10 | REFRIGERANT PIPE
Table.5-2
Pipe name
Main pipe
Indoor unit main pipe
Indoor unit aux. pipe
Indoor unit main pipe branching pipe assembly
Indoor unit aux. pipe branching pipe assembly
Outdoor unit branching pipe assembly
Outdoor unit connective pipe
SBOX equipment
5.3 Size of joint pipes for indoor unit
Table.5-3
Size of joint pipes for R410A indoor unit
Indoor unit main pipe (inches)
Capacity of
indoor unit A
Low-pressure
High-pressure
(×100W)
gas side
gas side
A<56
Ø12.7
56≤A<166
Ø19.1
166≤A<230
Ø22.2
230≤A<330
Ø22.2
330≤A<460
Ø28.6
460≤A<660
Ø28.6
660≤A<920
Ø34.9
920≤A<1350
Ø41.3
1350≤A
Ø44.5
e.x.1: Refer to Fig.5-2, the capacity of downstream units to L2 is
71×2+140+28=310, i.e. low pressure gas pipe for L2 is Ø22.2, high
pressure gas pipe is Ø19.1, high pressure liquid pipe is Ø12.7.
5.4 Size of joint pipes for outdoor unit
Based on the following tables, select the diameters of outdoor unit main
connective pipe. When the main pipe accessory is larger on the indoor unit,
use the larger pipe accessory.
Table.5-4
Size of joint pipes for R410A outdoor unit
When the equivalent length of all liquid
pipes < 90m, the size of main pipe (inches)
Model
Low-pressure
High-pressure
gas side
gas side
8HP
Ø22.2
10HP
Ø22.2
12HP
Ø25.4
14~16HP
Ø28.6
18~22HP
Ø31.8
24HP
Ø34.9
26~32HP
Ø34.9
34~48HP
Ø41.3
50~64HP
Ø44.5
6 720 862 437 (2016/10)
Code (As per
the Fig. 5-2)
L1
L2~L13
a, b, ...r
A, B, C, D, E
I, II, III, IV
L, M
g1, g2, g3, G1
SB1, ...SB7
Liquid
Available
side
branching pipe
Ø9.5
Ø6.4
IDU-BJR01
Ø15.9
Ø9.5
IDU-BJR01
Ø19.1
Ø9.5
IDU-BJR02
Ø19.1
Ø12.7
IDU-BJR02
Ø22.2
Ø12.7
IDU-BJR03
Ø22.2
Ø15.9
IDU-BJR03
Ø28.6
Ø19.1
IDU-BJR04
Ø34.9
Ø19.1
IDU-BJR05
Ø38.1
Ø22.2
IDU-BJR05
The 1st
Liquid
branching pipe for
side
indoor unit
Ø19.1
Ø9.5
IDU-BJR02
Ø19.1
Ø12.7
IDU-BJR02
Ø19.1
Ø12.7
IDU-BJR03
Ø22.2
Ø15.9
IDU-BJR03
Ø28.6
Ø15.9
IDU-BJR03
Ø28.6
Ø15.9
IDU-BJR04
Ø28.6
Ø19.1
IDU-BJR04
Ø34.9
Ø19.1
IDU-BJR05
Ø38.1
Ø22.2
IDU-BJR05
Table.5-5
Size of joint pipes for outdoor unit (R410a)
When the equivalent length of all liquid
pipes ≥ 90m, the size of main pipe (inches)
Model
Low-pressure
High-pressure
gas side
gas side
8HP
Ø22.2
10HP
Ø22.2
12HP
Ø25.4
14~16HP
Ø28.6
18~22HP
Ø31.8
24HP
Ø34.9
26~32HP
Ø34.9
34~48HP
Ø41.3
50~64HP
Ø44.5
5.5 Branch pipes for outdoor unit
Table.5-6
Outdoor unit pipe connective opening dimension (inches)
Model
Low-pressure gas
side
8~12HP
Ø22.2
14, 16HP
Ø28.6
5.6 Multi pipe connection assembly and pipe
diameter for outdoor unit
Based on Table 5-7 select the branch pipe assembly for the outdoor unit.
Before installation, please read the Outdoor Unit Branching Pipe Installation
Manual carefully.
Table.5-7
Outdoor unit branch pipe assembly (Illustration)
Outdoor
Illustration
unit Qty.
2 units
g2
g1
L
Main pipe
3 units
g3
g2
g1
Main pipe
M
L
G1
4 units
g4
g3
g2
g1
Main pipe
N
M
L
G1
G2
5.7 Example
1) Take (10+12+16) HP for the three modules as an example to clarify the
pipe selection.
2) Take Fig.5-2 as an example, providing that the equivalent length of all
pipes in this system is larger than 90m.
Table.5-8
Indoor unit aux. pipe (between branch joint and branch
Capacity
joint/SB) (inches)
of indoor unit A
(×100W)
Gas side
A<160
Ø15.9
Indoor unit aux. pipe (between indoor unit and branch joint/SB) (inches)
Capacity
When branching
of indoor unit A
pipe's length ≤10m
(×100W)
Gas side
Liquid side
A<56
Ø12.7
Ø6.4
160≥A≥56
Ø15.9
Ø9.5
RDCI Series – All DC Inverter Outdoor Units
The 1st
Liquid
branching pipe for
side
indoor unit
Ø19.1
Ø12.7
IDU-BJR02
Ø19.1
Ø12.7
IDU-BJR02
Ø19.1
Ø15.9
IDU-BJR03
Ø22.2
Ø15.9
IDU-BJR03
Ø28.6
Ø19.1
IDU-BJR03
Ø28.6
Ø19.1
IDU-BJR04
Ø28.6
Ø22.2
IDU-BJR04
Ø34.9
Ø22.2
IDU-BJR05
Ø38.1
Ø25.4
IDU-BJR05
High-pressure gas
Liquid side
side
Ø19.1
Ø12.7
Ø22.2
Ø15.9
Outdoor unit
Parallel connect with
connective pipe
the branching pipes
diameter
g1, g2:
8~12HP:
L:
Ø22.2/Ø19.1/Ø12.7
ODU-BJR02
14, 16HP:
Ø28.6/Ø22.2/Ø15.9
g1, g2, g3:
8~12HP:
Ø22.2/Ø19.1/Ø12.7
L+M:
14, 16HP:
ODU-BJR03
Ø28.6/Ø22.2/Ø15.9
G1: Ø34.9/Ø28.6/
Ø19.1
g1, g2, g3, g4:
8~12HP:
Ø28.2/Ø19.1/Ø12.7
L+M+N:
14, 16HP:
ODU-BJR04
Ø28.6/Ø22.2/Ø15.9
G1: Ø34.9/Ø28.6/Ø19.1
G2: Ø41.3/Ø34.9/Ø22.2
The branch pipe
assembly of indoor
unit aux. pipe
Liquid side
Ø9.5
IDU-BJR01
When branching pipe's length>10m
Gas side
Liquid side
Ø15.9
Ø9.5
Ø19.1
Ø12.7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rdci10/28-3Rdci8/25-3Rdci12/33-3Rdci16/45-3Rdci14/40-3