All screenshots in this documentation are application examples. Depending on the firmware version of the device and software version of the installed engineering tools, the screenshots in this documentation may differ from the screen representation. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
TD11 First edition Tip! Current documentation and software updates with regard to Lenze products can be found in the download area at: www.lenze.com Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Optically highlighted reference to another page. It is activated with a mouse-click in this online documentation. Step-by-step instructions Step-by-step instructions are indicated by a pictograph. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
EtherCAT® is a registered trademark and patented technology, licenced by Beckhoff Automation GmbH, Germany. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 13
PROFINET® (Process Field Network) is a real-time capable fieldbus system based on Ethernet. PROFINET® is a registered trademark and patented technology licensed by the PROFIBUS & PROFINET International user organisation (PI). Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Pictograph Signal word Meaning Note! Important note to ensure trouble-free operation Tip! Useful tip for easy handling Reference to another document Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
• Electrical wiring diagrams are directly printed on the module • Electrical isolation to the fieldbus and the process level • Creation of electrical isolations by power supply modules Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Supply voltage DC 24 V for the electronics • Side-by-side mounting of the module feet of the I/O compound modules provides for the electrical connection to the bus coupler module. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
(reading, setting, comparing) 10 bytes, writing EPM-S601 Counter 2, DC 24V 2 counters 32 bits, 24 V DC 12 bytes, reading (reading, setting) 12 bytes, writing Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 19
For using the modules EPM-S640 and EPM-S650, the L_COM_EPMS640 function library is available. Bus coupler module EPM-S130 (EtherCAT) Only I/O compound modules EPM-Sxxx from hardware version 1B are supported. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
0x09 30140 0x0A 37330 0x0B 40000 The values of the table result in the following time diagram: [2-1] Time diagram: Example time stamp function Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 21
0x00 0b00000000 0x00 The diagram indicates the status of the outputs at the "t" time. [2-2] Time diagram:Write time stamp entries 1 ... 5 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 22
The diagram indicates the status of the outputs at the "t" time. [2-4] Time diagram: Execute the time stamp function for the entries 2 ... 4 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 23
0b00000000 0x00 The diagram indicates the status of the outputs at the "t" time. [2-5] Time diagram: Write time stamp entries 6 ... 10 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 24
0x00 0b00000000 0x00 The diagram indicates the status of the outputs at the "t" time. [2-7] Time diagram: Write the last time stamp entry Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 25
The diagram indicates the status of the outputs at the "t" time. [2-8] Time diagram: Execute the time stamp function for the last entries Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
The correspondent channel of channel 1 is channel 3 and the one of channel 2 is channel 4. Unused • Deactivate unused channels by parameterisation. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Status set in the case of a zero crossing STS_LTCH Status of the latch input Reserved * The bits are set until reset with RES_SET (bit 6 control word) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Status set in the case of a zero crossing Reserved Reserved * The bits are set until reset with RES_SET (bit 6 control word) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Status set in the case of a zero crossing Reserved Reserved * The bits are set until reset with RES_SET (bit 6 control word) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Status set in the case of a zero crossing Reserved Reserved * The bits are set until reset with RES_SET (bit 6 control word) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
LPT-Port (EMF2173IB) or to a free USB port (EMF2177IB) via the PC system bus adapter. • The I/O system 1000 is supplied with DC 24 V for the control electronics. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Start Search button has been pressed in order to be able to read out data from the connected devices. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 35
• You can always change the properties subsequently. • Later you will find the name as project name in the Project view. 5. Click the Next button. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 36
Browse... button. 8. Click the Complete button. Step 4 - Reading online data 9. Select the "CAN" entry from the Bus connection list field. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 37
Stop! If you change parameters in the »Engineer« while the controller is connected online, the changes will be directly accepted by the controller! Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Step 1 - What would you like to do? 2. Select the Select component from catalogue option. 3. Click the Next button. Step 2 - Properties Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 39
• If you select the Always save projects here option, the indicated directory will be the standard memory location for new projects. 8. Click the Complete button. • The Insert a component dialog box appears. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 40
10. Select the "S110: CAN Bus coupler" module from the Search results list field. • More details and technical data of the selected module are displays on the right side. 11. Click the Next button. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 42
• Then, go online to transmit the parameter settings made in the »Engineer« to the I/O system 1000. Setting the communication path and going online ( 43) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
How to configure an online connection via system bus (CANopen): 1. Go to the Project view and select the I/O system 1000 to be connected online: 2. Select the menu command OnlineSet communication path and go online. If the changes you have made on the project have not been accepted yet, first a query on whether an update is to be carried out is effected.
Page 44
(e.g. "can:/dev1/"). 7. In the Communication path dialog box, click the Connect button to establish an online connection to the I/O system. In the Project view, a yellow icon indicates the online connection to the I/O system 1000: Stop! If you change parameters in the »Engineer«...
Detailed information on the function of the single I/O modules can be found in the system manual for the I/O system 1000. If you select the I/O system 1000 in the project view of the »Engineer«, the Workspace displays the settings and features of the I/O system.
The Lenze setting is accepted by switching the supply voltage on and off. All settings that have been saved before are deleted from the EEPROM of the CAN bus coupler. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
This chapter describes how to set up communication with the »PLC Designer« between the Engineering PC and the I/O system 1000. If the I/O system 1000 is used in line with the Lenze "Controller-based Automation" system, only the EtherCAT communication (...
Ethernet interface "LAN 1b" EtherCAT interface Slot for optional communication card (MC-Card) Contacts for backplane bus [4-1] Example: Interfaces on the Controller 3231 C Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 49
For all other fieldbus systems, optional communication cards are available for the Controllers. The interfaces of the communication card have to be connected to a corresponding bus coupler module. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
• The currently active channel is shown in the device view in bold and is marked with the "(active)" addition: • A channel represented in italics is set as active path but has not been found during the last network scan. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
• Enter a name for the »PLC Designer« in the Name input field. • Select the desired memory location under Location. 3. Confirm the entries by clicking OK. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 52
Configuring the I/O modules at the backplane bus of the Lenze Controller Configuring I/O modules on the EtherCAT bus coupler module Configuring I/O modules on the CANopen bus coupler module Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
The Lenze Controller consists of the following components: • I/O bus coupler module: controller with a PLC control in the form of a soft PLC. • I/O compound modules: Up to 64 modules which are connected to the controller via the Lenze backplane bus.
Page 54
"EPM-S200" has been selected): 3. Click Add device to add the selected device to the "I_O_Modul_Koppler". • The Add Device dialog box remains open. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 55
• In the event of an error, i.e. if the configuration deviates from the physical arrangement, the modules are marked with the symbol. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Start Search command in the context menu of the EtherCAT master after adding the EtherCAT master (step 3). Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 57
Device dialog box. 6. Click the Add Device button to add the selected device to the EtherCAT master. • The Add Device dialog box remains open. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 58
• In the event of an error, i.e. if the configuration deviates from the physical arrangement, the modules are marked with the symbol. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
2. Select the "CANbus" device in the Add Device dialog box: 3. Click Add Device to add the selected device to the Controller. • The Add Device dialog box remains open. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 60
Device dialog box. 9. Click Add Device to add the selected device to the CANopen Manager. • The Add Device dialog box remains open. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 61
12. Proceed as described before to add all other available I/O compound modules of the Device view. • Sample representation: 13. Click the Close button to close the Add Device dialog box again. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 62
17. Go to the CANopen_Manager tab: • Activate the Sync generation option. • Set the sync cycle time in the Cycle Period entry field. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 63
• In the event of an error, i.e. if the configuration deviates from the physical arrangement, the modules are marked with the symbol. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
4. Go to the CANopen Remote Device tab: • Activate the Expert Settings option. • Deactivate the Autokonfig. PDO Mapping option. 5. Execute the menu command WindowClose All Editors. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 65
If Autoconfig. PDO Mapping (see step 3) is reactivated after adding the manual configuration, the entire configuration that has been added manually will be deleted. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
• After the I/O system has been changed: Set the node address and the baud rate at the coding switch and then start the control. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
3. Tick the following on the PLC settings tab: 4. Add the matching gateway on the Communication settings tab. • Either via double-click or Add gateway... button Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 68
8. Go to the CANopen Remote Device tab: • Set node ID "2". • Activate the Expert Settings option. • Deactivate the Autoconfig. PDO Mapping option (untick). Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 69
12. Click on the OK button to accept the entries and close the dialog box again 13. Select the added PDO and click the Add Mapping... button: Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 70
• Select "cyclic – synchronous (type 1-240)" as transmission type. • Go to the Select element from the object directory dialog box and select the "Counter Value" with the subindex 1 (":16#01"): Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 71
• As soon as the value has been transmitted and a countable signal is applied at the corresponding input, the counter starts to count upwards. • The value is transmitted cyclically via the CAN bus to the control. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Setting the cycle time for access to the I/O modules In the Lenze Controller a central bus cycle task is selected, which is valid for the processing of all fieldbuses and for the I/O modules connected via the backplane bus.
• Use the Parameter tab to set the parameters required for the selected I/O compound module (for this example, an "EPM-S400" has been selected): Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
• Use the Modules tab to set the parameters required for the selected I/O compound module (for this example, an "EPM-S400" has been selected): Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Go to the parameter list of the bus coupler module in the All objects category and set the ’0x31FF’ index to the "Accept module parameters" selection. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Write semaphore timeout for group 3 Configuration error in the topology of the I/O modules Check sequence of the I/O modules in the device view. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 77
SDO communication error Contact Lenze Physical I/O module topology could not be read. Contact Lenze I/O system driver could not be opened. Contact Lenze Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Tip! Please visit the homepage of the CAN user organisation CiA (CAN in automation) for further information: http://www.can-cia.org Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
• The identifiers can also be set individually Assigning individual identifiers ( 85) 5.1.3 Saving settings The settings are permanently stored via I-1010 (communication protocol DS301/DS401). Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Only network management telegrams can be received. Parameter data and process data are not received. (stopped) The module outputs switch to the configured status (see chapter "Monitoring"). Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 81
• Identifier: 0x00 (broadcast telegram) • User data: 0x0100 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 82
= node ID: If a node address is given, only the state of the device with the corresponding address will be changed. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Note! Lenze inverters expect a PDO length of eight bytes even though not all of them may have assigned I/O values. The PDO length can be set via I-2100: • 0: PDO length of eight bytes (Lenze setting) •...
