Fig. 23. Commission warning.
NOTE: Clicking the Home, Back or Monitor button will exit
Commissioning mode and display the Home page.

Password

You must enter the R7999 Commission password into the
system (Fig. 24). The password consists of a minimum of four
characters/numbers and a maximum of ten characters/
numbers.
Fig. 24. Commission password.
To change the R7999 Commission password, proceed as
follows:
1. Select the Set Password button on the Commissioning
Warning screen.
2. Enter the current password in the Commission
Password field. (The factory default password is
"password".)
3. Press OK. The system must be successfully connected
in order to change the password.
4. Enter a new password in the New Password field.
5. Press OK.
NOTE: The password is not case sensitive. Make sure you
write down your new password before you press OK.
Once you have pressed this button you cannot enter
the system without the password.
Fig. 25. Commissioning login to set password.

Commission Configuration

The Commission Configuration screen is used to:
• Identify the configuration of the system you want to
commission, for example, dual fuel system with a FGR or a
single fuel system, etc.
• Begin configuration of the actuators.
• Allow the user to set System Parameters.
• Load a curve from the S7999B flash.
• Begin configuration of the modulation curve.
This screen (Fig. 26) selects the type (Base Configuration) of
ControLinks™ Control System to be configured. The Base
Configuration defines the number of actuators connected to
the ControLinks™ controller. After the Base Configuration is
chosen, the corresponding actuators are enabled as Endpoint
Configuration options.
Selecting the Unconfigured Base Configuration sets all the
ControLinks™ Control parameters back to the factory default
settings. All user configurable data stored in the
ControLinks™ Control will be deleted by selecting this option.
A warning message is displayed to confirm this selection.
Single Fuel configuration enables the Air and Fuel 1 actuator
buttons in the Endpoint Configuration options. Single Fuel with
FGR enables the Air, Fuel1 and FGR buttons. Dual Fuel
enables the Air, Fuel1 and Fuel2 buttons. Dual Fuel with FGR
enables all four actuator buttons. Begin configuring the
actuators by selecting the enabled buttons.
25
S7999B SYSTEM DISPLAY
65-0283—2