Creating An Emergency Repair Disk - Allen-Bradley ProcessLogix R500.1 Installation Instructions Manual

Table of Contents

Advertisement

8
ProcessLogix R500.1 Server Installation Instructions
Setting the Date and Time
To correctly set the date and time:
1. Click Start
2. Double-click the Date/Time icon.
3. In the Date and Time Properties window:
a. If necessary, adjust the Date and Time settings.
b. Set the appropriate Time Zone for your location.
c. Uncheck the Automatically adjust clock for daylight saving changes option.
d. Click OK.
ATTENTION
!

Creating an Emergency Repair Disk

1. Insert a blank diskette into the PC's floppy drive.
2. Click Start
3. Click Emergency Repair Disk.
4. An Emergency Repair Diskette window will appear.
5. Check the Also back up the registry to the repair directory checkbox and click OK.
6. When finished, click OK
Publication 1757-IN950A-EN-P - September 2002
Settings
Control Panel.
Failure to uncheck the Automatic adjustment for Daylight Savings
Time will cause Redundant Systems to loose "Sync" when the time
is automatically adjusted. Choosing not to automatically adjust the
time allows you to decide when to make the adjustment (at a time
that is not critical to your process).
Programs
Accessories
.
System Tools
Backup.