• First, a certain number (n) of sync telegrams must be transmitted (I-140x, subindex 2 = 1 ... 240). Then the PDO telegram must be received from the master. Finally, the process input data are accepted. • Event-controlled reception (Lenze setting) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 86
3. The data is accepted by the I/O system with the next sync telegram if "sync-controlled reception" is active. 4. All other telegrams (e.g. for parameter or event-controlled process data) are accepted asynchronously by the I/O system after transmission. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
• n x DO: I/O compound module with n digital outputs • n x AI: I/O compound module with n analog inputs • n x AO: I/O compound module with n analog outputs Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 88
With analog values the data lengths of which exceed on byte, the data consistency is extended. Since one channel assigns two bytes, each channel of an I/O compound module is mapped in two successive PDOs. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 92
OR-ed manner. 24 ... 31 – Current number of time stamp entries in FIFO memory. Digital-I/O EPM-S207, EPM-S310 – time stamp function (example) ( 20) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
– – Status word DO1 Status word DO2 11 ... – [5-7] Mapping contents PWM module EPM-S620 – control and status word ( 32) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
EPM-S600/-S602: Subindex is increased by 1 for each counter 2 DWord 2 EPM-S601/-S603: Subindex is ..increased by 2 for each counter 64 DWord 64 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 95
With every change of the count value, the time value of the timer is stored as 16-bit-s value together with the count value in the input area. Counter modules EPM-S600 ... EPM-S603 – control and status words ( 27) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
5.3.10 Data transfer between I/O system and inverter In the Lenze setting of the I/O system 1000, the basic identifiers of the PDOs are set according to CANopen. For communicating with Lenze inverters, the basic identifiers for the process data object 1 must be adapted.
The input data are accepted on sync telegram sync telegram transmission transmission. 241 ... 254 Reserved 255 Process data update on every Every received value is accepted. occurrence of an event Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 98
I-1809/1 2047 COB-ID used by TxPDO 10 • Defining the individual identifiers for process data object 1 • Lenze setting: 1728 + node ID Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 99
I-1809/3 65535 Inhibit time • Lenze setting: 0 ms I-1809/5 65535 Event time (cycle time) • Lenze setting: 100 ms Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
In data 4, this telegram always contains the value "6", in data 3 it contains an error code: Command code Error Response Data 3 Data 4 Error message 0x80 Access denied Wrong subindex Wrong index Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
8 bytes of user data Identifier Command Index Subindex Data 1 Data 2 Data 3 Data 4 code Low byte High byte 0xE8 0x03 0x00 0x00 (LSB) (MSB) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Writing a parameter (example) Task The I/O system 1000 has been assigned node address 2. The function of the first channel (voltage signal 0 ... +10 V, 0 ... 27648) is to be output at the first analog I/O compound module (EPM-S500, 2 analog outputs 0 ...
Page 104
8 bytes of user data Identifier Comman Index Subindex Data 1 Data 2 Data 3 Data 4 d code LOW byte HIGH byte 1410 0x60 0x01 0x30 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Reading a parameter (example) Task An I/O system 1000 has been assigned node address 21. The function of the first channel is to be read at the first analog I/O compound module (EPM-S500, 2 analog outputs 0 ... 10 V).
Page 106
Index Subindex Data 1 Data 2 Data 3 Data 4 d code LOW byte HIGH byte 1410 0x43 0x00 0x31 0x00 0x00 0x05 0x3B Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Memorising station structure Is the saved station structure available? Are the memorised and saved station structures identical? Operational Operational Error state Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
• Use the coding switch to set the node address of the I/O system at the CANopen bus coupler module. • The set node address can be read via the index I-100B. Index table ( 193) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Reserve Tip! • Store changed parameters in the EEPROM via index I-1010. The settings are maintained after the supply voltage is switched off. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
U = D * 10 / 16384 (0x20) D = 16384 * U / 10 16384 4000 Nominal range 8192 2000 0000 Not possible, is limited to 0 V Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
U = D * 10 / 16384 (0x20) D = 16384 * U / 10 16384 4000 Nominal range 8192 2000 0000 Not possible, is limited to 0 V Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
0x8000 channel 2 this value and the limit value monitoring function is enabled, I-310F/x a process alarm is triggered. 0x8000: Limit value alarm deactivated Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 116
U = D * 10 / 16384 (0x20) D = 16384 * U / 10 16384 4000 Nominal range 8192 2000 0000 -3277 F333 Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
0x8000 channel 2 this value and the limit value monitoring function is active, a I-310F/x process alarm is triggered. 0x8000: Limit value alarm deactivated Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 118
I = D * 16 / 16384 + 4 (0x40) D = 16384 * (I-4) / 16 16384 4000 Nominal range 8192 2000 0000 -3277 F333 Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
U = D * 10 / 16384 (0x20) D = 16384 * U / 10 16384 4000 Nominal range 8192 2000 0000 Not possible, is limited to 0 V Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
U = D * 10 / 16384 (0x20) D = 16384 * U / 10 16384 4000 Nominal range 8192 2000 0000 Not possible, is limited to 0 V Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
32767 Configures the individual analog output output responses The analog outputs provide the set 1 Channel 1 value 2 Channel 2 ..36 Channel 36 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
32767 Configures the individual analog output output responses The analog outputs provide the set 1 Channel 1 value 2 Channel 2 ..36 Channel 36 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
255 T x-PDO= FF|00|00|00|00 Enable digital output via control Transfer control word to the counter via PDO. word : Bit 1 (CTRL_DO_SET) = HIGH Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Four-fold evaluation The rising and falling edges of the channels A and B are evaluated. The number of pulses has quadrupled and is symmetrical. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Connection to "A/pulse" input transducer Double rotary transducer Quadruple rotary Connection to input "A/pulse" and "B/direction" transducer Direction Pulse at "A/pulse" input and direction at "B/direction" input Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 139
Diagnostic information is not automatically sent by the module but must be read out actively via SDO access. Further information:Product description ( 15) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 140
Bit 6 ... 4: Reset 0b000 = deactivated 0b001 = HIGH level 0b011 = rising edge 0b101 = one-time rising edge Bit 7: Reserved Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 141
2.048 ms between 0 and 522.24 ms. If the pulse duration is = 0, the output is set until the comparison condition is no longer met. I-3115/x ... Reserved I-3129/x Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Diagnostic information is not automatically sent by the module but must be read out actively via SDO access. Further information:Product description ( 15) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 143
0b100 = count value = comparison value Bit 3: Invert counting direction track B 0 = no (do not invert) 1 = yes (invert) Bit 7 ... 4: Reserved Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 144
See counter 1 0x00 counter 2 I-311A/x Signal evaluation See counter 1 0x00 counter 2 I-311B/x Set value counter 2 See counter 1 0x00 I-311E/x Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 145
2.048 ms between 0 and 522.24 ms. If the pulse duration is = 0, the output is set until the comparison condition is no longer met. I-3115/x ... Reserved I-3129/x Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Diagnostic information is not automatically sent by the module but must be read out actively via SDO access. Further information:Product description ( 15) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 147
Bit 6 ... 4: Reset 0b000 = deactivated 0b001 = HIGH level 0b011 = rising edge 0b101 = one-time rising edge Bit 7: Reserved Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
• 0b011 = rotary transducer 4-fold (connection to "A/pulse" input and "B/direction") • 0b100 = direction (pulse at "A/pulse" input and direction at "B/direction" input) Bit 7 ... 3: Reserved Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 150
"B/direction") • 0b100 = direction (pulse at "A/pulse" input and direction at "B/direction" input) Bit 7 ... 3: Reserved I-3108/x ... Reserved I-3129/x Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
More information can be found in the data sheet for your encoder. Value range: 0x00 ... 0x0F = 0 bit ... 15 bits Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Length of output data (backplane bus communication); the 0x00 (fix) image output data values are specified by the system. Other values are not permissible. I-3102/x ... Reserved I-3129/x Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Permissible values: 48 ... 8388607 (corresponds to 1 ... 175000 s Tip! The pulse/pause ratio is determined by specifying the period (0x3100 ... 0x3107) and pulse duration (0x5620). Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 159
Waiting time to be complied with until the next transmit I-3107/x ZNA (LOW byte) 0x00 request is executed. 0 ... 65535 [ms] (0x0000 ... 0xFFFF) Option 4 / 5, TMO Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 160
ASCII value of the end character that is sent after a frame and 0x00 marks the end of a transmission. 0 ... 255 (0x00 ... 0xFF) Option 12, reserved I-3110/x Reserved 0x00 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 161
Waiting time to be complied with until the next transmit request is executed. The ZNA is given as a factor of 20 ms steps. 0 ... 255 [ms] (0x00 ... 0xFA) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 162
In case of 3964(R), both partners must have different priorities. You have the following setting options: 0x00: Low 0x01: High Option 9 ... 12, reserved I-310D/x Reserved 0x00 I-3110/x Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
• 0b10: 1.5 • 0b11: 2 Bit 7/6: Flow control 0b00 • 0b00: None • 0b01: Hardware • 0b10: XON/XOFF Option 2 / 3, ZNA Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 164
The data are exchanged simultaneously between the communication partners; transmission and reception can take place at the same time. Each communication partner must simultaneously actuate a receive path. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 165
Signal R(A) 0V, signal R(B) 5V This pre-assignment corresponds to the idle state (no transmitter active) in half duplex operation under RS485. Open-circuit monitoring is not possible. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 166
Waiting time to be complied with until the next transmit I-3107/x ZNA (LOW byte) 0x00 request is executed. 0 ... 65535 [ms] (0x0000 ... 0xFFFF) Option 4 / 5, TMO Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 167
The data are exchanged simultaneously between the communication partners; transmission and reception can take place at the same time. Each communication partner must simultaneously actuate a receive path. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 168
Signal R(A) 0V, signal R(B) 5V This pre-assignment corresponds to the idle state (no transmitter active) in half duplex operation under RS485. Open-circuit monitoring is not possible. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 169
