Siemens ZIC-8B Installation Instructions Manual page 9

Zone indicating card
Table of Contents

Advertisement

CONFIGURATIONS
NOTES
1. All wiring must be in accordance with
Article 760 of NEC or local building
codes. Wiring for each zone must be
Class B.
2. All output circuits are power limited
to NFPA 70 per NEC 760.
3. Electrical Ratings:
Special Application 24VDC
Output Zone Supervisory:
8mA max @ 24VDC
Output Zone Alarm:
2A max @ 24VDC
4. EOL resistor , 24k ohms,
1W, 5%, P/N 140-033771.
5. Polarity shown in active state.
6. Maximum line resistance is
dependent upon the maximum
current draw of connected notifica-
tion appliances when activated. The
field wiring resistance cannot exceed
the maximum line resistance
specified for any given NAC current
draw. (See Table )
7 . For a list of Compatible Notification
Appliances, refer to P/N 315-096363.
8. Refer to CAB1/CAB1R (P/N 315-
0330007) and CAB2-BB/CAB3-BB
(P/N 315-033009) Installation
Instructions for details on the
separation of power limited and non-
power limited wiring.
9. Positive and negative ground fault
detected at <40K for terminals 1 - 16.
10. A maximum of 23 strobes can be
connected to a single circuit.
ZONE 5
24K,
1W
5%
ZONE 6
24K,
1W
5%
Figure 5
ZIC-8B Supervised Notification Appliance Wiring
Siemens Industry, Inc.
Building Technologies Division
The ZIC-8B zones can be configured for Notification Applicance (NFPA 72) as shown
below.
ZONE 1
ZONE 2
24K,
1W
5%
1
2
3
9
10
17
18
ZONE 1&2
INPUT
STYLE Y
CLASS B
ZONE 3
ZONE 4
24K,
24K,
24K,
1W
1W
1W
5%
5%
5%
4
5
6
7
8
11
12
13
14
15
16
ONE SLOT OF CC-5
19
20
21
22
23
24
ZONE 3&4
ZONE 5&6
ZONE 7&8
INPUT
INPUT
INPUT
9
Current
Max Line
Draw
Resistance
2.0A
1.50 ohms
1.5A
2.10 ohms
1.0A
3.30 ohms
0.5A
6.90 ohms
ZONE 8
24K,
1W
5%
ZONE 7
24K,
1W
5%
P/N 315-048670-11