Circuit-Breaker Opening - ABB Uniswitch Operation And Maintenance Manual

Medium voltage switchgear, 12 kv, 17.5 kv, 24 kv, 630 a and 1250 a
Table of Contents

Advertisement

4.4.4.4 Circuit-breaker opening

Instructions
Figure 4.21
ABB
Uniswitch Operation and
Maintenance Manual
For manual opening, press pushbutton (43.1) (Figure 4.20). When there
is a shunt opening release, the operation can also be carried out by
remote control by means of a control circuit. The indicator (43.3) (Figure
4.20) shows that opening has been accomplished.
An additional control mechanism fitted in the door of the circuit-breaker
compartment enables mechanical operation of the circuit-breaker with
the door closed and with the withdrawable part in either position.
Press the relative mechanical pushbutton (60.6), having previously
turned knob (60.12) anticlockwise to the stop, if the withdrawable
part is in the service position.
Observe the switch position indicator. Detailed information about
installation and maintenance can be found in instruction manual
647016.
36
UNI S14GB 05-02