Waiting time to be complied with until the next transmit request is executed. The ZNA is given as a factor of 20 ms steps. 0 ... 255 [ms] (0x00 ... 0xFA) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 170
You have the following setting options: 0x00: Low 0x01: High Option 9 ... 12, reserved I-310D/x Reserved 0x00 I-3110/x Option 13, operating mode Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 171
Signal R(A) 0V, signal R(B) 5V This pre-assignment corresponds to the idle state (no transmitter active) in half duplex operation under RS485. Open-circuit monitoring is not possible. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
0 = no function The numerical value is ASCII-coded and complies with: 1702257011 = save parameters 65 76 61 0x73 = "E" "V" "A" "S" Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
After executing "Load", acceptance is effected by • Voltage off/on, or • Transmission of a reset node telegram (00 82 xx, with xx = node address) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Guarding event will be triggered. The I/O system switches to the status set in I-1029. The outputs switch to defined states ). • A reset takes place by a change to Operational. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 175
The response time is computed as: Monitoring time × factor I-100E Node Guarding Read only identifier Identifier = basic identifier + node address (basic identifier cannot be modified) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
• After the cycle time has elapsed, the status telegram is transferred from the I/O system to the fieldbus. • A reset takes place by a change to Operational. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 177
= Node address of the I/O system Device status (bit 1 ... 6) of the heartbeat producer: Command Formula Info (hex) Boot-up Stopped Operational Pre-Operational Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
3 Lenze-PDO Control 4 Lenze-PDO Control 5 Lenze-PDO Control 6 Lenze-PDO Control 7 Lenze-PDO Control 8 Lenze-PDO Control 9 Lenze-PDO Control 10 Lenze PDO control Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
32767 Configures the individual analog output output responses The analog outputs provide the set 1 Channel 1 value 2 Channel 2 ..36 Channel 36 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
HIGH byte Error register Error information I-1001 Error code Error code The error code 0x81 (device error) is displayed in the index I-1001 (error register). Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
0x2000 Description of the 0x00 0x00 0x00 0x00 process data width not permissible for modules with time stamp functionality or serial interfaces (I-3100/x, I-3101/x) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Bit 6: Reserved Bit 7: Reserved The module-specific bit information of the "Diagnostic Bytes 1 ... 4" (process/diagnostic alarms) are described in the following sections. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Bit 2: Latch Bit 3: Hardware gate Bit 4: Reset Bit 7 ... 5: 0 (fixed) Ticker value at the time of the alarm Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Bit 4: Channel information available Bit 7 ... 5: 0 (fix) 0 (fixed) Bit 5 ... 0: 0 (fixed) Bit 6: Process alarm lost Bit 7: 0 (fixed) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Bit 4: set in the case of internal communication error Bits 7 ... 5: 0 (fixed) Bit 6 ... 0: Channel type, 0x60: Communication processor Bit 7: 0 (fix) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Bit 4: set in the case of internal communication error Bits 7 ... 5: 0 (fixed) Bit 6 ... 0: Channel type, 0x60: Communication processor Bit 7: 0 (fix) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
• The outputs can be set 1 Channel 1 manually (forcing): 2 Channel 2 • Depending on the CAN status and on I-2360 ..36 Channel 36 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Bit 2 ... 7: Reserved Bit 8 ... 15: Counter which counts from 0 ... 127 and restarts at 0. Bits 16 ... 32: ticker value Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Bit 8 ... 15: Counter which counts 80 DWORD 64 from 0 ... 127 and restarts at 0. Bits 16 ... 32: ticker value Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
I-1004 Number of Read only supported PDOs 1 Number of synchronous PDOs supported 2 Number of synchronous PDOs supported I-1005 * Sync COB-ID 2047 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 194
Lenze setting. Function in accordance with CANopen (DS301/DS401 communication protocol). Read only Number of subindexes assigned Number of the subindices used by the index I-1011 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 195
COB-ID client -> server (Rx) SDO channel activated: bit 31 = 0 + 2 SDO2-Tx COB-ID server -> client (Tx) identifier from the SDO area I-1400 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 196
241 ... Reserved Process data update on every Every received value is accepted occurrence of an event I-1404 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 197
241 ... Reserved Process data update on every Every received value is accepted occurrence of an event I-1408 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 198
7 7th mapped object 32 bit value 0x00000000 0xFFFFFFFF 8 8th mapped object 32 bit value 0x00000000 0xFFFFFFFF I-1602 Mapping parameters for receive PDOs Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 199
6 6th mapped object 32 bit value 0x00000000 0xFFFFFFFF 7 7th mapped object 32 bit value 0x00000000 0xFFFFFFFF 8 8th mapped object 32 bit value 0x00000000 0xFFFFFFFF Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 200
7 7th mapped object 32 bit value 0x00000000 0xFFFFFFFF 8 8th mapped object 32 bit value 0x00000000 0xFFFFFFFF I-1609 Mapping parameters for receive PDOs Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 201
5 3 Inhibit time Blocking time {1 ms} 65535 5 Event time Cycle time {1 ms} 65535 I-1802 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 202
5 3 Inhibit time Blocking time {1 ms} 65535 5 Event time Cycle time {1 ms} 65535 I-1804 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 203
5 3 Inhibit time Blocking time {1 ms} 65535 5 Event time Cycle time {1 ms} 65535 I-1806 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 204
5 3 Inhibit time Blocking time {1 ms} 65535 5 Event time Cycle time {1 ms} 65535 I-1808 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 205
7 7th mapped object 32 bit value 0x00000000 0xFFFFFFFF 8 8th mapped object 32 bit value 0x00000000 0xFFFFFFFF I-1A01 Mapping parameters for transmit PDOs Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 206
6 6th mapped object 32 bit value 0x00000000 0xFFFFFFFF 7 7th mapped object 32 bit value 0x00000000 0xFFFFFFFF 8 8th mapped object 32 bit value 0x00000000 0xFFFFFFFF Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 207
7 7th mapped object 32 bit value 0x00000000 0xFFFFFFFF 8 8th mapped object 32 bit value 0x00000000 0xFFFFFFFF I-1A08 Mapping parameters for transmit PDOs Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 208
Current bus state Operational Pre-Operational I-2361 Mode CANopen Lenze system bus I-2400 Timer value Monitoring time for process data {1 ms} 65535 input objects Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 209
2 DWord 2 EPM-S601/-S603: Subindex is ..increased by 2 for each counter 64 DWord 64 I-5401 Latch value Latch value 0x00000000 0xFFFFFFFF Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 210
Bit 2 ... 7: Reserved Bit 8 ... 15: Counter which counts from 0 ... 127 and restarts at 0. Bits 16 ... 32: ticker value Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 211
Status PWM 0x0000 0xFFFF 2 entries per module 1 DWORD 1 Specification of pulse duration in 2 DWORD 2 [s]..80 DWORD 64 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 213
Event-controlled process data priority than the settings in the transfer activated TxPDOs. • Lenze setting: • System bus (CAN): I-6423 = • CANopen: I-6423 = 0 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 214
-32768 32767 output output responses The analog outputs provide the set 1 Channel 1 value 2 Channel 2 ..36 Channel 36 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Simultaneously to the cyclic process data transfer, an acyclic data link to the slaves is built up in order to parameterise the slaves. Power section DP-V1 can only be used if it is supported by the master and the slaves. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
The slaves are connected in a decentralised way to the master via the transmission medium. This system configuration serves to achieve the shortest bus cycle time. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Writing the outputs can only be done by the corresponding master of class 1 (DPM 1). Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
While the process data transfer is in progress, the master can transmit new parameter data to the slave. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
• The data of the PROFIBUS input range is transmitted to the receive buffer (buffer receive). • The data of the transmit buffer (buffer send) is transmitted to the PROFIBUS output range. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
5. When all data records have been transferred, DPM 2 cancels the connection within one time slot. Note! DPM 1 can exchange parameter data acyclically with the slaves via the MS1 channel. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Note! For further information on the services and communication with DP-V0 and DP-V1, refer to standard IEC 61158. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
• The PROFIBUS bus coupler is provided with a 9-pole Sub-D socket for connecting them to the bus. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
1B and by bus coupler modules from HW version 1A. If a module in the system complies with an earlier HW version, the diagnostic function is deactivated for all modules. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
U = D * 10 / 16384 (0x20) D = 16384 * U / 10 16384 4000 Nominal range 8192 2000 0000 Not possible, is limited to 0 V Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 225
Bit 0: Configuration/parameterisation error Bit 5 ... 1: 0 (fixed) Bit 6: Measuring range not reached Bit 7: Measuring range exceeded 10 ... 15 0 (fixed) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
U = D * 10 / 16384 (0x20) D = 16384 * U / 10 16384 4000 Nominal range 8192 2000 0000 Not possible, is limited to 0 V Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 227
Bit 0: Configuration/parameterisation error Bit 5 ... 1: 0 (fixed) Bit 6: Measuring range not reached Bit 7: Measuring range exceeded 12 ... 15 0 (fixed) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
I = D * 16 / 16384 + 4 (0x40) D = 16384 * (I-4) / 16 16384 4000 Nominal range 8192 2000 0000 -3277 F333 Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 229
Bit 0: Configuration/parameterisation error Bit 5 ... 1: 0 (fixed) Bit 6: Measuring range not reached Bit 7: Measuring range exceeded 10 ... 15 0 (fixed) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
I = D * 16 / 16384 + 4 (0x40) D = 16384 * (I-4) / 16 16384 4000 Nominal range 8192 2000 0000 -3277 F333 Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 231
Bit 0: Configuration/parameterisation error Bit 5 ... 1: 0 (fixed) Bit 6: Measuring range not reached Bit 7: Measuring range exceeded 12 ... 15 0 (fixed) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Value from the rated range; if the actual value falls below 0x8000 channel 2 this value and the limit value monitoring function is active, a process alarm is triggered. 0x8000: Limit value alarm deactivated Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 233
U = D * 10 / 16384 (0x20) D = 16384 * U / 10 16384 4000 Nominal range 8192 2000 0000 -3277 F333 Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 234
Bit 0: Configuration/parameterisation error Bit 5 ... 1: 0 (fixed) Bit 6: Measuring range not reached Bit 7: Measuring range exceeded 12 ... 15 0 (fixed) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Value from the rated range; if the actual value falls below 0x8000 channel 2 this value and the limit value monitoring function is active, a process alarm is triggered. 0x8000: Limit value alarm deactivated Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 236
