7.3 The nameplate of SBOX02-1
TRANS
RED
BLUE
Y/G
T2C1 T2C2
P Q E
POWER IN
TO INDOOR2
7.4 The nameplate of SBOX02E-1
TRANS
RED
BLUE
Y/G
T2C1 T2C2
XT2
POWER IN
Table.7-1
Model of SBOX
SBOX02-1
SBOX04-1
Maximum
capacity
16kW
of single group
pipe
Maximum indoor
units quantity of
4
single group pipe
Maximum
28kW
capacity of SB
Downstream of the
largest length
NOTE
RDCI Series – All DC Inverter Outdoor Units
M-O
M-I
CN13
P Q E
P Q E
TO INDOOR1
TO OUTDOOR
Fig. 7-3
M-O
M-I
CN13
P Q E
P Q E
TO INDOOR
TO OUTDOOR
Fig. 7-4
SBOX06-1
SBOX02E-1
SBOX04E-1
___________
1
45kW
28kW
56kW
40m
Single group pipe means one connecting liquid pipe and one
connecting gas pipe.
If you disable auto mode function you can connect up to 4 units via
an SBOX. If auto mode is selected then only one indoor unit can be
connected.
Indoor units connected together on the same connection ports at
the SBOX, auto mode cannot be selected. This will conflict modes
and cause error.
Prior to installing the SBOX, ensure a suitable location is selected, as
an SBOX will create operational noises.
The SBOX must be installed horizontally and level.
There must be at least 1m distance between an SBOX and a branch
joint pipe assembly.
There will be 30 seconds auto-checking function after the indoor
and outdoor units have been activated.
Indoor units must be manually addressed.

8. ELECTRIC WIRING

8.1 Terminal base function
L1
L2
L3
To 380-415V 3N~ 50Hz
Outdoor units
Indoor units
Network
centralised
centralised
accounting
monitoring
controls
ELECTRIC WIRING | 15
N
Fig. 8-1
Indoor units
Outdoor units
communication
communication
Fig. 8-2
6 720 862 437 (2016/10)