ABB Uniswitch Operation And Maintenance Manual page 44

Medium voltage switchgear, 12 kv, 17.5 kv, 24 kv, 630 a and 1250 a
Table of Contents

Advertisement

Checkpoints
Maintenance
instructions
Other relevant
instruction manuals
References
ABB
Uniswitc h Operation and
Maintenanc e Manual
Check that there are no visible signs of, or damage from, partial
discharge.
There should also not be any visible signs of connection joints
overheating.
All components should perform perfectly and any faulty components
are to be replaced.
Maintenance serves to preserve trouble-free operation and achieve the
longest possible working life of the switchgear.
It comprises the following closely related activities:
Inspection: Determination of the actual condition
Servicing: Measures to preserve the specified condition
Repair: Measures to restore the specified condition
The
inspection
and
equipment/components (e.g. parts subjects to wear) are determined by
fixed criteria, such as switching frequency, length of service and number
of short-circuit breaking operations. On the other hand, for other parts
the length of the intervals may depend, for example, on the different
modes of operation in individual cases, the degree of loading, and also
environmental influences (including pollution and aggressive air).
Time intervals for maintenance work to be carried out always depend on
the operating conditions of the switchgear, and mainly on the mode of
operation, the number of rated and short-circuit current switching
operations, ambient temperature, pollution etc.
For the Uniswitch switchgear under normal service conditions
maintenance intervals and measures according to Table 5.1
recommended. In more demanding conditions (for example areas with
high pollution levels) three year intervals are recommended for all
maintenance measures.
The
switch-disconnector's
maintenance free and do not require any lubrication.
For circuit-breakers, refer to the Sace/Calor Emag Maintenance
Instructions for Circuit-breaker.
The operation of all protection relays should be checked in accordance
with the manufacturer's instructions.
The following operating instructions must also be followed, together with
this instruction manual in the individual cases concerned:
Vacuum circuit-breaker: type VD4
SF
circuit-breaker: type HD4
6
If necessary, further details can be taken from the technical
documentation for the switchgear installation (including, for example,
any special operating conditions agreed on).
servicing
intervals
1-
and
2-spring
for
some
of
the
are
mechanisms
are
BA 352E
647016
41
UNI S14GB 05-02