I = D * 16 / 16384 + 4 (0x40) D = 16384 * (I-4) / 16 16384 4000 Nominal range 8192 2000 0000 -3277 F333 Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 237
Bit 0: Configuration/parameterisation error Bit 5 ... 1: 0 (fixed) Bit 6: Measuring range not reached Bit 7: Measuring range exceeded 12 ... 15 0 (fixed) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
U = D * 10 / 16384 (0x20) D = 16384 * U / 10 16384 4000 Nominal range 8192 2000 0000 Not possible, is limited to 0 V Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 239
Bit 0: Configuration/parameterisation error Bit 2 ... 1: 0 (fixed) Bit 3: Short circuit after M Bit 7 ... 4: 0 (fixed) 10 ... 15 0 (fixed) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
U = D * 10 / 16384 (0x20) D = 16384 * U / 10 16384 4000 Nominal range 8192 2000 0000 Not possible, is limited to 0 V Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 241
Bit 0: Configuration/parameterisation error Bit 2 ... 1: 0 (fixed) Bit 3: Short circuit after M Bit 7 ... 4: 0 (fixed) 12 ... 15 0 (fixed) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 251
Ticker value at the time of the alarm After mains connection, a timer (s ticker) is started, which after 65535 s starts with 0 again. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 252
With diagnostic alarm: OB40: OB40_2 OB40_3 OB40_4 OB40_1 OB82_1 OB82_2 OB82_1 OB82_2 OB82: incomming incomming outgoing outgo. lost Buffer memory proc. (FIFO): Buffer memory diag. (FIFO): Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 253
Bit 7 ... 5: 0 (fixed) 9 ... 15 0 (fixed) Data set 1, diagnostic alarm outgoing After the error correction, a diagnostic alarm takes place. outgoing Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
If the measured value is outside a limit value and the limit value monitoring is activated, a process alarm is triggered. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 256
Ticker value at the time of the alarm After mains connection, a timer (s ticker) is started, which after 65535 s starts with 0 again. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 257
With diagnostic alarm: OB40: OB40_2 OB40_3 OB40_4 OB40_1 OB82_1 OB82_2 OB82_1 OB82_2 OB82: incomming incomming outgoing outgo. lost Buffer memory proc. (FIFO): Buffer memory diag. (FIFO): Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 258
Bit 7 ... 5: 0 (fixed) 9 ... 15 0 (fixed) Data set 1, diagnostic alarm outgoing After the error correction, a diagnostic alarm takes place. outgoing Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
By specification of a hysteresis you can for instance prevent the output from being permanently switched if the value of an encoder signal fluctuates around the comparison value. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 260
Set value: With an edge change 0-1 of COUNTERVAL_SET in the control word, the set value is accepted in the counter. Counter modules EPM-S600 ... EPM-S603 – control and status words ( 27) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 261
0x02 7 (0x07): 5 kHz Gate 8 (0x08): 2 kHz 9 (0x09): 1 kHz Other values are not permissible! Input frequency 0x00 Reset Reserved Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 262
Bit 7: Gate function (internal gate) • 0= abort (counting process starts again from loading value) • 1 = interrupt (counting process is continued with counter content) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 263
With every change of the count value, the time value of the timer is stored as 16-bit-s value together with the count value in the input area. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 264
With diagnostic alarm: OB40: OB40_2 OB40_3 OB40_4 OB40_1 OB82_1 OB82_2 OB82_1 OB82_2 OB82: incomming incomming outgoing outgo. lost Buffer memory proc. (FIFO): Buffer memory diag. (FIFO): Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 265
Bit 7 ... 5: 0 (fixed) 9 ... 15 0 (fixed) Data set 1, diagnostic alarm outgoing After the error correction, a diagnostic alarm takes place. outgoing Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
If the diagnostic alarm is enabled in the parameter setting, it occurs if another process alarm is triggered for the same event during a process alarm processing. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 267
The diagnostic information describes the diagnostic contents that can be read out of a module. Diagnostic information is not automatically sent by the module but must be read out actively via SDO access. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 268
STS_COMP in the counter status or the process alarm is to be specified via data record 0x80 for counter 1 and 0x82 for counter 2. Counter modules EPM-S600 ... EPM-S603 – control and status words ( 27) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 269
Input frequency 0x02 7 (0x07): 5 kHz Counter 2, track B 8 (0x08): 2 kHz 9 (0x09): 1 kHz Other values are not permissible! Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 270
0 and 255. With the settings 0 and 1 the hysteresis is switched off. The hysteresis has an effect on the zero crossing, comparison, overflow/underflow. Reserved Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 271
Final value counter 2 See counter 1 0x00 8...11 Loading value See counter 1 0x00 counter 2 Hysteresis counter 2 See counter 1 0x00 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 272
With every change of the count value, the time value of the timer is stored as 16-bit-s value together with the count value in the input area. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 273
With diagnostic alarm: OB40: OB40_2 OB40_3 OB40_4 OB40_1 OB82_1 OB82_2 OB82_1 OB82_2 OB82: incomming incomming outgoing outgo. lost Buffer memory proc. (FIFO): Buffer memory diag. (FIFO): Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 274
Bit 7 ... 4: 0 (fixed) 10 ... 15 0 (fixed) Data set 1, diagnostic alarm outgoing After the error correction, a diagnostic alarm takes place. outgoing Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
If the diagnostic alarm is enabled in the parameter setting, it occurs if another process alarm is triggered for the same event during a process alarm processing. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 276
The diagnostic information describes the diagnostic contents that can be read out of a module. Diagnostic information is not automatically sent by the module but must be read out actively via SDO access. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 277
Set value: With an edge change 0-1 of COUNTERVAL_SET in the control word, the set value is accepted in the counter. Counter modules EPM-S600 ... EPM-S603 – control and status words ( 27) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 278
4 (0x04): 30 kHz 6 (0x06): 10 kHz Reserved 7 (0x07): 5 kHz 8 (0x08): 2 kHz 9 (0x09): 1 kHz Other values are not permissible! Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 279
0x81 4...7 Final value Upper limitation of the counting range 0x00 8...11 Start value Lower limitation of the counting range 0x00 Hysteresis 0x00 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 280
With every change of the count value, the time value of the timer is stored as 16-bit-s value together with the count value in the input area. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 281
With diagnostic alarm: OB40: OB40_2 OB40_3 OB40_4 OB40_1 OB82_1 OB82_2 OB82_1 OB82_2 OB82: incomming incomming outgoing outgo. lost Buffer memory proc. (FIFO): Buffer memory diag. (FIFO): Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 282
Bit 7 ... 4: 0 (fixed) 10 ... 15 0 (fixed) Data set 1, diagnostic alarm outgoing After the error correction, a diagnostic alarm takes place. outgoing Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Access Assignment Word Counter 1: Control word Word Counter 2: Control word Counter modules EPM-S600 ... EPM-S603 – control and status words ( 27) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 284
• 0b011 = rotary transducer 4-fold (connection to "A/pulse" input and "B/direction") • 0b100 = direction (pulse at "A/pulse" input and direction at "B/direction" input) Bit 7 ... 3: Reserved Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 285
Number of diagnostic bits output by the module per channel (here 0x00)) Number of channels of a module (here 0x02) 7 ... 15 0 (fixed) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
With every change of the encoder value, the time value of the timer is stored as 16-bit-s value together with the count value in the input area. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 287
More information can be found in the data sheet for your encoder. Value range: 0x00 ... 0x0F = 0 bit ... 15 bits Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 288
Information on this can be found in the data sheet for your encoder. 0 = standard code 1 = Gray code Bit 7 ... 5: Reserved Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 289
In the "monitor operation" mode, the module starts with the encoder evaluation. 0 (0x00) = inhibited 1 (0x01) = enabled Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 290
With diagnostic alarm: OB40: OB40_2 OB40_3 OB40_4 OB40_1 OB82_1 OB82_2 OB82_1 OB82_2 OB82: incomming incomming outgoing outgo. lost Buffer memory proc. (FIFO): Buffer memory diag. (FIFO): Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 291
8 ... 15 0 (fixed) Data set 1, diagnostic alarm outgoing Byte Bit 7 ... 0 After the error correction, a diagnostic alarm takes place. outgoing Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
With every change of the encoder value, the time value of the timer is stored as 16-bit-s value together with the count value in the input area. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 293
Number of diagnostic bits output by the module per channel (here 0x00)) Number of channels of a module (here 0x02) 7 ... 15 0 (fixed) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Note that no more time stamp entries can be accepted once the FIFO memory is full. You should always establish the status of the FIFO memory before the transfer to ensure that your entries are accepted. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 295
Ticker value: Specify a time here in s at which the status of the outputs is to be accepted (value range: 0 ... 65535). Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 296
Number of diagnostic bits output by the module per channel (here 0x00)) Number of channels of a module (here 0x02) 7 ... 15 0 (fixed) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Here you can define the PWM output behaviour for the corresponding channel and start or stop the PWM output. PWM module EPM-S620 – control and status word ( 32) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 298
0x02 Byte 0: Here 0x02 CHERR Reserved 0x00 CH0ERR ... CH7ERR Reserved 0x00 DIAG_US Value of s ticker when diagnostics occur Bytes 0 ...3 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 301
Waiting time to be complied with until the next transmit ZNA (LOW byte) 0x00 request is executed. 0 ... 65535 [ms] (0x0000 ... 0xFFFF) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 302
ASCII value of the end character that is sent after a frame and 0x00 marks the end of a transmission. 0 ... 255 (0x00 ... 0xFF) Option 12, reserved 0x80 Reserved 0x00 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 303
• 0b10: 1.5 • 0b11: 2 Bit 7/6: Flow control 0b00 • 0b00: None • 0b01: Hardware • 0b10: XON/XOFF Option 2, ZNA (x 20 ms) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 304
In case of 3964(R), both partners must have different priorities. You have the following setting options: 0x00: Low 0x01: High Option 9 ... 12, reserved 0x80 Reserved 0x00 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 305
Bit 7 ... 0: Reserved 0x00 CH0ERR ... CH7ERR Bit 7 ... 0: Reserved 0x00 DIAG_US Value of s ticker when diagnostics occur 0x00 Bytes 0 ...3 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
• 0b10: 1.5 • 0b11: 2 Bit 7/6: Flow control 0b00 • 0b00: None • 0b01: Hardware • 0b10: XON/XOFF Option 2 / 3, ZNA Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 307
The data are exchanged simultaneously between the communication partners; transmission and reception can take place at the same time. Each communication partner must simultaneously actuate a receive path. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 308
