Medium voltage switchgear, 12 kv, 17.5 kv, 24 kv, 630 a and 1250 a
Table of Contents

Advertisement

2.2 Internal arc classification

Data
Standards
ABB
Uniswitc h Operation and
Maintenanc e Manual
Resistance to internal arc faults is as follows:
Table 2.2 Fault withstand capacity.
12 kV
17.5 kV
24 kV
The switchgear units have been tested according to IEC 60298
Standards (appendix AA, class A, criteria 1 to 6).
!
Uniswitch switchgear has to be installed in closed rooms
suitable for electrical equipment. This means the
accessibility must be restricted to authorised personnel
only.
The rear side of the switchgear is not accessible. Rear-side
accessibility must be discussed with the manufacturer.
20 kA
20 kA
20 kA
1s
1s
1s
6
UNI S14GB 05-02