
1
The digital outputs DO1 and DO2 are pulsed (T1 and T2 below). As a
result, the connections to the digital inputs are monitored.
Figure 3.3 Digital Input Monitoring
T1
configurable 5 to 2000 µs
T2
configurable 5 to 2000 µs
The FAULT LED on the front plate of the controller/module flashes,
the inputs are set to 0 and an error code is generated when the
following faults occur:
• short-circuit between two parallel connections
• reversal of two connections
• ground fault on one of the lines
• line break (or opening of the contacts when one of the
Emergency OFF switches is pressed)

AB Parts

2
2
DI
3
Publication 1755-RM001B-EN-P - March 2004
Input Channels
3-5
Emergency
OFF 2
4
t