Signal R(A) 0V, signal R(B) 5V This pre-assignment corresponds to the idle state (no transmitter active) in half duplex operation under RS485. Open-circuit monitoring is not possible. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 309
Waiting time to be complied with until the next transmit ZNA (LOW byte) 0x00 request is executed. 0 ... 65535 [ms] (0x0000 ... 0xFFFF) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 310
The data are exchanged simultaneously between the communication partners; transmission and reception can take place at the same time. Each communication partner must simultaneously actuate a receive path. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 311
Signal R(A) 0V, signal R(B) 5V This pre-assignment corresponds to the idle state (no transmitter active) in half duplex operation under RS485. Open-circuit monitoring is not possible. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 312
• 0b10: 1.5 • 0b11: 2 Bit 7/6: Flow control 0b00 • 0b00: None • 0b01: Hardware • 0b10: XON/XOFF Option 2, ZNA (x 20 ms) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 313
In case of 3964(R), both partners must have different priorities. You have the following setting options: 0x00: Low 0x01: High Option 9 ... 12, reserved 0x80 Reserved 0x00 Option 13, operating mode Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 314
Signal R(A) 0V, signal R(B) 5V This pre-assignment corresponds to the idle state (no transmitter active) in half duplex operation under RS485. Open-circuit monitoring is not possible. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 315
Bits 7 ... 5: 0 (fixed) CH1ERR ... CH7ERR Bit 7 ... 0: Reserved 0x00 DIAG_US Value of s ticker when diagnostics occur 0x00 Bytes 0 ...3 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
ID number Low Byte More information on the structure of the standard diagnostic data can be found in the documentation of the PROFIBUS user organisation. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Bit 7: Entry of module in PROFIBUS slot 56 x + 8 Bit 0: Entry of module in PROFIBUS slot 57 Bit 7: Entry of module in PROFIBUS slot 64 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Bit 3, 2: Module status module in PROFIBUS slot 34 Bit 5, 4: Module status module in PROFIBUS slot 35 Bit 7, 6: Module status module in PROFIBUS slot 36 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 319
Bit 3, 2: Module status module in PROFIBUS slot 62 Bit 5, 4: Module status module in PROFIBUS slot 63 Bit 7, 6: Module status module in PROFIBUS slot 64 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
• 0b10: Diagnostic alarm outgoing • 0b11: Reserved Bit 2: • 0 (fixed) Bit 7 ... 3: Alarm sequence number 0 ... 31 • 0b00000 ... 0b11111 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 322
More information on the diagnostic data of a process alarm (bytes x + 4 to x + 7) can be found in the respective module description. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
As each EtherCAT gateway is assigned a clear address (MAC address), the data-related sequence is independent of the physical sequence of the EtherCAT gateways in the network. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
• Length of the datagrams within the EtherCAT frame (length) • One reserved bit • Type of the datagrams within the EtherCAT frame (type) • Datagrams • Checksum of the EtherCAT frame Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
• Mailbox communication on the "Application Layer" • Process data communication (only the inputs are evaluated, the outputs are in the "safe" status.) Operational • Inputs and outputs are evaluated. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
The process data size of the I/O area is described by XML device description files. Import the following two files via an EtherCAT configurator for this purpose: • EtherCAT bus coupler module: Lenze_IOSystem1000_EPM_S130.xml • I/O compound module: Lenze_IOSystem1000_EPM_S130_Modules.xml Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
I-7000 0x00 Output data Unsigned8 Number of output data subindexes for the corresponding EtherCAT slot no. I-703F 0x01 Output data (see module description) 0x02 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
• are, for instance, used for one-off plant settings or a change of material in a machine. • are transmitted with a low priority. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
The following example shows access to the parameters of the module in slot 4 via index I-3103. Phy. slot Module Index 0x3100* 03101* 0x3102* 0x3103 EtherCAT slot no. This entry is not executed because the module is not parameterisable. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
U = D * 10 / 16384 (0x20) D = 16384 * U / 10 16384 4000 Nominal range 8192 2000 0000 Not possible, is limited to 0 V Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
U = D * 10 / 16384 (0x20) D = 16384 * U / 10 16384 4000 Nominal range 8192 2000 0000 Not possible, is limited to 0 V Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Value from the rated range; if the actual value falls below this 0x8000 channel 2 value and the limit value monitoring function is active, a process alarm is triggered. 0x8000: Limit value alarm deactivated Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 335
U = D * 10 / 16384 (0x20) D = 16384 * U / 10 16384 4000 Nominal range 8192 2000 0000 -3277 F333 Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Value from the rated range; if the actual value falls below this 0x8000 channel 2 value and the limit value monitoring function is active, a process alarm is triggered. 0x8000: Limit value alarm deactivated Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 337
I = D * 16 / 16384 + 4 (0x40) D = 16384 * (I-4) / 16 16384 4000 Nominal range 8192 2000 0000 -3277 F333 Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
U = D * 10 / 16384 (0x20) D = 16384 * U / 10 16384 4000 Nominal range 8192 2000 0000 Not possible, is limited to 0 V Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
U = D * 10 / 16384 (0x20) D = 16384 * U / 10 16384 4000 Nominal range 8192 2000 0000 Not possible, is limited to 0 V Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
By specification of a hysteresis you can for instance prevent the output from being permanently switched if the value of an encoder signal fluctuates around the comparison value. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 352
Bit 3: Proc. alarm underflow Bit 4: Proc. alarm comparison value Bit 5: Proc. alarm final value Bit 6: Proc. alarm latch value Bit 7: Reserved Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 353
* The values will only be accepted after the state has changed from "Pre-Operational" to "Operational". Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
The diagnostic information describes the diagnostic contents that can be read out of a information module. Diagnostic information is not automatically sent by the module but must be read out actively via SDO access. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 356
0b100 = count value = comparison value Bit 3: Invert counting direction track B 0 = no (do not invert) 1 = yes (invert) Bit 7 ... 4: Reserved Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 357
2 Hysteresis counter 2 See counter 1 0x00 * The values will only be accepted after the state has changed from "Pre-Operational" to "Operational". Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
The diagnostic information describes the diagnostic contents that can be read out of a information module. Diagnostic information is not automatically sent by the module but must be read out actively via SDO access. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 359
Bit 6 ... 4: Reset 0b000 = deactivated 0b001 = HIGH level 0b011 = rising edge 0b101 = one-time rising edge Bit 7: Reserved Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 360
Lower limitation of the counting range 0x00 Hysteresis 0x00 * The values will only be accepted after the state has changed from "Pre-Operational" to "Operational". Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
• 0b011 = rotary transducer 4-fold (connection to "A/pulse" input and "B/direction") • 0b100 = direction (pulse at "A/pulse" input and direction at "B/direction" input) Bit 7 ... 3: Reserved Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 362
• 0b100 = direction (pulse at "A/pulse" input and direction at "B/direction" input) Bit 7 ... 3: Reserved * The values will only be accepted after the state has changed from "Pre-Operational" to "Operational". Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Gray-binary conversion. More information can be found in the data sheet for your encoder. Value range: 0x00 ... 0x0F = 0 bit ... 15 bits Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Length of output data (backplane bus communication); the 0x00 (fix) image output data values are specified by the system. Other values are not permissible. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Values below 25 s are ignored. If the pulse duration is higher or equal to the period, the DO output is set permanently. Value range: 1200 ... 8388607 (25 s ... approx. 175 ms) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 370
Waiting time to be complied with until the next transmit 0x08 ZNA (LOW byte) 0x00 request is executed. 0 ... 65535 [ms] (0x0000 ... 0xFFFF) Option 4 / 5, TMO Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 371
ASCII value of the end character that is sent after a frame and 0x00 marks the end of a transmission. 0 ... 255 (0x00 ... 0xFF) Option 12, reserved 0x11 Reserved 0x00 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 372
Waiting time to be complied with until the next transmit request is executed. The ZNA is given as a factor of 20 ms steps. 0 ... 255 [ms] (0x00 ... 0xFA) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 373
In case of 3964(R), both partners must have different priorities. You have the following setting options: 0x00: Low 0x01: High Option 9 ... 12, reserved 0x0E Reserved 0x00 0x11 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
• 0b10: 1.5 • 0b11: 2 Bit 7/6: Flow control 0b00 • 0b00: None • 0b01: Hardware • 0b10: XON/XOFF Option 2 / 3, ZNA Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 375
The data are exchanged simultaneously between the communication partners; transmission and reception can take place at the same time. Each communication partner must simultaneously actuate a receive path. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 376
Signal R(A) 0V, signal R(B) 5V This pre-assignment corresponds to the idle state (no transmitter active) in half duplex operation under RS485. Open-circuit monitoring is not possible. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 377
Waiting time to be complied with until the next transmit 0x08 ZNA (LOW byte) 0x00 request is executed. 0 ... 65535 [ms] (0x0000 ... 0xFFFF) Option 4 / 5, TMO Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 378
The data are exchanged simultaneously between the communication partners; transmission and reception can take place at the same time. Each communication partner must simultaneously actuate a receive path. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 379
Signal R(A) 0V, signal R(B) 5V This pre-assignment corresponds to the idle state (no transmitter active) in half duplex operation under RS485. Open-circuit monitoring is not possible. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 380
Waiting time to be complied with until the next transmit request is executed. The ZNA is given as a factor of 20 ms steps. 0 ... 255 [ms] (0x00 ... 0xFA) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 381
You have the following setting options: 0x00: Low 0x01: High Option 9 ... 12, reserved 0x0E Reserved 0x00 0x11 Option 13, operating mode Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 382
Signal R(A) 0V, signal R(B) 5V This pre-assignment corresponds to the idle state (no transmitter active) in half duplex operation under RS485. Open-circuit monitoring is not possible. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
• Writing to 0x06 of index I-5000: Resets counter for process alarms • Writing to 0x06 of index I-5002: Resets counter for diagnostics alarm Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Bit 2: Limit value underflow, channel 3 Bit 3: Limit value underflow, channel 4 Bit 7 ... 4: 0 (fix) Ticker value at the time of the alarm Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 385
