Electrical Wiring Connection - Daikin FWG05AATNMV1 Installation Manual

Ceiling cassette chilled water fan coil unit
Hide thumbs Also See for FWG05AATNMV1:
Table of Contents

Advertisement

Available languages

Available languages

IMPORTANT: * These values are for information only. They should be checked and selected to comply with local and/or
national codes and regulations. They are also subject to the type of installation and size of conductors.
** The appropriate voltage range should be checked with label data on the unit.
There must be an all pole disconnection in the supply mains with a contact separation of at least 3mm.
Model: FWG05/08/11AAT
FCU 1
CVLV
N1
L
3WV
X1
CHILLER
Model: FWG05/08/11AAF
FCU 1
HVLV
N1
CVLV
N2
L
3WV
3WV
X1
CHILLER
Model
Voltage Range**
Recommended time delay fuse*
Power Supply Cable*
Interconnection cable size*
Number of conductors

ELECTRICAL WIRING CONNECTION

FCU 2
N
CVLV
N1
3WV
L
N
There must be an all pole
disconnection in the supply
mains with a contact separation
of at least 3mm.
All power line must be from the
same phase.
FCU 2
N
HVLV
N1
CVLV
N2
3WV
3WV
L
N
There must be an all pole
disconnection in the supply
mains with a contact separation
of at least 3mm.
All power line must be from the
same phase.
FWG05AAT(F)
(A)
(mm
2
)
(mm
2
)
L
N
CVLV
N1
3WV
L
N
X2
L
N
HVLV
N1
3WV
L
N
X2
FWG08AAT(F)
220V-240V/~/50Hz +
2
2
1.5
1.5
3
3
1-9
FCU 3
L
N
L
N
X3
3WV
3 Way Valve
X1, X2,X3
Relay
Field Supply Wire
FCU 3
CVLV
N2
L
N
3WV
L
N
X3
3WV
3 Way Valve
X1, X2,X3
Relay
Field Supply Wire
FWG11AAT(F)
2
1.5
3