The switch-fuse has not operated even
though a fuse has blown.
Circuit-breaker cubicle
The cable compartment door will not
open.
The circuit-breaker will not go to the
closed position.
Instrument Transformers
Secondary measurements from the
current transformers are not possible.
ABB
Uniswitc h Operation and
Maintenanc e Manual
Check that the fuse is correctly fitted so that the trip pin
indicator is pointing upwards.
Check that the switch is in the earthed position.
Check the interlocking selector is in the 'Door open'
position.
Remove the key from the circuit-breaker before
opening or closing the door.
Ensure that the closing spring is fully charged, and
that the interlocking coil is not energised.
Check that the circuit-breaker key is in place and
turned to the correct operating position.
Check that the circuit-breakers auxiliary voltage plug
is properly locked into the socket.
Check that the control pin is on its position (HAD-
US).
Check that all shorting links on the secondary
terminals of the current transformers have been
removed.
Check the connections.
53
UNI S14GB 05-02