Bit 2: Counter 2, A/pulse Bit 3: Counter 2, B/direction Bit 7 ... 4: 0 (fix) 16 bit s value at the time of the alarm Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Bit 4: Set in case of internal communication error Bit 5: Reserved Bit 6: Set if process alarm is lost Bit 7: 0 (fixed) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 387
Bits 7 ... 5: 0 (fixed) 0 (fixed) Bit 5 ... 0: 0 (fix) Bit 6: Set if process alarm is lost Bit 7: 0 (fixed) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 388
Bit 4: channel information available Bits 7 ... 5: 0 (fixed) 0 (fixed) Bit 5 ... 0: 0 (fix) Bit 6: Process alarm lost Bit 7: 0 (fixed) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 390
Bit5: Set if process alarm is lost Bit 6: Set in case of measuring range underflow Bit 7: Set in case of measuring range exceedance 11 ... 16 0 (fixed) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 391
Bit 2: Overflow/underflow/final value Bit 3: Comparison value reached Bit 4: Latch value Bits 7 ... 5: 0 (fixed) 10 ... 16 0 (fixed) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 392
Bit 1 ... 0: 0 (fix) Bit 2: Overflow/underflow/final value Bit 3: Comparison value reached Bit 7 ... 4: 0 (fix) 11 ... 16 0 (fixed) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 393
Bit 1 ... 0: 0 (fix) Bit 2: Overflow/underflow/final value Bit 3: Comparison value reached Bit 7 ... 4: 0 (fix) 11 ... 16 0 (fixed) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 394
Number of diagnostic bits output by the module per channel (here 0x08)) Number of channels of a module (here 0x01) Bit 0: Error in channel group 0 9 ... 16 0 (fixed) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Mapping for coupler's alarm counter 1 Input mapping Mapping for process alarm counter 2 Input mapping ..Mapping for the diagnostic alarm counter Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 396
EtherCAT coupler. In this mode, diagnostic data is overwritten by new alarms. Auto- acknowledge = 1 by default. Auto-acknowledge should be activated for continuous use. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 397
1 Master FPGA FPGA version 2 I/O bus Backplane bus version 3 Firmware package Version package 4 Mx file Name and version of coupler's Mx file Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 398
0xF100 and acknowledge the process alarm by writing any value to subindex 0x06 of index I-5000. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
O, S O, P S P + E, S + E Configuration 0x0032 PLL Error O, S O S + E Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
EPM-S130 module area too P > S P + E big or small Init P: Pre-Operational S: Safe-Operational O: Operational B: Bootstrap E: Error Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Object directory dynamic generation fails or no object directory is present (e.g. object directory is generated from file and generation fails because of an file error) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Messages that are longer than 8 bytes are subject to the fragmentation service. A set of rules for master/slave, peer-to-peer- and multi-master connections is also available. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 405
Addressing All stations on the bus must be uniquely identified by means of an ID address. Every DeviceNet device has addressing facilities. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
DeviceNet bus coupler. In the following, slots within the DeviceNet are called DeviceNet slots. Counting always starts at 1. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
9. Start the DeviceNet scanner. After the DeviceNet scanner has been configured, the input and output modules can be triggered under the configured addresses. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Modules that have not yet been parameterised will be automatically supplied with their default values as soon as a read access from the configuration tool is executed. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
U = D * 10 / 16384 (0x20) D = 16384 * U / 10 16384 4000 Nominal range 8192 2000 0000 Not possible, is limited to 0 V Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
U = D * 10 / 16384 (0x20) D = 16384 * U / 10 16384 4000 Nominal range 8192 2000 0000 Not possible, is limited to 0 V Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
0x8000: Limit value alarm deactivated With the formulas listed in the following you can convert a digital value into an analog output value and vice versa. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 415
U = D * 10 / 16384 (0x20) D = 16384 * U / 10 16384 4000 Nominal range 8192 2000 0000 -3277 F333 Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
0x8000: Limit value alarm deactivated With the formulas listed in the following you can convert a digital value into an analog output value and vice versa. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 417
I = D * 16 / 16384 + 4 (0x40) D = 16384 * (I-4) / 16 16384 4000 Nominal range 8192 2000 0000 -3277 F333 Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
U = D * 10 / 16384 (0x20) D = 16384 * U / 10 16384 4000 Nominal range 8192 2000 0000 Not possible, is limited to 0 V Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
U = D * 10 / 16384 (0x20) D = 16384 * U / 10 16384 4000 Nominal range 8192 2000 0000 Not possible, is limited to 0 V Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
By specification of a hysteresis you can for instance prevent the output from being permanently switched if the value of an encoder signal fluctuates around the comparison value. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 434
Diagnostic information is not automatically sent by the module but must be read out actively via SDO access. Further information:Product description ( 15) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 435
0b001000 = periodic counting, main counting direction is forward 0b010000 = periodic counting, main counting direction is backward 0b100000 = periodic counting, no main counting direction Bit 7 ... 6: Reserved Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 436
2.048 ms between 0 and 522.24 ms. If the pulse duration is = 0, the output is set until the comparison condition is no longer met. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Diagnostic information is not automatically sent by the module but must be read out actively via SDO access. Further information:Product description ( 15) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 438
0b100 = count value = comparison value Bit 3: Invert counting direction track B 0 = no (do not invert) 1 = yes (invert) Bit 7 ... 4: Reserved Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 439
0x00 Final value counter 2 See counter 1 0x00 Loading value See counter 1 0x00 counter 2 Hysteresis counter 2 See counter 1 0x00 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Diagnostic information is not automatically sent by the module but must be read out actively via SDO access. Further information:Product description ( 15) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 441
Bit 6 ... 4: Reset 0b000 = deactivated 0b001 = HIGH level 0b011 = rising edge 0b101 = one-time rising edge Bit 7: Reserved Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 442
• 1 = interrupt (counting process is continued with counter content) Final value Upper limitation of the counting range 0x00 Start value Lower limitation of the counting range 0x00 Hysteresis 0x00 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
• 0b011 = rotary transducer 4-fold (connection to "A/pulse" input and "B/direction") • 0b100 = direction (pulse at "A/pulse" input and direction at "B/direction" input) Bit 7 ... 3: Reserved Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 444
• 0b011 = rotary transducer 4-fold (connection to "A/pulse" input and "B/direction") • 0b100 = direction (pulse at "A/pulse" input and direction at "B/direction" input) Bit 7 ... 3: Reserved Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
More information can be found in the data sheet for your encoder. Value range: 0x00 ... 0x0F = 0 bit ... 15 bits Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Length of output data (backplane bus communication); the 0x00 (fix) image output data values are specified by the system. Other values are not permissible. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
0x10: 109700 Baud Protocol The protocol to be used. This setting influences the structure 0x01 of the parameter data. 0x01: ASCII Option 1, drawing frame Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 451
Waiting time to be complied with until the next transmit ZNA (LOW byte) 0x00 request is executed. 0 ... 65535 [ms] (0x0000 ... 0xFFFF) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 452
ASCII value of the end character that is sent after a frame and 0x00 marks the end of a transmission. 0 ... 255 (0x00 ... 0xFF) Option 12, reserved Reserved 0x00 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 453
• 0b10: 1.5 • 0b11: 2 Bit 7/6: Flow control 0b00 • 0b00: None • 0b01: Hardware • 0b10: XON/XOFF Option 2, ZNA (x 20 ms) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 454
In case of 3964(R), both partners must have different priorities. You have the following setting options: 0x00: Low 0x01: High Option 9 ... 12, reserved Reserved 0x00 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
• 0b10: 1.5 • 0b11: 2 Bit 7/6: Flow control 0b00 • 0b00: None • 0b01: Hardware • 0b10: XON/XOFF Option 2 / 3, ZNA Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 456
The data are exchanged simultaneously between the communication partners; transmission and reception can take place at the same time. Each communication partner must simultaneously actuate a receive path. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 457
Signal R(A) 0V, signal R(B) 5V This pre-assignment corresponds to the idle state (no transmitter active) in half duplex operation under RS485. Open-circuit monitoring is not possible. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 458
Waiting time to be complied with until the next transmit ZNA (LOW byte) 0x00 request is executed. 0 ... 65535 [ms] (0x0000 ... 0xFFFF) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 459
The data are exchanged simultaneously between the communication partners; transmission and reception can take place at the same time. Each communication partner must simultaneously actuate a receive path. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 460
Signal R(A) 0V, signal R(B) 5V This pre-assignment corresponds to the idle state (no transmitter active) in half duplex operation under RS485. Open-circuit monitoring is not possible. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 461
• 0b10: 1.5 • 0b11: 2 Bit 7/6: Flow control 0b00 • 0b00: None • 0b01: Hardware • 0b10: XON/XOFF Option 2, ZNA (x 20 ms) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 462
In case of 3964(R), both partners must have different priorities. You have the following setting options: 0x00: Low 0x01: High Option 9 ... 12, reserved Reserved 0x00 Option 13, operating mode Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 463
Signal R(A) 0V, signal R(B) 5V This pre-assignment corresponds to the idle state (no transmitter active) in half duplex operation under RS485. Open-circuit monitoring is not possible. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
This ensures the time- controlled and cycle-synchronous transfer of data. Here, sync frames of a sync master in the network provide for synchronisation. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 465
A network is physically limited by a router. For communication via network limits, you must program your routers in such a way that they permit this communication. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 466
GSDML file Lenze provides you with a GSDML file for your IO-Device. This file is either located on the enclosed data medium or in the download area of www.lenze.de. Install the GSDML file in your project planning tool. More information on how to install the GSDML file can be found in the manual of your project planning tool.
