Allen-Bradley 1784-KTX Reference Manual page 78

Table of Contents

Advertisement

Appendix A
Dual port Layout
Address
Mnemonic
:00E
host_dead_counter
:00F
reserved2
:012
alive_flag
:013
duplicate_node
:014
off_ktx
:015
stopped_flag
:016
module_state
:017
cos_link_address
:01B
unused
:07C
num_adapter_addresses
:07D
num_faulted_adapters
:07E
operating_status
A-2
Size
Host
KTx
1
3
1
1
R
W
1
1
1
R
W
1
R/W
R/W
65H
1
R
R/W
1
R
R/W
2
R
R/W
Description
If zero, the host dead counter is disabled. A non-zero
value defines the timeout period:
20ms * value
The host must set the alive_flag = 0 before the timeout
expires or the scanner will declare the host dead.
See host_dead_counter.
Set to 1 if a duplicate scanner is detected.
If there is a runtime error (CRC or RAM test), the error
code will be written here.
If the host enables CHANGE OF STATE detection, the link
address of the adapter that had a change of state will be
written here by the scanner. The host must clear this by
writing an 0FFh.
Number of adapters on link
Number of adapters on link that are currently faulted
This byte is used by the KTx to indicate to the host the
state of the module by setting/clearing the bits. The bits
(when set) are defined as:
Bit 0:
Program mode
Bit 1:
Test mode
Bit 2:
Run mode
Bit 3:
Debug mode
Bit 4:
Unsolicited BT received on link
Bit 5:
BT pending
Bit 6:
Fault exists
Bit 7:
Fault changed
Bit 8:
Unsolicited BT read reply
Bit 9:
Unsolicited BT write reply
Bit 10:
Confirmation queue is full
Bit 11:
Unknown host interrupt type
Bit 12:
Scanner declared host dead
Bit 13:
Input Image Table changed state
Bits 14-15:
unused