NOTES
1. All wiring must be in
accordance with Article 760
of NEC or local building
codes. Wiring for each zone
must be Class B.
2. All output circuits are power
limited to NFPA 70 per NEC
760.
3. Electrical Ratings:
Output Zone Supervisory:
8mA max @ 24VDC
Output Zone Active:
25V — 25 watts max / zone
70V — 30 watts max / zone
4. EOL resistor, 24k ohms,
1 watt , 5%, P/N 140-033771.
5. Polarity shown in active
state.
6. For a list of Compatible
Notification Appliances, refer
to P/N 315-096363.
7 . Refer to CAB1/CAB1R (P/N
315-0330007) and CAB2-BB/
CAB3-BB (P/N 315-033009)
Installation Instructions for
details on the separation of
power limited and non-
power limited wiring.
8. Positive and negative ground
fault detected at <40K for
terminals 1 - 16.
STYLE Y
(CLASS B)
ZONE 5
24K,
1W
5%
STYLE Y
(CLASS B)
ZONE 6
24K,
1W
5%
TO NEXT ZIC-8B
Figure 6
ZIC-8B Single-Channel Audio Wiring
Siemens Industry, Inc.
Building Technologies Division
ZONE 1
ZONE 2
ZONE 3
STYLE Y
STYLE Y
STYLE Y
CLASS B
CLASS B
CLASS B
24K,
24K,
24K,
1W
1W
1W
5%
5%
5%
1
2
3
4
5
6
9
10
11
12
13
ONE SLOT OF CC-5
17
18
19
20
21
10
ZONE 4
STYLE Y
CLASS B
24K,
1W
5%
7
8
14
15
16
22
23
24
AUDIO FROM PREVIOUS
ZIC-8B OR ZIC-4A OR FROM
ZAC-40/
1A AND 1B OR 2A AND 2B
STYLE Y
ZONE 8
(CLASS B)
24K,
1W
5%
STYLE Y
ZONE 7
(CLASS B)
24K,
1W
5%
ZAM-180 TERMINALS