Data record DS 0x01 of the module parameters 1 ... 64 0x007F Data record DS 0x80 ... 0x90 of the module parameters 1 ... 64 0x0080 ...0x0090 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
• Index = 0x0001: Data record DS 0x01 of the diagnostic data Note! Information on how to assign the ranges can be found in the descriptions of the corresponding I/O compound module. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 471
Value of the s ticker when diagnostic data is generated (The I/O compound module features a timer that is started with mains ON and restarts with 0 after 232-1 s.) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
PROFINET IO -> More field devices -> I/O > I/O system 1000 GSDML file Lenze provides you with a GSDML file for the I/O device. This file is either located on the enclosed data medium or in the download area of www.lenze.de. Install the GSDML file in your configuring tool.
Page 473
In the Intel format, the bytes are stored in ascending order, i.e. the first byte contains the Low byte and the second byte contains the High byte. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
I&M0 / Index 0xAFF0: 0x54 (see the following table) I&M1 / Index 0xAFF1: 0x54 I&M2 / Index 0xAFF2: 0x16 I&M3 / Index 0xAFF3: 0x54 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 475
Maintenance data 2: (index 0xAFF2) IM_DATE Read/write YYYY-MMDD Selection of an (16 bytes) HH:MM date Maintenance data 3: (index 0xAFF3) IM_DESCRIPTOR Read/write Selection of a (54 bytes) comment Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
U = D * 10 / 16384 (0x20) D = 16384 * U / 10 16384 4000 Nominal range 8192 2000 0000 Not possible, is limited to 0 V Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 478
Bit 0: Configuration/parameterisation error Bit 5 ... 1: 0 (fixed) Bit 6: Measuring range not reached Bit 7: Measuring range exceeded 10 ... 15 0 (fixed) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
U = D * 10 / 16384 (0x20) D = 16384 * U / 10 16384 4000 Nominal range 8192 2000 0000 Not possible, is limited to 0 V Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 480
Bit 0: Configuration/parameterisation error Bit 5 ... 1: 0 (fixed) Bit 6: Measuring range not reached Bit 7: Measuring range exceeded 12 ... 15 0 (fixed) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
I = D * 16 / 16384 + 4 (0x40) D = 16384 * (I-4) / 16 16384 4000 Nominal range 8192 2000 0000 -3277 F333 Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 482
Bit 0: Configuration/parameterisation error Bit 5 ... 1: 0 (fixed) Bit 6: Measuring range not reached Bit 7: Measuring range exceeded 10 ... 15 0 (fixed) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
I = D * 16 / 16384 + 4 (0x40) D = 16384 * (I-4) / 16 16384 4000 Nominal range 8192 2000 0000 -3277 F333 Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 484
Channel-specific errors: channel 3: Bit 0: Configuration/parameterisation error Bit 5 ... 1: 0 (fixed) Bit 6: Measuring range not reached Bit 7: Measuring range exceeded Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Value from the rated range; if the actual value falls below 0x8000 channel 2 this value and the limit value monitoring function is active, a process alarm is triggered. 0x8000: Limit value alarm deactivated Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 486
U = D * 10 / 16384 (0x20) D = 16384 * U / 10 16384 4000 Nominal range 8192 2000 0000 -3277 F333 Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 487
Bit 0: Configuration/parameterisation error Bit 5 ... 1: 0 (fixed) Bit 6: Measuring range not reached Bit 7: Measuring range exceeded 12 ... 15 0 (fixed) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Value from the rated range; if the actual value falls below 0x8000 channel 2 this value and the limit value monitoring function is active, a process alarm is triggered. 0x8000: Limit value alarm deactivated Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 489
I = D * 16 / 16384 + 4 (0x40) D = 16384 * (I-4) / 16 16384 4000 Nominal range 8192 2000 0000 -3277 F333 Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 490
Bit 0: Configuration/parameterisation error Bit 5 ... 1: 0 (fixed) Bit 6: Measuring range not reached Bit 7: Measuring range exceeded 12 ... 15 0 (fixed) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
U = D * 10 / 16384 (0x20) D = 16384 * U / 10 16384 4000 Nominal range 8192 2000 0000 Not possible, is limited to 0 V Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 492
Bit 0: Configuration/parameterisation error Bit 2 ... 1: 0 (fixed) Bit 3: Short circuit after M Bit 7 ... 4: 0 (fixed) 10 ... 15 0 (fixed) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
U = D * 10 / 16384 (0x20) D = 16384 * U / 10 16384 4000 Nominal range 8192 2000 0000 Not possible, is limited to 0 V Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 494
Bit 0: Configuration/parameterisation error Bit 2 ... 1: 0 (fixed) Bit 3: Short circuit after M Bit 7 ... 4: 0 (fixed) 12 ... 15 0 (fixed) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
As soon as the measured value is outside a limit value and limit value monitoring is activated, a process alarm is triggered. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 500
As soon as the measured value is outside a limit value and limit value monitoring is activated, a process alarm is triggered. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 501
-243 °C -2430 Underflow 4-wire: PT1000 +1000 °C +10000 Overflow (0x61) -200 ... +850 °C -2000 ... +8500 Nominal range -243 °C -2430 Underflow Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 504
Ticker value at the time of the alarm After mains connection, a timer (s ticker) is started, which after 65535 s starts with 0 again. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 505
With diagnostic alarm: OB40: OB40_2 OB40_3 OB40_4 OB40_1 OB82_1 OB82_2 OB82_1 OB82_2 OB82: incomming incomming outgoing outgo. lost Buffer memory proc. (FIFO): Buffer memory diag. (FIFO): Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 506
Bit 7 ... 5: 0 (fixed) 9 ... 15 0 (fixed) Data set 1, diagnostic alarm outgoing After the error correction, a diagnostic alarm takes place. outgoing Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
If the measured value is outside a limit value and the limit value monitoring is activated, a process alarm is triggered. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 509
Ticker value at the time of the alarm After mains connection, a timer (s ticker) is started, which after 65535 s starts with 0 again. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 510
With diagnostic alarm: OB40: OB40_2 OB40_3 OB40_4 OB40_1 OB82_1 OB82_2 OB82_1 OB82_2 OB82: incomming incomming outgoing outgo. lost Buffer memory proc. (FIFO): Buffer memory diag. (FIFO): Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 511
Bit 7 ... 5: 0 (fixed) 9 ... 15 0 (fixed) Data set 1, diagnostic alarm outgoing After the error correction, a diagnostic alarm takes place. outgoing Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
By specification of a hysteresis you can for instance prevent the output from being permanently switched if the value of an encoder signal fluctuates around the comparison value. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 513
Set value: With an edge change 0-1 of COUNTERVAL_SET in the control word, the set value is accepted in the counter. Counter modules EPM-S600 ... EPM-S603 – control and status words ( 27) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 514
0x02 7 (0x07): 5 kHz Gate 8 (0x08): 2 kHz 9 (0x09): 1 kHz Other values are not permissible! Input frequency 0x00 Reset Reserved Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 515
Bit 7: Gate function (internal gate) • 0= abort (counting process starts again from loading value) • 1 = interrupt (counting process is continued with counter content) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 516
With every change of the count value, the time value of the timer is stored as 16-bit-s value together with the count value in the input area. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 517
With diagnostic alarm: OB40: OB40_2 OB40_3 OB40_4 OB40_1 OB82_1 OB82_2 OB82_1 OB82_2 OB82: incomming incomming outgoing outgo. lost Buffer memory proc. (FIFO): Buffer memory diag. (FIFO): Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 518
Bit 7 ... 5: 0 (fixed) 9 ... 15 0 (fixed) Data set 1, diagnostic alarm outgoing After the error correction, a diagnostic alarm takes place. outgoing Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
If the diagnostic alarm is enabled in the parameter setting, it occurs if another process alarm is triggered for the same event during a process alarm processing. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 520
The diagnostic information describes the diagnostic contents that can be read out of a module. Diagnostic information is not automatically sent by the module but must be read out actively via SDO access. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 521
STS_COMP in the counter status or the process alarm is to be specified via data record 0x80 for counter 1 and 0x82 for counter 2. Counter modules EPM-S600 ... EPM-S603 – control and status words ( 27) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 522
Input frequency 0x02 7 (0x07): 5 kHz Counter 2, track B 8 (0x08): 2 kHz 9 (0x09): 1 kHz Other values are not permissible! Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 523
0 and 255. With the settings 0 and 1 the hysteresis is switched off. The hysteresis has an effect on the zero crossing, comparison, overflow/underflow. Reserved Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 524
Final value counter 2 See counter 1 0x00 8...11 Loading value See counter 1 0x00 counter 2 Hysteresis counter 2 See counter 1 0x00 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 525
With every change of the count value, the time value of the timer is stored as 16-bit-s value together with the count value in the input area. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 526
With diagnostic alarm: OB40: OB40_2 OB40_3 OB40_4 OB40_1 OB82_1 OB82_2 OB82_1 OB82_2 OB82: incomming incomming outgoing outgo. lost Buffer memory proc. (FIFO): Buffer memory diag. (FIFO): Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 527
Bit 7 ... 4: 0 (fixed) 10 ... 15 0 (fixed) Data set 1, diagnostic alarm outgoing After the error correction, a diagnostic alarm takes place. outgoing Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
