Connecting; Power Circuit - ABB ATS021 Installation And Operating Instructions Manual

Automatic transfer switch
Table of Contents

Advertisement

Installation and operating instructions, ATS021

6. Connecting

Only an authorised electrician may perform the electrical installation and maintenance
of automatic transfer switches. Do not attempt any installation or maintenance actions
when an automatic transfer switch is connected to the electrical mains. Before starting
work, make sure that the circuit breaker is de-energised.

6.1 Power circuit

Operating voltage, setting with DIP-switches
Main voltage:
208Vac - 480Vac (± 20%)
Phase voltage:
120Vac - 277Vac (± 20%)
Frequency:
50Hz - 60Hz (± 10%)
DIP
Phase setting with
If the automatic transfer switch ATS021 is used without neutral (three-phase connection), the external
transformer must be used. The transformer will drop the main voltage to the phase voltage level. Neutral
has to be connected when using a single phase connection.
Figure 6.1
The external transformer must be used, if the automatic transfer switch ATS021 is used
without neutral (three-phase connection). Neutral has to be connected when using a
single phase connection.
22
1SDH000759R0002, L4106
switches: Single phase or Three-phase (default).
6. Connecting

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents