Download Print this page

Honeywell SUPER TRADELINE L4064B Installation Manual page 2

Universal combination fan and limit controllers
Hide thumbs Also See for SUPER TRADELINE L4064B:

Advertisement

SWIVEL MOUNTING
L4064 may also be swivel-mounted. The swivel
bracket requires a 1-9/16 in. (39.7 mm) hole in the
plenum (Fig. 2).
1. Use bracket as a template to mark the location
of mounting holes in plenum. Drill or punch holes
for mounting screws.
2. Fasten the brackets in place with furnished
screws. Start the screws but do not tighten.
3. Insert element tube through bracket, straighten
controller, and fasten. Tighten the mounting screws
securely. It may be necessary to rotate the bracket
to tighten all screws securely.
32612A SWIVEL
Fig. 2 - Swivel mounting requires a 1-9/16 in. (39.7
mm) diameter mounting hole for element insertion.
RIGID BRACKET MOUNTING
!
WARNING
When mounting control on bracket, setscrew must
strike tube frame not sensing element to prevent
bypassing the safety limit function.
L4064 may be mounted using a rigid bracket. The
rigid bracket requires a hole 13/16 in. (20.6 mm)
diameter for element insertion (Fig. 3).
1. Use bracket as a template to mark the location of
mounting holes in plenum. Drill or punch holes for
mounting screws.
2. Fasten bracket in place with furnished screws.
Tighten the screws securely.
3. Insert element tube through bracket, straighten
controller and fasten by tightening setscrew. Be sure
screw strikes tube frame and does not strike sensing
element.
4. For replacement installations with existing 1 in.
(25.4 mm) diameter hole. SUPER TRADELINE
models are supplied with split steel bushings and wire
snap ring. Follow the instructions below for using the
steel bushing adapter.
STEEL BUSHING ADAPTER
1. Insert one-half of the split steel bushing (Fig. 4),
through the wire ring. It may be necessary to spread
the ring slightly.
2. Insert the other half of the steel bushing into the
ring making sure tabs and ears are at the same ends.
3. Place bushing assembly on element, ear end
first.
4. Holding bushing at seams, push firmly to the
control end of element.
BRACKET
REQUIRE 1-9/16
IN. (39.7 MM)
DIAMETER HOLE
IN PLENUM
FURNACE
11,220
PLENUM
5. Insert element tube with adapter through bracket,
straighten controller and fasten. Tighten setscrew. Be sure
screw strikes bushing not coiled bimetal sensing element.
Fig. 3 - Rigid bracket mounting requires a hole 13/
16 in. (20.6 mm) diameter for element insertion.
TAB
Fig. 4 - Using SUPER TRADELINE adapter.
WIRING
Disconnect power supply before beginning
installation to prevent electrical shock or equipment
damage.
All wiring must comply with local electrical codes and
ordinances or in the absence of local codes with the
National Electrical Code ANSI C1-1981-NFPA 70.
Follow burner or furnace manufacturer's instructions if
available; otherwise, see Fig. 10 and proceed as
follows.
The brass jumper is the breakaway type. It must be
removed when the limit is used in the low voltage
circuit. To remove jumper, break with a needlenose
pliers and remove completely, Once removed, it is
not replaceable. See Fig. 8 for location.
The slotted knockouts on the bottom of the case and
the strain relief bushing are provided to simplify the
installation procedure and to protect the wires.
1. To remove the slotted knockout(s), use a
needlenose pliers as shown in Fig. 5 and pull straight
down.
2. If cable is used, we recommend using a strain relief
bushing in the knockout (Fig. 6). Pass the wires through
bushing before connecting.
2
SETSCREW
RIGID BRACKET
L4064
HELICAL ELEMENT
EAR
IMPORTANT
FURNACE
PLENUM
11,205
2696A
69-0117-3

Advertisement