If the diagnostic alarm is enabled in the parameter setting, it occurs if another process alarm is triggered for the same event during a process alarm processing. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 529
The diagnostic information describes the diagnostic contents that can be read out of a module. Diagnostic information is not automatically sent by the module but must be read out actively via SDO access. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 530
Set value: With an edge change 0-1 of COUNTERVAL_SET in the control word, the set value is accepted in the counter. Counter modules EPM-S600 ... EPM-S603 – control and status words ( 27) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 531
4 (0x04): 30 kHz 6 (0x06): 10 kHz Reserved 7 (0x07): 5 kHz 8 (0x08): 2 kHz 9 (0x09): 1 kHz Other values are not permissible! Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 532
0x81 4...7 Final value Upper limitation of the counting range 0x00 8...11 Start value Lower limitation of the counting range 0x00 Hysteresis 0x00 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 533
With every change of the count value, the time value of the timer is stored as 16-bit-s value together with the count value in the input area. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 534
With diagnostic alarm: OB40: OB40_2 OB40_3 OB40_4 OB40_1 OB82_1 OB82_2 OB82_1 OB82_2 OB82: incomming incomming outgoing outgo. lost Buffer memory proc. (FIFO): Buffer memory diag. (FIFO): Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 535
Bit 7 ... 4: 0 (fixed) 10 ... 15 0 (fixed) Data set 1, diagnostic alarm outgoing After the error correction, a diagnostic alarm takes place. outgoing Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Access Assignment Word Counter 1: Control word Word Counter 2: Control word Counter modules EPM-S600 ... EPM-S603 – control and status words ( 27) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 537
• 0b011 = rotary transducer 4-fold (connection to "A/pulse" input and "B/direction") • 0b100 = direction (pulse at "A/pulse" input and direction at "B/direction" input) Bit 7 ... 3: Reserved Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 538
Number of diagnostic bits output by the module per channel (here 0x00)) Number of channels of a module (here 0x02) 7 ... 15 0 (fixed) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
With every change of the encoder value, the time value of the timer is stored as 16-bit-s value together with the count value in the input area. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 540
More information can be found in the data sheet for your encoder. Value range: 0x00 ... 0x0F = 0 bit ... 15 bits Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 541
Information on this can be found in the data sheet for your encoder. 0 = standard code 1 = Gray code Bit 7 ... 5: Reserved Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 542
In the "monitor operation" mode, the module starts with the encoder evaluation. 0 (0x00) = inhibited 1 (0x01) = enabled Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 543
With diagnostic alarm: OB40: OB40_2 OB40_3 OB40_4 OB40_1 OB82_1 OB82_2 OB82_1 OB82_2 OB82: incomming incomming outgoing outgo. lost Buffer memory proc. (FIFO): Buffer memory diag. (FIFO): Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 544
Bit 0: Error in channel group 0 8 ... 15 0 (fixed) Data set 1, diagnostic alarm outgoing After the error correction, a diagnostic alarm takes place. outgoing Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
With every change of the encoder value, the time value of the timer is stored as 16-bit-s value together with the count value in the input area. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 546
Number of diagnostic bits output by the module per channel (here 0x00)) Number of channels of a module (here 0x02) 7 ... 15 0 (fixed) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Note that no more time stamp entries can be accepted once the FIFO memory is full. You should always establish the status of the FIFO memory before the transfer to ensure that your entries are accepted. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 548
Ticker value: Specify a time here in s at which the status of the outputs is to be accepted (value range: 0 ... 65535). Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 549
Number of diagnostic bits output by the module per channel (here 0x00)) Number of channels of a module (here 0x02) 7 ... 15 0 (fixed) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Here you can define the PWM output behaviour for the corresponding channel and start or stp the PWM output. PWM module EPM-S620 – control and status word ( 32) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 551
0x02 Byte 0: Here 0x02 CHERR Reserved 0x00 CH0ERR ... CH7ERR Reserved 0x00 DIAG_US Value of s ticker when diagnostics occur Bytes 0 ...3 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 554
Waiting time to be complied with until the next transmit ZNA (LOW byte) 0x00 request is executed. 0 ... 65535 [ms] (0x0000 ... 0xFFFF) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 555
ASCII value of the end character that is sent after a frame and 0x00 marks the end of a transmission. 0 ... 255 (0x00 ... 0xFF) Option 12, reserved 0x80 Reserved 0x00 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 556
• 0b10: 1.5 • 0b11: 2 Bit 7/6: Flow control 0b00 • 0b00: None • 0b01: Hardware • 0b10: XON/XOFF Option 2, ZNA (x 20 ms) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 557
In case of 3964(R), both partners must have different priorities. You have the following setting options: 0x00: Low 0x01: High Option 9 ... 12, reserved 0x80 Reserved 0x00 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 558
Bit 7 ... 0: Reserved 0x00 CH0ERR ... CH7ERR Bit 7 ... 0: Reserved 0x00 DIAG_US Value of s ticker when diagnostics occur 0x00 Bytes 0 ...3 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
• 0b10: 1.5 • 0b11: 2 Bit 7/6: Flow control 0b00 • 0b00: None • 0b01: Hardware • 0b10: XON/XOFF Option 2 / 3, ZNA Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 560
The data are exchanged simultaneously between the communication partners; transmission and reception can take place at the same time. Each communication partner must simultaneously actuate a receive path. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 561
Signal R(A) 0V, signal R(B) 5V This pre-assignment corresponds to the idle state (no transmitter active) in half duplex operation under RS485. Open-circuit monitoring is not possible. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 562
Waiting time to be complied with until the next transmit ZNA (LOW byte) 0x00 request is executed. 0 ... 65535 [ms] (0x0000 ... 0xFFFF) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 563
The data are exchanged simultaneously between the communication partners; transmission and reception can take place at the same time. Each communication partner must simultaneously actuate a receive path. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 564
Signal R(A) 0V, signal R(B) 5V This pre-assignment corresponds to the idle state (no transmitter active) in half duplex operation under RS485. Open-circuit monitoring is not possible. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 565
• 0b10: 1.5 • 0b11: 2 Bit 7/6: Flow control 0b00 • 0b00: None • 0b01: Hardware • 0b10: XON/XOFF Option 2, ZNA (x 20 ms) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 566
In case of 3964(R), both partners must have different priorities. You have the following setting options: 0x00: Low 0x01: High Option 9 ... 12, reserved 0x80 Reserved 0x00 Option 13, operating mode Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 567
Signal R(A) 0V, signal R(B) 5V This pre-assignment corresponds to the idle state (no transmitter active) in half duplex operation under RS485. Open-circuit monitoring is not possible. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 568
Bits 7 ... 5: 0 (fixed) CH1ERR ... CH7ERR Bit 7 ... 0: Reserved 0x00 DIAG_US Value of s ticker when diagnostics occur 0x00 Bytes 0 ...3 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Layer Function Protocol Application layer Modbus TCP Presentation layer Session layer Transport layer Network layer Data link layer (protection) Physical layer (bit transmission) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 570
20 Byte 20 Byte Depending of length Modbus TCP Port 502 Modbus TCP header Modbus User data 6 Byte max. 254 Byte [10-1] API structure Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 571
In case of words, the most significant bit is transmitted first. A Modbus slave is accessed via function codes Function codes ( 575) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Please observe that modules assigning more than 1 byte such as analog modules are stored from of a straight address onwards. Otherwise word access errors will be caused for Modbus TCP. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 576
1 word Response message: Modbus TCP Header Slave Function Address Value code Address Word Word 6 byte 1 byte 1 byte 1 word 1 word Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 577
Response message: Modbus TCP Header Slave Function Address code Address Word Mask Mask 6 byte 1 byte 1 byte 1 word 1 word 1 word Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Page 578
Number Data 1. Data 2. of bytes word word 6 byte 1 byte 1 byte 1 word 1 word 1 word max. 126 words Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
"Alarm Information Image" and saves the corresponding alarm data. In the I/O system 1000, it is made a distinction between diagnostic alarm and process alarm. For this purpose, the diagnostic image has one 64 bit wide field each (bit 0 = Modbus TCP slot 0 to bit 63 = Modbus TCP slot 63) for process alarm and diagnostic alarm.
Security Settings: All functions for the writing access to the Modbus TCP bus coupler can be protected with a password query. Software Update: This link is intended for future firmware updates. Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Go online (Engineer) Wire conductor measurement (2-, 3-, 4-wire conductor) I/O compound modules I/O system 1000 features Identifiers Identifiers of the process data objects (PDO) Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17...
Perhaps we have not succeeded in achieving this objective in every respect. If you have suggestions for improvement, please e-mail us feedback-docu@lenze.com Thank you very much for your support. Your Lenze documentation team...
Need help?
Do you have a question about the I/O system 1000 and is the answer not in the manual?
Questions and answers